ELECTRICAL DATA
RYS+FTYS20B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTYS20BVMB
RYS20BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
13.0
15
38
2.91
25
0.35
18
0.20
3D040467
RYS+FTYS25B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTYS25BVMB
RYS25BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
13.0
15
52
4.01
25
0.35
18
0.20
3D040468
RYS+FTYS35B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTYS35BVMB
RYS35BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
13.0
15
71
5.51
25
0.35
18
0.20
3D040469
RYS+FTYS50B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTYS50BVMB
RYS50BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
72
6.92
53
0.18
40
0.16
3D040875
RYS+FTYS60B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTYS60BVMB
RYS60BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
72
8.86
53
0.24
43
0.16
3D040875
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RHz
: Rated operating frequency (Hz)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps
W
: Rated motor output (W)
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
•
Pair Application
•
R-410A
•
RYS20,25,35,50,60BVMB
2
Specifications
1
2
5
•
Split - Sky Air
•
Outdoor Units