Outdoor unit installation drawings
Wrap the installation pipe with the
finishing tape from bottom to top
Model
50 class
60 class
Max. allowable length
30m
Max. allowable height
20m
Additional refrigerant required
for refrigerant pipe exceeding
10 m in length.
20 g/m
Gas pipe
O.D. 12.7 mm
Liquid pipe
O.D. 6.4 mm
* Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
In sites with poor drainage, use block
bases for outdoor unit. Adjust foot
height until the unit is leveled. Otherwise,
water leakage or pooling of water may
occur.
Where there is a danger of the unit falling, use foot
bolts, or wires.
Allow space for piping and electrical
servicing.
Service lid
Foot bolt-hole
centres
Foot bolt-hole centres
From unit’s side
250 mm from wall
RYS50,60B
580 mm
120 mm
330 m
m
•
Pair Application
•
R-410A
•
RYS20,25,35,50,60BVMB
10
Installation
1
10
18
•
Split - Sky Air
•
Outdoor Units