RYS+FTYS60B
Cooling capacity
230V [50Hz]
AFR
16.4
BF
0.29
Indoor
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
6.06
3.97
1.77
5.91
3.90
1.87
5.76
3.83
1.96
5.70
3.80
2.00
5.61
3.76
2.06
5.46
3.69
2.15
16.0
22
6.22
4.00
1.80
6.07
3.93
1.89
5.92
3.86
1.99
5.86
3.83
2.02
5.77
3.79
2.08
5.62
3.72
2.18
18.0
25
6.37
4.03
1.82
6.22
3.96
1.92
6.07
3.89
2.01
6.01
3.87
2.05
5.92
3.82
2.11
5.77
3.75
2.20
19.0
27
6.45
4.05
1.84
6.30
3.98
1.93
6.15
3.91
2.03
6.09
3.88
2.06
6.00
3.84
2.12
5.85
3.77
2.22
22.0
30
6.68
4.10
1.87
6.53
4.03
1.97
6.38
3.96
2.06
6.32
3.93
2.10
6.23
3.89
2.16
6.08
3.82
2.25
24.0
32
6.84
4.14
1.90
6.69
4.07
2.00
6.54
4.00
2.09
6.48
3.97
2.13
6.39
3.93
2.19
6.24
3.86
2.28
Heating capacity
230V [50Hz]
AFR
17.5
Indoor
Outdoor temperature (°CWB)
EDB
-15
-10
-5
0
6
10
(°C)
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
16.0
3.51
1.50
4.36
1.61
5.21
1.71
6.05
1.81
7.07
1.94
7.75
2.02
18.0
3.48
1.58
4.32
1.68
5.17
1.78
6.02
1.89
7.04
2.01
7.71
2.10
20.0
3.44
1.65
4.29
1.76
5.14
1.86
5.98
1.96
7.00
2.09
7.68
2.17
21.0
3.43
1.69
4.27
1.79
5.12
1.90
5.97
2.00
6.98
2.13
7.66
2.21
22.0
3.41
1.73
4.25
1.83
5.10
1.94
5.95
2.04
6.97
2.17
7.64
2.25
24.0
3.37
1.80
4.22
1.91
5.07
2.01
5.91
2.12
6.93
2.24
7.61
2.32
3D040898
SYMBOLS
AFR:
Air flow rate
(m
3
/min)
BF:
Bypass factor
EWB:
Entering wet bulb temp.
(°CWB)
EDB:
Entering dry bulb temp.
(°CDB)
TC:
Total capacity
(kW)
SHC:
Sensible heating capacity
(kW)
PI:
Power input
(kW)
NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat
2.
Shows nominal cooling capacities and power input
3. TC, PI and SHC must be calculated by interpolation using the figures in the
above tables. (Figures out of the tables should not be used for calculation.)
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m
3
/min) x (1-BF) x (DB-EDB)
Add SHC* to SHC.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0 m
6. Air flow rate (AFR) and Bypass factor (BF) are taburated above.
•
Pair Application
•
R-410A
•
RYS20,25,35,50,60BVMB
3
Capacity tables
1
3
8
•
Split - Sky Air
•