background image

4

Piping Works And Flaring Technique

Do not use contaminated or damaged copper tubing. If any
piping, evaporator or condenser had been exposed or had been
opened for 15 seconds or more, vacuum the system. Generally,
do not remove plastic, rubber plugs and brass nuts from the
valves, fittings, tubings and coils until it is ready for connection.

If any brazing work is required, ensure that the nitrogen gas is
passed through piping and joints while the brazing work is
being done. This will eliminate soot formation on the inside
walls of the copper tubings.

Cut the pipe stage by stage, advancing the blade of  pipe cutter
slowly. Extra force and deep cut will cause more
distortion of pipe and therefore extra burr.

Remove burrs from cut edges of pipes with a remover as shown
in Fig. R. This will avoid unevenness on the flare faces which
will cause gas leak. Hold the pipe on top position and burr
remover at lower position to prevent metal chips from entering
the pipe.

Insert the flare nuts mounted on the connection parts of both
indoor and outdoor unit, into the copper pipes.
The exact length of pipe protruding from the face of the flare
die is determined by the flaring tool.

Fix the pipe firmly on the flare die. Match the centers of both
the flare die and the flaring punch, and tighten flaring punch
fully.

1/4t

Cutting Copper Tube

Copper Tube

Swaging Block

Ø Tube, D

A (mm)

Inch

mm

Imperial

Rigid

1/4"

6.35

1.3

0.7

3/8"

9.52

1.6

1.0

1/2"

12.70

1.9

1.3

5/8"

15.88

2.2

1.7

3/4"

19.05

2.5

2.0

Piping Connection To The Units

Align the center of the piping and sufficiently tighten the flare
nut with fingers.
Finally, tighten the flare nut with torque wrench
until the wrench clicks.
When tightening the flare nut with the torque wrench,
ensure that the direction for tightening follows the arrow on
the wrench.

The refrigerant pipe connection are insulated by polyurethane
(ARMAFLEX type or similar).

Pipe Size, mm (in)

Torque (Nm)

6.35 (1/4)

18

9.53 (3/8)

42

12.7 (1/2)

55

15.88 (5/8)

65

19.05 (3/4)

78

Spanar

Torque Wrench

Indoor Piping

Flare Nut

Flared Tube

Flare Joint

Fig. R

Remove Burr

Copper Tube

Summary of Contents for RY100CV1M

Page 1: ...0CV1M RY80CV1M FDYM90CV1M FDYB90CV1M RY90CV1M FDYM90CV1M FDYB90CV1M RY90CY1M FDYM100CV1M RY100CV1M FDYM125CV1M FDYB125CV1M RY125CV1M FDYM125CV1M FDYB125CV1M RY125CY1M FDYM140CV1M FDYB140CV1M RY140CY1M...

Page 2: ...8 8 4 2 5 3 9 9 4 8 4 FDYM90CV1M 359 999 956 917 408 5 378 541 256 173 306 70 5 160 5 248 220 0 FDYB90CV1M 14 1 39 3 37 6 36 1 16 1 14 9 21 3 10 1 6 8 12 0 2 8 6 3 9 8 8 7 FDYM100CV1M 371 2 1312 1264...

Page 3: ...B C D E F G H I J K L M N O RY60CV1M 855 628 328 513 182 44 93 149 101 113 603 126 164 17 49 33 7 24 7 12 9 20 0 7 1 1 7 3 7 5 9 4 0 4 4 23 7 5 0 6 4 0 7 1 9 RY71CV1M 855 730 328 513 182 44 93 149 10...

Page 4: ...M N P RY90CV1M RY90CY1M 1030 850 400 390 414 827 72 196 91 488 448 141 5 746 5 82 RY100CV1M RY125CV1M 40 6 33 5 15 7 15 4 16 3 32 6 2 8 7 7 3 6 19 2 17 6 5 6 29 4 3 2 RY125CY1M RY140CY1M All dimensio...

Page 5: ...l A B C D E F G H J K L M N RY160CY1M 1030 850 400 448 746 5 320 25 50 85 40 141 5 20 60 40 6 33 5 15 7 17 6 29 4 12 6 1 0 2 0 3 3 1 6 5 6 0 8 2 4 All dimensions are in mm in J H C F K K B G A L E L M...

Page 6: ...OM WARNING Installation and maintenance should be performed by qualified persons who are familiar with local code and regulation and experienced with this type of appliance All field wiring must be in...

Page 7: ...allation provide clearance for servicing ease as shown in diagram and table below C mm inch D mm inch FDYM30CV1M FDYB30CV1M FDYM40CV1M FDYB40CV1M 200 500 FDYM60CV1M 7 9 19 7 FDYB60CV1M FDYM71CV1M FDYB...

Page 8: ...V1M FDYM71CV1M FDYM80CV1M Data FDYB30CV1M FDYB40CV1M FDYB60CV1M FDYB71CV1M Maximum Length Am ft 12 39 4 12 39 4 15 49 2 15 49 2 15 49 2 Maximum Elevation B m ft 5 16 4 5 16 4 8 26 2 8 26 2 8 26 2 Maxi...

Page 9: ...hips from entering the pipe Insert the flare nuts mounted on the connection parts of both indoor and outdoor unit into the copper pipes The exact length of pipe protruding from the face of the flare d...

Page 10: ...Power Supply Cable N 4WV OF COMP L N N COMP OF 4WV FDYM80CV1M RY80CV1M There must be a all pole switch with a minimum 3 mm contact gap and fuse circuit breaker as recommended in the fixed installation...

Page 11: ...There must be a all pole switch with a minimum 3 mm contact gap and fuse circuit breaker as recommended in the fixed installation circuits FDYM90CV1M FDYB90CV1M RY90CY1M FDYM125CV1M FDYB125CV1M RY125...

Page 12: ...r manifold gauge with the vacuum pump Connect the manifold gauge to the service port of the 3 ways valve Start the vacuum pump Check the low pressure manifold gauge until it indicate 0 9 bar The evacu...

Page 13: ...linder valve Disconnect the manometer and the gas cylinder Place back the service port cap Indoor FDYM30CV1M FDYM40CV1M FDYM60CV1M FDYM71CV1M FDYM80CV1M FDYB30CV1M FDYB40CV1M FDYB60CV1M FDYB71CV1M Out...

Page 14: ...he installer 1 Charging procedures Single phase compressors Evacuate the system to 500 microns Hg 67Pa To reduce evacuation time use short large diameter hoses and connect to unrestricted service port...

Page 15: ...mooth drainage of water Check that 1 Condenser fan is running with warm air blowing off the condensing unit 2 Evaporator blower is running and discharge cool air 3 The remote controller incorporates a...

Page 16: ...for any faulty contacts caused by loose connections foreign matters etc Tighten the wires onto the terminal block if necessary 1 No maintenance needed if the refrigerant circuit remain sealed However...

Page 17: ...5 Discharge air flow has bad odor 6 Condensation on the front air grille of the indoor unit 7 Water flowing out from the air conditioner unit 8 Hissing air flow sound from the air conditioner unit du...

Reviews: