background image

18 Energy saving and optimum operation

Installer and user reference guide

50

RXYSQ4~6TAY1B

VRV IV-S system air conditioner

4P482257-1 – 2017.03

18

Energy saving and optimum
operation

Observe  the  following  precautions  to  ensure  the  system  operates
properly.

▪ Adjust  the  air  outlet  properly  and  avoid  direct  air  flow  to  room

inhabitants.

▪ Adjust  the  room  temperature  properly  for  a  comfortable

environment. Avoid excessive heating or cooling.

▪ Prevent  direct  sunlight  from  entering  a  room  during  cooling

operation by using curtains or blinds.

▪ Ventilate  often.  Extended  use  requires  special  attention  to

ventilation.

▪ Keep doors and windows closed. If the doors and windows remain

open,  air  will  flow  out  of  your  room  causing  a  decrease  in  the
cooling or heating effect.

▪ Be careful not to cool or heat too much. To save energy, keep the

temperature setting at a moderate level.

▪ Never place objects near the air inlet or the air outlet of the unit. It

may cause deterioration in the effect or stop the operation.

▪ Turn off the main power supply switch to the unit when the unit is

not used for longer periods of time. If the switch is on, it consumes
electricity.  Before  restarting  the  unit,  turn  on  the  main  power
supply switch 6 hours before operation to ensure smooth running.
(Refer to "Maintenance" in the indoor unit manual.)

▪ When  the  display  shows 

  (time  to  clean  the  air  filter),  ask  a

qualified  service  person  to  clean  the  filters.  (Refer  to
"Maintenance" in the indoor unit manual.)

▪ Keep  the  indoor  unit  and  user  interface  at  least  1  m  away  from

televisions, radios, stereos, and other similar equipment. Failing to
do so may cause static or distorted pictures.

▪ Do  not  place  items  under  the  indoor  unit,  they  may  be  damaged

by water.

▪ Condensation  may  form  if  the  humidity  is  above  80%  or  if  the

drain outlet gets blocked.

This  heat  pump  system  is  equipped  with  advanced  energy  saving
functionality.  Depending  on  the  priority,  emphasises  can  be  put  on
energy saving or comfort level. Several parameters can be selected,
resulting  in  the  optimal  balance  between  energy  consumption  and
comfort for the particular application.

Several patterns are available and roughly explained below. Contact
your installer or dealer for advice or to modify the parameters to the
needs of your building.

Detailed  information  is  given  for  the  installer  in  the  installation
manual. He can help you to realize the best balance between energy
consumption and comfort.

18.1

Available main operation methods

Basic

The refrigerant temperature is fixed independent from the situation. It
corresponds  to  the  standard  operation  which  is  known  and  can  be
expected from/under previous VRV systems.

Automatic

The refrigerant temperature is set depending on the outdoor ambient
conditions.  As  such  adjusting  the  refrigerant  temperature  to  match
the  required  load  (which  is  also  related  to  the  outdoor  ambient
conditions).

E.g., when your system is operating in cooling, you do not need as
much  cooling  under  low  outdoor  ambient  temperatures  (e.g.,  25°C)
as under high outdoor ambient temperatures (e.g., 35°C). Using this

idea,  the  system  automatically  starts  increasing  its  refrigerant
temperature,  automatically  reducing  the  delivered  capacity  and
increasing the system's efficiency.

Hi-sensible/economic (cooling/heating)

The  refrigerant  temperature  is  set  higher/lower  (cooling/heating)
compared to basic operation. The focus under high sensible mode is
comfort feeling for the customer.

The  selection  method  of  indoor  units  is  important  and  has  to  be
considered as the available capacity is not the same as under basic
operation.

For  details  concerning  to  Hi-sensible  applications,  please  contact
your installer.

18.2

Available comfort settings

For  each  of  above  modes  a  comfort  level  can  be  selected.  The
comfort  level  is  related  to  the  timing  and  the  effort  (energy
consumption)  which  is  put  in  achieving  a  certain  room  temperature
by  temporarily  changing  the  refrigerant  temperature  to  different
values in order to achieve requested conditions more quickly.

▪ Powerful

▪ Quick

▪ Mild

▪ Eco

19

Maintenance and service

NOTICE

Never  inspect  or  service  the  unit  by  yourself.  Ask  a
qualified service person to perform this work.

WARNING

Never replace a fuse with a fuse of a wrong ampere ratings
or  other  wires  when  a  fuse  blows  out.  Use  of  wire  or
copper wire may cause the unit to break down or cause a
fire.

CAUTION

Do not insert fingers, rods or other objects into the air inlet
or  outlet.  Do  not  remove  the  fan  guard.  When  the  fan  is
rotating at high speed, it will cause injury.

CAUTION

Pay attention to the fan.

It is dangerous to inspect the unit while the fan is running.

Be  sure  to  turn  off  the  main  switch  before  executing  any
maintenance task.

CAUTION

After  a  long  use,  check  the  unit  stand  and  fitting  for
damage. If damaged, the unit may fall and result in injury.

NOTICE

Do  not  wipe  the  controller  operation  panel  with  benzine,
thinner,  chemical  dust  cloth,  etc.  The  panel  may  get
discoloured  or  the  coating  peeled  off.  If  it  is  heavily  dirty,
soak  a  cloth  in  water-diluted  neutral  detergent,  squeeze  it
well  and  wipe  the  panel  clean.  Wipe  it  with  another  dry
cloth.

Summary of Contents for RXYSQ5TAY1B

Page 1: ...Installer and user reference guide VRV IV S system air conditioner English Installer and user reference guide VRV IV S system air conditioner RXYSQ4TAY1B RXYSQ5TAY1B RXYSQ6TAY1B...

Page 2: ...6 4 5 Using the stop valve and service port 17 6 4 6 To remove the pinched pipes 18 6 4 7 To connect the refrigerant piping to the outdoor unit 19 6 4 8 To connect the refrigerant branching kit 20 6 5...

Page 3: ...not work 53 20 2 3 Symptom The fan strength does not correspond to the setting 54 20 2 4 Symptom The fan direction does not correspond to the setting 54 20 2 5 Symptom White mist comes out of a unit...

Page 4: ...ste batteries are disposed of correctly you will help to prevent potential negative consequences for the environment and human health 1 3 For the installer 1 3 1 General If you are not sure how to ins...

Page 5: ...ave to operate WARNING Always recover the refrigerant Do NOT release them directly into the environment Use a vacuum pump to evacuate the installation NOTICE After all the piping has been connected ma...

Page 6: ...tor Failure to do so may cause electric shock or fire When installing the earth leakage protector make sure it is compatible with the inverter resistant to high frequency electric noise to avoid unnec...

Page 7: ...hat you have to do after the box with the outdoor unit is delivered on site It contains information about Unpacking and handling the units Removing the accessories from the units Keep the following in...

Page 8: ...utdoor installation and aimed for air to air heat pump applications Specification RXYSQ4 6 Capacity Heating 14 2 18 0 kW Cooling 12 1 15 5 kW Ambient design temperature Heating 20 15 5 C WB Cooling 5...

Page 9: ...g works where a lot of dust is created the unit must be covered Choose the installation location with sufficient place for carrying the unit in and out of the site 5 2 1 Installation site requirements...

Page 10: ...the outdoor unit is exposed to direct sea winds install a windbreaker Height of windbreaker 1 5 height of outdoor unit Mind the service space requirements when installing the windbreaker a b c d c d...

Page 11: ...d leak The unit of measurement of the concentration is kg m3 the weight in kg of the refrigerant gas in 1 m3 volume of the occupied space Compliance to the local applicable regulations and standards f...

Page 12: ...6 4 mm 1 4 9 5 mm 3 8 12 7 mm 1 2 Annealed O 0 80 mm t 15 9 mm 5 8 Annealed O 0 99 mm 19 1 mm 3 4 22 2 mm 7 8 Half hard 1 2H 0 80 mm a Depending on the applicable legislation and the unit s maximum w...

Page 13: ...ge 12 Refnet joint at first branch counting from outdoor unit When using refnet joints at the first branch counted from the outdoor unit side choose from the following table in accordance with the cap...

Page 14: ...imum height difference indoor indoor Examples H2 Limit 15 m 15 m Maximum height difference outdoor BP Example 2 H3 Limit N A 30 m Maximum height difference BP BP Example 2 H4 Limit N A 15 m Maximum he...

Page 15: ...r and all indoors 600 m If the total transmission wiring exceeds these limits it may result in communication error 6 Installation 6 1 Overview Installation This chapter describes what you have to do a...

Page 16: ...in order to avoid ice accumulation Prepare a water drainage channel around the foundation to drain waste water surrounding the unit Avoid drain water flowing over the footpath so that it does not beco...

Page 17: ...egardless of the period INFORMATION Do NOT open the refrigerant stop valve before checking the refrigerant piping When you need to charge additional refrigerant it is recommended to open the refrigera...

Page 18: ...ing the service port make sure to tighten the service port cover securely For the tightening torque refer to the table below Check for refrigerant leaks after tightening the service port cover Tighten...

Page 19: ...a with screw b a b 2 Choose a piping route a b c or d a b c d 3 If you have chosen the downwards piping route Drill a 4 and remove the knockout hole b Cut out the slits c with a metal saw c c b a 4 6...

Page 20: ...ll initialise This means that they will close Leak test and vacuum drying of field piping and indoor units is impossible when this happens Therefore there will be explained 2 methods for initial insta...

Page 21: ...est for leaks by applying a bubble test solution to all piping connections 3 Discharge all nitrogen gas NOTICE Make sure to use a recommended bubble test solution from your wholesaler Do not use soap...

Page 22: ...perly NOTICE Be sure to turn on the power 6 hours before operation in order to have power running to the crankcase heater and to protect the compressor NOTICE If operation is performed within 12 minut...

Page 23: ...refrigerant in manual additional refrigerant charge mode instructions Charging refrigerant in manual additional refrigerant charge mode The remaining additional refrigerant charge can be charged by op...

Page 24: ...onsists of the following stages 1 Making sure the power supply system complies with the electrical specifications of the units 2 Connecting the electrical wiring to the outdoor unit 3 Connecting the e...

Page 25: ...tor Install power cables at least 1 metre away from televisions or radios to prevent interference Depending on the radio waves a distance of 1 metre may not be sufficient WARNING After finishing the e...

Page 26: ...ical wiring on the outdoor unit NOTICE Follow the wiring diagram delivered with the unit located at the inside of the service cover Make sure the electrical wiring does NOT obstruct proper reattachmen...

Page 27: ...e as shown in figure below a b c d e a Liquid pipe b Gas pipe c Insulator d Transmission wiring F1 F2 e Finishing tape 6 9 2 To close the outdoor unit NOTICE When closing the outdoor unit cover make s...

Page 28: ...SET For field setting BS3 RETURN For field setting BS4 TEST For test operation BS5 RESET For resetting the address when the wiring is changed or when an additional indoor unit is installed Display Th...

Page 29: ...lay Mode 2 You can change the value of setting 2 8 Te target temperature during cooling operation to 4 8 C as follows Action Button display 1 Start from the default situation 2 Select mode 2 BS1 5 s 3...

Page 30: ...ecked again through this monitoring settings For the content or reason behind the malfunction code see 11 3 Solving problems based on error codes on page 38 where most relevant malfunction codes are e...

Page 31: ...ow noise setting and level during night time By changing this setting you activate the automatic low noise operation function of the unit and define the level of operation Depending on the chosen leve...

Page 32: ...y consumption and comfort No matter which control is selected variations on the behaviour of the system are still possible due to protection controls to keep the unit operating under reliable conditio...

Page 33: ...se of cooling operation the evaporating temperature is allowed to go down to 6 C on temporary base depending on the situation In case of heating operation the condense temperature is allowed to go up...

Page 34: ...orating temperature Quick Powerful Mild Room temperature evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful 7 3 4 Example Automatic mode d...

Page 35: ...ting up the unit Field wiring Be sure that the field wiring has been carried out according to the instructions described in the chapter 6 8 Connecting the electrical wiring on page 24 according to the...

Page 36: ...essure equalisation Cooling start up control Cooling stable condition Communication check Stop valve check Pipe length check Pump down operation Unit stop INFORMATION During the test operation it is n...

Page 37: ...al operation will not be performed For details refer to the wiring diagram labelled on the back of the service cover Pay attention to the fan It is dangerous to inspect the unit while the fan is runni...

Page 38: ...vercharge Open the stop valve on both the gas and liquid side Recalculate the required amount of refrigerant from the piping length and correct the refrigerant charge level by recovering any excessive...

Page 39: ...or unit is connected correctly Faulty wiring to Q1 Q2 Check Q1 Q2 wiring System mismatch Wrong type of indoor units combined R410A R407C RA etc Indoor unit malfunction Check if other indoor units have...

Page 40: ...diagram Wiring diagram 13 2 Dimensions Outdoor unit dimensions in mm 191 142 67 95 940 223 30 16 55 350 160 95 61 55 145 160 30 68 89 84 68 19 48 44 53 90 13 67 80 54 395 47 52 1430 54 95 60 320 89 6...

Page 41: ...B HU HB HD HD HU 100 1000 1000 500 HU HD HU 200 1000 1000 500 HD HU 200 1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 5...

Page 42: ...A1 If there is danger of drainage dripping and freezing between the upper and lower units A2 Then install a roof between the upper and lower units Install the upper unit high enough above the lower u...

Page 43: ...erant charge f Stop valve gas g Stop valve liquid h Cable tie mountings to fix the field wiring with cable ties to ensure stress relief i Subcool heat exchanger j Accumulator k Fan A1P Printed circuit...

Page 44: ...g Heat exchanger h Service port high pressure i Oil separator j Capillary tube 2 k Service port refrigerant charge M1C Compressor M1F M2F Fan motor R1T Thermistor air R2T Thermistor suction 1 R3T The...

Page 45: ...HT RED TO MULTI UNIT TO OUT D TO IN D INDOOR OUTDOOR Note 5 TERMINAL OF M1C LAYOUTOF M1F M2F M1C L1R EL COMPO BOX DETAILOF EL COMPO BOX ARROW VIEW OUTER SHELL FRONT MARK BLU MARK RED MARK RED EL COMPO...

Page 46: ...stor air R2T Thermistor suction 1 R3T Thermistor discharge R4T Thermistor heat exchanger de icer R5T Thermistor subcool heat exchanger R6T Thermistor liquid pipe R7T Thermistor suction 2 S1NPH High pr...

Page 47: ...ired to connect Residential Air RA or Sky Air SA direct expansion DX indoor units f Residential Air RA direct expansion DX indoor units g User interface wireless dedicated depending on indoor unit typ...

Page 48: ...ation the refrigerant cycle will reverse and energy from inside the building will be used to defrost the outdoor unit coil The indoor unit will indicate defrost operation on the displays Hot start In...

Page 49: ...user interfaces as the master user interface The displays of slave user interfaces show change over under centralised control and slave user interfaces automatically follow the operation mode directed...

Page 50: ...ation methods Basic The refrigerant temperature is fixed independent from the situation It corresponds to the standard operation which is known and can be expected from under previous VRV systems Auto...

Page 51: ...unit Do not use the system until a service person confirms that the portion where the refrigerant leaks is repaired 19 4 After sales service and warranty 19 4 1 Warranty period This product includes...

Page 52: ...oting If one of the following malfunctions occur take the measures shown below and contact your dealer WARNING Stop operation and shut off the power if anything unusual occurs burning smells etc Leavi...

Page 53: ...on outdoor De icing temperature sensor malfunction outdoor Liquid temperature sensor after subcool HE malfunction outdoor Liquid temperature sensor coil malfunction outdoor Gas temperature sensor afte...

Page 54: ...stop When the drain pump optional accessories is in operation this noise is heard A pishi pishi squeaking sound is heard when the system stops after heating operation Expansion and contraction of pla...

Page 55: ...relevant and applicable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual Instruction manual sp...

Page 56: ...4P482257 1 2017 03 Copyright 2017 Daikin...

Reviews: