4 Preparation

Installation and operation manual

7

RXYSQ4~Y1B
VRV IV-S system air conditioner
4P397284-1 – 2015.05

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

9.5 mm (3/8")

12.7 mm (1/2")

Annealed (O)

≥0.80 mm

t

Ø

15.9 mm (5/8")

Annealed (O)

≥0.99 mm

19.1 mm (3/4")

Half hard (1/2H)

≥0.80 mm

(a)

Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.

Flare connections:

 Only use annealed material.

4.2.3

To select the piping size

Determine the proper size referring to following tables and reference
figure (only for indication).

INFORMATION

▪ Combination of VRV DX and RA DX indoor units is not

allowed.

▪ Combination  of  RA  DX  and  AHU  indoor  units  is  not

allowed.

▪ Combination of RA DX and aircurtain indoor units is not

allowed.

INFORMATION

If  you  install  RA  DX  indoor  units,  you  have  to  configure
field  setting  [2‑38]  (=  type  of  installed  indoor  units).  See

"6.1.8 Mode 2: Field settings" on page 19

.

A

B-1

B-2

C-1

C-2

C-3

C-4

E

E

E

E

1

1

3-1

3-2

3-3

3-4

A

D

RA DX

VRV DX

D

4

4

5

5

5

5

2

2

2

2

1

Outdoor unit

2

Refrigerant branch kits

3-1~3-4

VRV DX indoor units

4

BP units

5

RA DX indoor units

A

Piping between outdoor unit and (first) refrigerant branch
kit

B-1 B-2

Piping between refrigerant branch kits

C-1~C-4

Piping between refrigerant branch kit and indoor unit

D

Piping between refrigerant branch kit and BP unit

E

Piping between BP unit and RA DX indoor unit

In  case  the  required  pipe  sizes  (inch  sizes)  are  not  available,  it  is
also allowed to use other diameters (mm sizes), taken the following
into account:

▪ Select the pipe size nearest to the required size.

▪ Use  the  suitable  adapters  for  the  change-over  from  inch  to  mm

pipes (field supply).

▪ The  additional  refrigerant  calculation  has  to  be  adjusted  as

mentioned  in 

"5.6.2  To  determine  the  additional  refrigerant

amount" on page 13

.

A: Piping between outdoor unit and (first)
refrigerant branch kit

When the equivalent pipe length between outdoor and indoor units is
90 m or more, the size of the main gas pipe must be increased (size-
up).  If  the  recommended  gas  pipe  (size-up)  is  not  available,  you
must  use  the  standard  size  (which  might  result  in  a  small  capacity
decrease).

a

e

b

c

d

a

Outdoor unit

b

Main gas pipe

c

Increase

d

First refrigerant branch kit

e

Indoor unit

Outdoor unit

capacity type (HP)

Piping outer diameter size (mm)

Gas pipe

Liquid pipe

Standard

Size-up

4+5

15.9

19.1

9.5

6

19.1

22.1

B: Piping between refrigerant branch kits

Choose  from  the  following  table  in  accordance  with  the  indoor  unit
total  capacity  type,  connected  downstream.  Do  not  let  the
connection  piping  exceed  the  refrigerant  piping  size  chosen  by  the
general system model name.

Indoor unit capacity

index

Piping outer diameter size (mm)

Gas pipe

Liquid pipe

<150

15.9

9.5

150≤x≤182

19.1

Example: 

Downstream capacity for B-1 = capacity index of unit 3-1

+ capacity index of unit 3-2

C: Piping between refrigerant branch kit and
indoor unit

Use  the  same  diameters  as  the  connections  (liquid,  gas)  on  the
indoor units. The diameters of the indoor units are as follows:

Indoor unit capacity

index

Piping outer diameter size (mm)

Gas pipe

Liquid pipe

15~50

12.7

6.4

63~140

15.9

9.5

D: Piping between refrigerant branch kit and BP
unit

Total capacity index
of connected indoor

units

Piping outer diameter size (mm)

Gas pipe

Liquid pipe

15~62

12.7

6.4

63~149

15.9

9.5

150~182

19.1

Summary of Contents for RXYSQ5T7V1B

Page 1: ...lation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSQ4T7V1B RXYSQ5T7V1B RXYSQ6T7V1B RXYSQ4T7Y1B RXYSQ5T7Y1B RXYSQ6...

Page 2: ...1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB H...

Page 3: ...normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad j...

Page 4: ...settings 17 6 1 2 To access the field setting components 17 6 1 3 Field setting components 17 6 1 4 To access mode 1 or 2 18 6 1 5 To use mode 1 18 6 1 6 To use mode 2 18 6 1 7 Mode 1 and default sit...

Page 5: ...e installing Paper in the box of the outdoor unit Outdoor unit installation and operation manual Installation and operation instructions Installer and user reference guide Preparation of the installat...

Page 6: ...keep the drain holes of the unit free by using proper equipment In heating T AO C WB a b 20 15 5 15 10 5 0 5 10 15 20 10 15 20 2527 30 TAI C DB a Warming up operation range b Operation range TAI Ambie...

Page 7: ...o account Select the pipe size nearest to the required size Use the suitable adapters for the change over from inch to mm pipes field supply The additional refrigerant calculation has to be adjusted a...

Page 8: ...acity index Refrigerant branch kit 182 KHRQ22M29H INFORMATION Maximum 8 branches can be connected to a header 4 3 Preparing electrical wiring 4 3 1 Safety device requirements The power supply must be...

Page 9: ...f you install the unit on a frame install a waterproof plate within 150 mm of the bottom side of the unit in order to prevent the invasion of water in the unit and to avoid the drain water dripping se...

Page 10: ...service port cover Tightening torques Stop valve size mm Tightening torque N m turn clockwise to close Shaft Valve body Hexagonal wrench Cap valve lid Service port 9 5 5 4 6 6 4 mm 13 5 16 5 11 5 13 9...

Page 11: ...se This means that they will close Leak test and vacuum drying of field piping and indoor units is impossible when this happens Therefore there will be explained 2 methods for initial installation lea...

Page 12: ...maximum operation pressure of the unit i e 4 0 MPa 40 bar 2 Test for leaks by applying a bubble test solution to all piping connections 3 Discharge all nitrogen gas NOTICE Make sure to use a recommen...

Page 13: ...riginal amount of refrigerant refer to the nameplate on the unit and the determined additional refrigerant amount 5 6 2 To determine the additional refrigerant amount INFORMATION For final charge adju...

Page 14: ...ion is detected during the procedure e g in case of closed stop valve a malfunction code will be displayed In that case refer to 5 6 4 Error codes when charging refrigerant on page 14 and solve the ma...

Page 15: ...the electrical wiring Tightening torques Wiring Screw size Tightening torque N m Power supply wiring power supply shielded ground M5 2 2 2 7 Transmission wiring M3 5 0 8 0 97 5 7 4 To connect the ele...

Page 16: ...s to prevent the edge of the knockout hole from cutting the wires a b c d e A B A Inside of the outdoor unit B Outside of the outdoor unit a Wire b Bush c Nut d Frame e Hose 6 Reattach the service cov...

Page 17: ...quired to abort the special operation before normal operation can restart It will be indicated in below explanations 6 1 2 To access the field setting components See 5 1 1 To open the outdoor unit on...

Page 18: ...t confused in the middle of the process press BS1 to return to the default situation 6 1 5 To use mode 1 In mode 1 and in default situation you can read out some information Example 7 LEDs display Def...

Page 19: ...mitation can be set in mode 2 There are two methods to activate power consumption limitation of the outdoor unit system The first method is to enable a forced power consumption limitation by field set...

Page 20: ...tion was not aborted by pushing BS3 the unit will stop its operation after 30 minutes If 30 minutes was not sufficient to add the needed refrigerant amount the function can be reactivated by changing...

Page 21: ...n an external signal is sent to the unit this setting defines the level power consumption limitation that will be applied for step 2 The level is according to the table 30 default 40 50 2 32 Forced al...

Page 22: ...local supply panel The voltage must correspond to the voltage on the identification label of the unit Earth wiring Be sure that the earth wires have been connected properly and that the earth terminal...

Page 23: ...ntralised control will display on the user interface of indoor units Steps during the automatic system test run procedure Step Description Control before start up pressure equalisation Cooling start u...

Page 24: ...circuit A1P X12A Check connection on PCB or actuator Suction temperature sensor malfunction R3T A1P X12A R5T A1P X12A Check connection on PCB or actuator Liquid temperature sensor coil malfunction R4T...

Page 25: ...ice space between the unit and obstacles A B C D and E eB Maximum distance between the unit and the edge of obstacle E in the direction of obstacle B eD Maximum distance between the unit and the edge...

Page 26: ...installation manual for indoor outdoor transmission F1 F2 wiring 6 When using the central control system connect outdoor outdoor transmission F1 F2 Notes for RXYSQ4 6_Y1 1 Symbols see below 2 For X37...

Page 27: ...stor air R2T Thermistor discharge R3T Thermistor suction 1 R4T Thermistor heat exchanger R5T Thermistor suction 2 R6T Thermistor subcool heat exchanger R7T Thermistor liquid pipe R10T Thermistor fin S...

Page 28: ...d user interface To protect the unit turn on the main power switch 6 hours before operation If the main power supply is turned off during operation operation will restart automatically after the power...

Page 29: ...t changeover remote control switch To start 1 Press the operation mode selector button on the user interface several times and select program dry operation 2 Press the ON OFF button of the user interf...

Page 30: ...y the master user interface Only the master user interface can select heating or cooling mode 12 5 2 To designate the master user interface VRV DX In case only VRV DX indoor units are connected to the...

Page 31: ...off the main power switch If water leaks from the unit Stop the operation The operation switch does not work well Turn off the power Malfunction Measure If the user interface display indicates the uni...