1-2 Electrical Specifications (50Hz)
RXYSQ4PA7Y1B
RXYSQ5PA7Y1B
RXYSQ6PA7Y1B
Power Supply
Name
Y1
Phase
3N~
Frequency
Hz
50
Voltage
V
380-415
Current
Nominal running
current (RLA)
Cooling
A
5.30
6.77
7.79
Starting current (MSC)
A
5.30
6.77
7.79
Maximum Running Current
A
13.5
13.5
13.5
Minimum circuit amps (MCA)
A
13.5
13.5
13.5
Maximum fuse amps (MFA)
A
16.0
16.0
16.0
Full load amps (FLA)
A
0.3+0.3 (Fan motor)
Voltage range
Minimum
V
342
342
342
Maximum
V
456
456
456
Wiring connections
For Power Supply
Quantity
5
5
5
Remark
Earth wire included
For connection with
indoor
Quantity
2
2
2
Remark
F1+F2
Power Supply Intake
Both indoor and outdoor unit
Field earth leakage breaker
mA
300
300
300
Notes
RLA is based on following conditions : indoor temperature : 27°CDB/19°CWB , outdoor temperature :
35°CDB
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminal
is not below or above listed range limits
Maximum allowable voltage range variation between phases is 2%
Instead of fuse, use circuit breaker. MFA is used to select circuit breaker and the ground fault circuit
interrupter (earth leakage circuit breaker)
MSC means the maximum current during start up of the compressor
Select wire size based on MCA