Specifications
Refrigerant
Name
R-410A
Charge
kg
4.0
4.0
4.0
Control
Expansion valve (electronic type)
Nr of Circuits
1
1
1
Refrigerant Oil
Name
Daphne FVC68D
Charged Volume
l
1.5
1.5
1.5
Piping connections
Liquid (OD)
Type
Flare connection
Diameter (OD)
mm
9.52
9.52
9.52
Gas
Type
Flare connection
Flare connection
Braze connection
Diameter (OD)
mm
15.9
15.9
19.1
Drain
Quantity
3
3
3
Diameter (OD)
mm
26 x 3
Heat Insulation
Both liquid and gas pipes
Max total length
m
300
300
300
Defrost Method
Reversed cycle
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
Inverter controlled
Capacity Control
24 to 100
Safety devices
HPS
Fan motor thermal protection
Inverter overload protector
PC board fuse
Standard Accessories Standard Accessories
Installation manual
Quantity
1
1
1
Standard Accessories
Operation manual
Quantity
1
1
1
Standard Accessories
Connection pipes
Quantity
3
Notes
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature
: 35°CDB, equivalent refrigerant piping : 5m, level difference : 0m.
Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB,
6°CWB, equivalent refrigerant piping: 5m, level diference: 0m.
Sound pressure level is a relative value, depending on the distance and acoustic environment. For more
details, please refer to sound level drawings.
Sound power level is an absolute value that a sound source generates.
Sound values are measured in a semi-anechoic room.
1-1 Technical Specifications
RXYSQ4PA7Y1B
RXYSQ5PA7Y1B
RXYSQ6PA7Y1B
EEDEN10-200_11_RXYSQ4-6P7Y1B.pdf 5