Operation manual
4
RXYQ8~1 RXYQ8~12P7YLK
VRVIII system air conditioner
5.
O
PERATION
RANGE
Operation range
Use the system in the following temperature and humidity ranges for
safe and effective operation.
6.
O
PERATION
PROCEDURE
■
Operation procedure varies according to the combination of
outdoor unit and remote controller. Read
"2. What to do before
operation" on page 3
.
■
To protect the unit, turn on the main power switch 6 hours before
operation.
■
If the main power supply is turned off during operation, operation
will restart automatically after the power turns back on again.
6.1.
Cooling, heating, and fan only operation
(See
figure 4
and
figure 6.1
)
■
Changeover cannot be made with a remote controller whose
display shows
(change-over under centralized control).
■
When the display
(change-over under centralized control)
flashes, refer to
"6.5. Setting the master remote controller" on
page 6
.
■
The fan may keep on running for about 1 minute after the
heating operation stops.
■
The air flow rate may adjust itself depending on the room
temperature or the fan may stop immediately. This is not a
malfunction.
■
It may take some time to change the air flow rate. This is a
normal operation.
For systems without cool/heat selector
(See figure 4)
1
Press the operation mode selector button several times and
select the operation mode of your choice.
2
Press the on/off button.
The operation lamp lights up and the system starts operation.
For systems with cool/heat selector
1
Select operation mode with the cool/heat selector as follows:
2
Press the on/off button.
The operation lamp lights up and the system starts operation.
Adjustment
For programming temperature, fan speed and air flow direction,
follow the procedure as explained below (only for remote controller of
type BRC1A51: FXC, FXF, FXH, FXK and FXA).
3
Press the temperature setting button and set the
desired temperature.
Each time this button is pressed, the temperature
setting will be raised or lowered by 1°C.
4
Press the fan speed control button and select the fan speed of
your preference.
5
Press the air flow direction adjust button.
Refer to the chapter
"6.3. Adjusting the air flow direction" on
page 5
for more details.
Stopping the system
6
Press the on/off button once again.
The operation lamp goes off and the system stops operation.
Explanation of heating operation
It may take longer to reach the set temperature for general heating
operation than for cooling operation.
The following operation is performed in order to prevent the heating
capacity from dropping or cold air from blowing.
Defrost operation
■
In heating operation, freezing of the outdoor unit coil increases.
Heating capability decreases and the system goes into defrost
operation.
■
The indoor unit fan stops and the remote controller displays
.
■
After maximum 10 minutes of defrost operation, the system
returns to heating operation again.
Hot start
■
In order to prevent cold air from blowing out of an indoor unit at
the start of heating operation, the indoor fan is automatically
stopped. The display of the remote controller shows
.
It may take some time before the fan starts. This is not a
malfunction.
RXYQ8~12P7
Outdoor temperature
–20~21°C DB
–20~15.5°C WB
Indoor temperature
14~25°C WB
15~27°C DB
21~32°C DB
Indoor humidity
≤
80%
(*)
(*)
to avoid condensation and water dripping out the unit.
If the temperature or the humidity is beyond these conditions, safety devices may
work and the air conditioner may not operate.
Cooling operation
Heating operation
Fan only operation
Cooling operation (
figure 6.1
)
Heating operation (
figure 6.2
)
Fan only operation (
figure 6.3
)
NOTE
■
Set the temperature within the operation
range.
■
Temperature setting is not possible for fan
only operation.
NOTE
Do not turn off power immediately after the unit stops,
but wait for at least 5 minutes, otherwise water could
leak or other damage to the unit could occur.
NOTE
■
The heating capacity drops when the outside
temperature falls. If this happens, use another
heating device together with the unit. (When using
together with appliances that produce open fire,
ventilate the room constantly.)
Do not place appliances that produce open fire in
places exposed to the air flow from the unit or
under the unit.
■
It takes some time to heat up the room from the
time the unit is started since the unit uses a hot-air
circulating system to heat the entire room.
■
If the hot air rises to the ceiling, leaving the area
above the floor cold, we recommend that you use
the circulator (the indoor fan for circulating air).
Contact your dealer for details.
4PW41759-1A – 08.2011
–5~52°C DB