Operation Manual
SiEN34-705
320
Operation Manual
• Table 1 “Inspection Cycle” and “Maintenance Cycle” Lists
Note 1
This table indicates main parts.
See the maintenance and inspection contract for details.
Note 2
This maintenance cycle indicates recommended lengths of time until
the need arises for maintenance work, in order to ensure the product
is operational as long as possible
Use for appropriate maintenance design (budgeting maintenance
and inspection fees, etc.)
Depending on the content of the maintenance and inspection con-
tract, the inspection and maintenance cycles may in reality be shorter
than those listed here.
Shortening of “maintenance cycle” and “replacement cycle”
needs to be considered in the following cases.
1.
When used in hot, humid locations or locations where temper-
ature and humidity fluctuate greatly.
2.
When used in locations where power fluctuation (voltage, fre-
quency, wave distortion, etc.) is high.
(Cannot be used if it is outside the allowable range.)
3.
When installed and used in locations where bumps and vibra-
tions are frequent.
4.
When used in bad locations where dust, salt, harmful gas or oil
mist such as sulfurous acid and hydrogen sulfide may be
present in the air.
5.
When used in locations where the machine is started and
stopped frequently or operation time is long. (Example: 24
hour air-conditioning)
!
Recommended replacement cycle of wear-out parts
[The cycle is not the same as the warranty period.]
• Table 2 “Replacement Cycle” Lists
Note 1
This table indicates main parts.
See the maintenance and inspection contract for details.
Note 2
This maintenance cycle indicates recommended lengths of time until
the need arises for maintenance work, in order to ensure the product
is operational as long as possible.
Use for appropriate maintenance design (budgeting maintenance
and inspection fees, etc.).
Contact your dealer for details.
Note: Breakage due to taking apart or cleaning inside by anyone
other than our authorized dealers may not be included in the war-
ranty.
!
Moving and discarding the unit
• Contact your dealer for removing and reinstalling the system air
conditioner since they require technical expertise.
• The system air conditioner uses fluorocarbon refrigerant.
Contact your dealer for discarding the system air conditioner
since it is required by law to collect, transport and discard the
refrigerant in accordance with relevant local and national regula-
tions.
!
Where to call
For after-sales service, etc., consult with your dealer.
!
Warranty period:
•
This product includes a warranty card.
The warranty card is given to a customer after dealer staff fills
out necessary items in the card. The customer should check
the entered items and store it carefully.
Warranty period:
Within one year after installation.
For further details, refer to the warranty
card.
•
If it is necessary to repair the air conditioner within the warranty
period, contact your dealer and show your warranty card. If
the warranty card is not shown, pay-service repair may be per-
formed even though the warranty period is not expired.
Name of Main Part
Inspection
Cycle
Maintenance Cycle
[replacements and/or
repairs]
Electric motor (fan,
damper, etc.)
1 year
20,000 hours
PC boards
25,000 hours
Heat exchanger
5 years
Sensor (thermistor, etc.)
5 years
remote control and
switches
25,000 hours
Drain pan
8 years
Expansion valve
20,000 hours
Electromagnetic valve
20,000 hours
Name of Main Part
Inspection
Cycle
Replacement Cycle
Air filter
1 year
5 years
High efficiency filter
(Optional accessory)
1 year
Fuse
10 years
Crankcase heater
8 years