Si39-407
Troubleshooting by Remote Controller
Troubleshooting
179
Outdoor
Unit
LA
9
9
9
Malfunction of power unit
—
LC
9
9
9
Malfunction of transmission between inverter and
control PC board
P1
9
9
9
Inverter over-ripple protection
P4
9
9
9
Malfunction of inverter radiating fin temperature rise
sensor
System
U0
8
7
9
Low pressure drop due to refrigerant shortage or
electronic expansion valve failure
U1
9
9
9
Reverse phase / open phase
U2
9
9
9
Power supply insufficient or instantaneous failure
U3
9
9
9
Check operation is not conducted.
U4
9
9
9
Malfunction of transmission between indoor and
outdoor units
U5
9
9
9
Malfunction of transmission between remote
controller and indoor unit
U5
7
8
7
Failure of remote controller PC board or setting
during control by remote controller
U7
9
9
9
Malfunction of transmission between outdoor units
U8
9
9
7
Malfunction of transmission between master and
slave remote controllers (malfunction of slave remote
controller)
U9
9
9
9
Malfunction of transmission between indoor unit and
outdoor unit in the same system
UA
9
9
9
Excessive number of indoor units etc.
UC
8
8
8
Address duplication of central remote controller
UE
9
9
9
Malfunction of transmission between central remote
controller and indoor unit
UF
9
9
9
Refrigerant system not set, incompatible wiring /
piping
UH
9
9
9
Malfunction of system, refrigerant system address
undefined
Centralized
Control
and
Schedule
Timer
M1
8
or
7
9
9
PC board defect
M8
8
or
7
9
9
Malfunction of transmission between optional
controllers for centralized control
MA
8
or
7
9
9
Improper combination of optional controllers for
centralized control
MC
8
or
7
9
9
Address duplication, improper setting
Heat
Reclaim
Ventilation
64
8
7
9
Indoor unit’s air thermistor error
—
65
8
7
9
Outside air thermistor error
—
68
8
7
9
—
6A
8
7
9
Damper system alarm
—
6A
9
9
9
Damper thermistor error
—
6F
8
7
9
Malfunction of simple remote controller
—
6H
8
7
9
Malfunction of door switch or connector
—
94
9
9
9
Internal transmission error
—
Malfunction
code
Operation
lamp
Inspection
display
Unit No.
Malfunction contents
Page
Referred
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Summary of Contents for RXYQ5-48MAY1
Page 1: ...RXYQ5 48MAY1 R410A Heat Pump 50Hz Si39 407...
Page 59: ...Specifications Si39 407 48 Specifications...
Page 83: ...Refrigerant Flow for Each Operation Mode Si39 407 72 Refirgerant Circuit...
Page 173: ...Field Setting Si39 407 162 Test Operation...
Page 184: ...Si39 407 Troubleshooting by Remote Controller Troubleshooting 173...
Page 277: ...Troubleshooting OP Unified ON OFF Controller Si39 407 266 Troubleshooting...
Page 279: ...Piping Diagrams Si39 407 268 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ5MAY1 3D048203...
Page 280: ...Si39 407 Piping Diagrams Appendix 269 RXYQ8MAY1 RXYQ10MAY1 RXYQ12MAY1 3D048033A...
Page 281: ...Piping Diagrams Si39 407 270 Appendix RXYQ14MAY1 RXYQ16MAY1 3D048034A...
Page 286: ...Si39 407 Piping Diagrams Appendix 275 FXAQ BEVQ Indoor unit Connection Unit 4D047084 4D034127B...
Page 287: ...Piping Diagrams Si39 407 276 Appendix FXLQ BEVQ Indoor unit Connection Unit 4D047084 4D034127B...
Page 289: ...Wiring Diagrams for Reference Si39 407 278 Appendix RXYQ8MAY1 RXYQ10MAY1 RXYQ12MAY1 3D047088C...
Page 290: ...Si39 407 Wiring Diagrams for Reference Appendix 279 RXYQ14MAY1 RXYQ16MAY1 3D047089C...
Page 295: ...Wiring Diagrams for Reference Si39 407 284 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Page 296: ...Si39 407 Wiring Diagrams for Reference Appendix 285 FXZQ20M 25M 32M 40M 50MVE 3D038359...
Page 298: ...Si39 407 Wiring Diagrams for Reference Appendix 287 FXKQ25M 32M 40M 63MVE 3D039564A...
Page 299: ...Wiring Diagrams for Reference Si39 407 288 Appendix FXDQ20N 25N 32N 40N 50N 63NVE 3D045500A...
Page 301: ...Wiring Diagrams for Reference Si39 407 290 Appendix FXMQ40M 50M 63M 80M 100M 125MVE 3D039620A...
Page 302: ...Si39 407 Wiring Diagrams for Reference Appendix 291 FXMQ200M 250MVE 3D039621A...
Page 303: ...Wiring Diagrams for Reference Si39 407 292 Appendix FXHQ32M 63M 100MVE 3D039801C...
Page 304: ...Si39 407 Wiring Diagrams for Reference Appendix 293 FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206A...
Page 306: ...Si39 407 Wiring Diagrams for Reference Appendix 295 FXUQ71M 100M 125MV1 3D044973...
Page 307: ...Wiring Diagrams for Reference Si39 407 296 Appendix FXAQ20MH 25MH 32MH 40MH 50MHV1 3D046348A...
Page 308: ...Si39 407 Wiring Diagrams for Reference Appendix 297 FXLQ20MH 25MH 32MH 40MH 50MHV1 3D046787A...
Page 309: ...Wiring Diagrams for Reference Si39 407 298 Appendix FXMQ125MF 200MF 250MFV1 3D044996B...
Page 310: ...Si39 407 Wiring Diagrams for Reference Appendix 299 BEVQ50MVE 3D046579A Notes...
Page 311: ...Wiring Diagrams for Reference Si39 407 300 Appendix BEVQ71M 100M 125MVE 3D044901A Notes...
Page 335: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 407 324 Appendix...
Page 349: ...Si39 407 iv Index...
Page 352: ...Printed in Singapore 03 2005 COS...