Si39-407
Outline of Control (Indoor Unit)
Function
113
(3) Thermostat OFF by discharge air temperature
<Cooling>
<Heating>
6.7.3 Low Outdoor Air Temperature Protection Control
Objective
In cooling (or fan operation) or heating, if outdoor air is low in temperature, stop the fan forcibly.
Details
[Cooling and fan operation]
Turn OFF the fan for a period of 60 minutes at a suction temperature of 5
°
C or lower.
In order to monitor the outdoor air temperature, however, turn ON the fan for a period of one
minute and turn OFF the fan again at a temperature of 5
°
C or lower after the said timer
completes the operative period.
Reset the 60-minute timer when the fan stops running.
[Heating]
Turn OFF the fan for a period of 60 minutes at a suction temperature of –5
°
C or lower.
In order to monitor the outdoor air temperature, however, turn ON the fan for a period of one
minute and turn OFF the fan again at a temperature of –5
°
C or lower after the said timer
completes the operative period.
Reset the 60-minute timer when the fan stops running.
* The thermostat will not turn ON in one minute due to the temperature while the fan stops.
This control shall be disabled at test run both in cooling and heating. (The test run shall be
conducted first.)
6.8
Heater Control
The heater control is conducted in the following manner.
[Normal control]
While in heating operation, the heater
control (ON/OFF) is conducted as
shown on the right.
[Overload control]
When the system is overloaded in
heating operation, the heater will
be turned OFF in the following two
manners.
(1) The heater control (ON/OFF) is
conducted through the liquid
pipe temperature (R2T) of the
indoor unit.
Target discharge air temp. Ts – Discharge air temp. T4
>5 degree continue for 5 minutes.
→
Thermostat stops for 1 minute.
→
Thermostat ON
&
Discharge air temp. T4 – Target discharge air temp. Ts >5 degree
continue for 5
minutes
EV opening is low limit
→
Thermostat stops for 1 minute.
→
Thermostat ON
ON
Set temperature
OFF
2ºC
2ºC
ON
43ºC
50ºC Liquid pipe temperature
OFF
*47ºC on Model FXAQ, FXLQ or FXHQ
Summary of Contents for RXYQ5-48MAY1
Page 1: ...RXYQ5 48MAY1 R410A Heat Pump 50Hz Si39 407...
Page 59: ...Specifications Si39 407 48 Specifications...
Page 83: ...Refrigerant Flow for Each Operation Mode Si39 407 72 Refirgerant Circuit...
Page 173: ...Field Setting Si39 407 162 Test Operation...
Page 184: ...Si39 407 Troubleshooting by Remote Controller Troubleshooting 173...
Page 277: ...Troubleshooting OP Unified ON OFF Controller Si39 407 266 Troubleshooting...
Page 279: ...Piping Diagrams Si39 407 268 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ5MAY1 3D048203...
Page 280: ...Si39 407 Piping Diagrams Appendix 269 RXYQ8MAY1 RXYQ10MAY1 RXYQ12MAY1 3D048033A...
Page 281: ...Piping Diagrams Si39 407 270 Appendix RXYQ14MAY1 RXYQ16MAY1 3D048034A...
Page 286: ...Si39 407 Piping Diagrams Appendix 275 FXAQ BEVQ Indoor unit Connection Unit 4D047084 4D034127B...
Page 287: ...Piping Diagrams Si39 407 276 Appendix FXLQ BEVQ Indoor unit Connection Unit 4D047084 4D034127B...
Page 289: ...Wiring Diagrams for Reference Si39 407 278 Appendix RXYQ8MAY1 RXYQ10MAY1 RXYQ12MAY1 3D047088C...
Page 290: ...Si39 407 Wiring Diagrams for Reference Appendix 279 RXYQ14MAY1 RXYQ16MAY1 3D047089C...
Page 295: ...Wiring Diagrams for Reference Si39 407 284 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Page 296: ...Si39 407 Wiring Diagrams for Reference Appendix 285 FXZQ20M 25M 32M 40M 50MVE 3D038359...
Page 298: ...Si39 407 Wiring Diagrams for Reference Appendix 287 FXKQ25M 32M 40M 63MVE 3D039564A...
Page 299: ...Wiring Diagrams for Reference Si39 407 288 Appendix FXDQ20N 25N 32N 40N 50N 63NVE 3D045500A...
Page 301: ...Wiring Diagrams for Reference Si39 407 290 Appendix FXMQ40M 50M 63M 80M 100M 125MVE 3D039620A...
Page 302: ...Si39 407 Wiring Diagrams for Reference Appendix 291 FXMQ200M 250MVE 3D039621A...
Page 303: ...Wiring Diagrams for Reference Si39 407 292 Appendix FXHQ32M 63M 100MVE 3D039801C...
Page 304: ...Si39 407 Wiring Diagrams for Reference Appendix 293 FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206A...
Page 306: ...Si39 407 Wiring Diagrams for Reference Appendix 295 FXUQ71M 100M 125MV1 3D044973...
Page 307: ...Wiring Diagrams for Reference Si39 407 296 Appendix FXAQ20MH 25MH 32MH 40MH 50MHV1 3D046348A...
Page 308: ...Si39 407 Wiring Diagrams for Reference Appendix 297 FXLQ20MH 25MH 32MH 40MH 50MHV1 3D046787A...
Page 309: ...Wiring Diagrams for Reference Si39 407 298 Appendix FXMQ125MF 200MF 250MFV1 3D044996B...
Page 310: ...Si39 407 Wiring Diagrams for Reference Appendix 299 BEVQ50MVE 3D046579A Notes...
Page 311: ...Wiring Diagrams for Reference Si39 407 300 Appendix BEVQ71M 100M 125MVE 3D044901A Notes...
Page 335: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 407 324 Appendix...
Page 349: ...Si39 407 iv Index...
Page 352: ...Printed in Singapore 03 2005 COS...