Symptom-based Troubleshooting
Si39-407
166
Troubleshooting
1. Symptom-based Troubleshooting
Symptom
Supposed Cause
Countermeasure
1
The system does not start operation at all.
Blowout of fuse(s)
Turn Off the power supply and
then replace the fuse(s).
Cutout of breaker(s)
• If the knob of any breaker is in
its OFF position, turn ON the
power supply.
• If the knob of any circuit
breaker is in its tripped position,
do not turn ON the power
supply.
Power failure
After the power failure is reset,
restart the system.
2
The system starts operation but makes an
immediate stop.
Blocked air inlet or outlet of indoor
or outdoor unit
Remove obstacle(s).
Clogged air filter(s)
Clean the air filter(s).
3
The system does not cool or heat air well.
Blocked air inlet or outlet of indoor
or outdoor unit
Remove obstacle(s).
Clogged air filter(s)
Clean the air filter(s).
Enclosed outdoor unit(s)
Remove the enclosure.
Improper set temperature
Set the temperature to a proper
degree.
Airflow rate set to "LOW"
Set it to a proper airflow rate.
Improper direction of air diffusion Set it to a proper direction.
Open window(s) or door(s)
Shut it tightly.
[In cooling] Direct sunlight received
Hang curtains or shades on
windows.
[In cooling] Too many persons staying in a
room
[In cooling] Too many heat sources (e.g. OA
equipment) located in a room
4
The system does
not operate.
The system stops and
immediately restarts operation.
If the OPERATION lamp on the
remote controller turns ON, the
system will be normal. These
symptoms indicate that the
system is controlled so as not to
put unreasonable loads on the
system.
Normal operation. The system will
automatically start operation after
a lapse of five minutes.
Pressing the TEMP ADJUST
button immediately resets the
system.
The remote controller displays
"UNDER CENTRALIZED
CONTROL", which blinks for a
period of several seconds
when the OPERATION button
is depressed.
The system is controlled with
centralized controller. Blinking
display indicates that the system
cannot be operated using the
remote controller.
Operate the system using the
COOL/HEAT centralized remote
controller.
The system stops immediately
after turning ON the power
supply.
The system is in preparation
mode of micro computer
operation.
Wait for a period of approximately
one minute.
5
The system
makes
intermittent
stops.
The remote controller displays
malfunction codes "U4" and
"U5", and the system stops but
restarts after a lapse of several
minutes.
The system stops due to an
interruption in communication
between units caused by
electrical noises coming from
equipment other than air
conditioners.
Remove causes of electrical
noises.
If these causes are removed, the
system will automatically restart
operation.
6
COOL-HEAT
selection is
disabled.
The remote controller displays
"UNDER CENTRALIZED
CONTROL".
This remote controller has no
option to select cooling operation.
Use a remote controller with
option to select cooling operation.
The remote controller displays
"UNDER CENTRALIZED
CONTROL", and the COOL-
HEAT selection remote
controller is provided.
COOL-HEAT selection is made
using the COOL-HEAT selection
remote controller.
Use the COOL-HEAT selection
remote controller.
ON
OFF
Knob
Tripped
Circuit breaker
Summary of Contents for RXYQ5-48MAY1
Page 1: ...RXYQ5 48MAY1 R410A Heat Pump 50Hz Si39 407...
Page 59: ...Specifications Si39 407 48 Specifications...
Page 83: ...Refrigerant Flow for Each Operation Mode Si39 407 72 Refirgerant Circuit...
Page 173: ...Field Setting Si39 407 162 Test Operation...
Page 184: ...Si39 407 Troubleshooting by Remote Controller Troubleshooting 173...
Page 277: ...Troubleshooting OP Unified ON OFF Controller Si39 407 266 Troubleshooting...
Page 279: ...Piping Diagrams Si39 407 268 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ5MAY1 3D048203...
Page 280: ...Si39 407 Piping Diagrams Appendix 269 RXYQ8MAY1 RXYQ10MAY1 RXYQ12MAY1 3D048033A...
Page 281: ...Piping Diagrams Si39 407 270 Appendix RXYQ14MAY1 RXYQ16MAY1 3D048034A...
Page 286: ...Si39 407 Piping Diagrams Appendix 275 FXAQ BEVQ Indoor unit Connection Unit 4D047084 4D034127B...
Page 287: ...Piping Diagrams Si39 407 276 Appendix FXLQ BEVQ Indoor unit Connection Unit 4D047084 4D034127B...
Page 289: ...Wiring Diagrams for Reference Si39 407 278 Appendix RXYQ8MAY1 RXYQ10MAY1 RXYQ12MAY1 3D047088C...
Page 290: ...Si39 407 Wiring Diagrams for Reference Appendix 279 RXYQ14MAY1 RXYQ16MAY1 3D047089C...
Page 295: ...Wiring Diagrams for Reference Si39 407 284 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Page 296: ...Si39 407 Wiring Diagrams for Reference Appendix 285 FXZQ20M 25M 32M 40M 50MVE 3D038359...
Page 298: ...Si39 407 Wiring Diagrams for Reference Appendix 287 FXKQ25M 32M 40M 63MVE 3D039564A...
Page 299: ...Wiring Diagrams for Reference Si39 407 288 Appendix FXDQ20N 25N 32N 40N 50N 63NVE 3D045500A...
Page 301: ...Wiring Diagrams for Reference Si39 407 290 Appendix FXMQ40M 50M 63M 80M 100M 125MVE 3D039620A...
Page 302: ...Si39 407 Wiring Diagrams for Reference Appendix 291 FXMQ200M 250MVE 3D039621A...
Page 303: ...Wiring Diagrams for Reference Si39 407 292 Appendix FXHQ32M 63M 100MVE 3D039801C...
Page 304: ...Si39 407 Wiring Diagrams for Reference Appendix 293 FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206A...
Page 306: ...Si39 407 Wiring Diagrams for Reference Appendix 295 FXUQ71M 100M 125MV1 3D044973...
Page 307: ...Wiring Diagrams for Reference Si39 407 296 Appendix FXAQ20MH 25MH 32MH 40MH 50MHV1 3D046348A...
Page 308: ...Si39 407 Wiring Diagrams for Reference Appendix 297 FXLQ20MH 25MH 32MH 40MH 50MHV1 3D046787A...
Page 309: ...Wiring Diagrams for Reference Si39 407 298 Appendix FXMQ125MF 200MF 250MFV1 3D044996B...
Page 310: ...Si39 407 Wiring Diagrams for Reference Appendix 299 BEVQ50MVE 3D046579A Notes...
Page 311: ...Wiring Diagrams for Reference Si39 407 300 Appendix BEVQ71M 100M 125MVE 3D044901A Notes...
Page 335: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 407 324 Appendix...
Page 349: ...Si39 407 iv Index...
Page 352: ...Printed in Singapore 03 2005 COS...