• VRV Systems • Outdoor Units
8
• Outdoor Units • VRV HEAT PUMP • RXYHQ12-36P(8)
2
Electrical data
RXYHQ-P
NOTES
1
In accordance with EN/IEC 61000-3-11
(1)
, respectively EN/IEC 61000-3-11
(2)
, it may be necessary to consult the distribution network
operator to ensure that the equipment is connected only to a supply with Z
sys
(4)
Z
max
, respectively S
sc
(3)
minimum S
sc
value
2
(1)
European/International technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage
supply systems for equipment with rated
75A.
(2)
European/International technical standard setting the limits for harmonic currents produced by equipment connected to public low-
voltage system with input current
16A and
75A per phase .
(3)
Short-circuit power
(4)
System impedance.
Combination of
Minimum Ssc value
[kVA]
Zmax
[
]
RXYHQ12
1114
0.27
RXYHQ16
RXYQ8 + RXYQ8
2436
-
RXYHQ18
RXYQ8 + RXYQ10
2146
0.27
RXYHQ20
RXYQ8 + RXYHQ12
2332
0.27
RXYHQ22
RXYHQ12
2042
0.25
RXYHQ24
RXYQ8 + RXYQ8 + RXYQ8
3654
-
RXYHQ26
RXYQ8 + RXYQ8 + RXYQ10
3364
0.27
RXYHQ28
RXYQ8 + RXYQ10
3074
0.25
RXYHQ30
RXYQ8 + RXYHQ12
3260
0.25
RXYHQ32
RXYQ8 + R RXYHQ12
3446
0.25
RXYHQ34
R RXYHQ12
3156
0.24
RXYHQ36
R R RXYHQ12
3342
0.24
4TW31461-4A