• Outdoor Units • VRV HEAT PUMP • RXYHQ12-36P(8)
1
1
• VRV Systems • Outdoor Units
7
1
Specifications
1-3 ELECTRICAL SPECIFICATIONS
(50HZ)
RXYHQ26P8W1B
RXYHQ28P8W1B
RXYHQ30P8W1B
RXYHQ32P8W1B
RXYHQ34P8W1B
RXYHQ36P8W1B
Power Supply
Name
W1
Phase
3N~
Frequency
Hz
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
Current
Nominal
running current
(RLA)
Cooling
A
26.3
30.1
37.9
45.7
49.5
57.3
Heating
A
27.5
30.4
32.2
34.0
36.9
38.7
Starting current (MSC)
A
82
91
91
92
101
101
Z-max
Text
0.27
0.25
0.25
0.25
0.24
0.24
Minimum Ssc value
kVa
3,364
3,074
3,260
3,446
3,156
3,342
Minimum circuit amps
(MCA)
A
58.6
61.7
62.8
63.9
67.0
68.1
Maximum fuse amps (MFA) A
80
80
80
80
80
80
Full load amps (FLA)
A
2.3
2.5
2.8
3.1
3.3
3.6
Voltage range
Minimum
V
360
360
360
360
360
360
Maximum
V
440
440
440
440
440
440
Wiring
connections
For Power
Supply
Quantity
5
5
5
5
5
5
Remark
Earth wire include
For connection
with indoor
Quantity
2
2
2
2
2
2
Remark
F1-F2
Power Supply Intake
Both indoor and outdoor unit
Notes
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
MSC means the maximum current during start up of the compressor
Maximum allowable voltage range variation between phases is 2%
RLA is based on following conditions : indoor temperature : 27×CDB/19×CWB , outdoor temperature : 35×CDB
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or
above listed range limits
In accordance with EN/IEC 61000-3-11(1), respectively EN/IEC 61000-3-12(2), it may be necessary to consult the
distribution network operator to ensure that the equipment is connected only to a supply with Zsys(4) <= Zmax,
respectively Ssc(3) >= minimum Ss
Select wire size based on MCA