3
|
Troubleshooting
Service manual
21
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.5.7 CC-00 – Humidity sensor abnormality
Trigger
Effect
Reset
▪
Disconnected sensor
▪
Broken sensor
▪
Communication error
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the humidity sensor. See
86].
Possible cause:
Faulty humidity sensor.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.5.8 CE-00 – Intelligent thermal sensor abnormality
Trigger
Effect
Reset
▪
Disconnected sensor
▪
Broken sensor
▪
Communication error
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the intelligent thermal sensor. See
122].
Possible cause:
Faulty intelligent thermal sensor.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.