135
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
CAUTION
Make sure the fuse is plugged‑in correctly (contact with the fuse holder).
a
a
a
a
Fuse
Is the problem solved?
Action
Yes
No further actions required.
No
Return to
126] of the PCB and
continue with the next procedure.
4.15 Outdoor unit fan motor
4.15.1 Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a mechanical check of the propeller fan blade assembly
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
If propeller fan blade touches the bell mounth, check if the fan motor is
correctly mounted on its base, see
2
Check the state of the propeller fan blade assembly for damage, deformations
and cracks.
Is the propeller fan blade assembly
damaged?
Action
Yes
Replace the propeller fan blade
assembly, see
138].
No
Perform a mechanical check of the DC
fan motor assembly, see
135].