background image

9

English

Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit.

1) Remove the valve cap from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4) After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.

Forced cooling operation

Using the indoor unit ON/OFF switch 

Press the indoor unit ON/OFF switch for at least 5 seconds. (Operation will start.)
• Forced cooling operation will stop automatically after around 15 minutes. 

To force a trial operation to stop, press the indoor unit ON/OFF switch.

Using the indoor unit’s remote controller

1) Press “MODE” button and select the cooling mode.
2) Press “ON/OFF” button to turn on the system.
3) Press both of “TEMP” button and “MODE” button at the same time.
4) Press “MODE” button twice. (

 will be displayed and the unit will enter trial 

operation.)

• Trial operation will stop automatically after around 30 minutes. To stop trial 

operation, press “ON/OFF” button.

Using the outdoor unit forced cooling operation switch (with standby 
electricity saving function turned off)

Push on “

” (SW1) with a screwdriver. (Operation will start.)

• Forced cooling operation will stop automatically after around 15 minutes.

To force a trial operation to stop, press the forced operation switch (SW1).

 CAUTION

• When pressing the switch, do not touch the terminal block. It has a high voltage, so doing so may cause electric shock.
• After closing the liquid stop valve, close the gas stop valve within 3 minutes, then stop the forced operation.

Facility Setting (cooling only model)

(cooling at low outdoor temperature)

This function is limited only for facilities (the target of air conditioning is equipment (such as computer)). Never use it in 
a residence or office (the space where there is a human).

1) Cutting jumper 4 (J4) on the circuit board will expand the operation range down to –15°C. However it will stop if the outdoor 

temperature drops below –20°C and start back up once the temperature rises again.

 CAUTION

• If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
• Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
• Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used. 

A humidifier might cause dew jumping from the indoor unit outlet vent.

• Cutting jumper 4 (J4) sets the indoor fan tap to the highest position. Notify the user about this.

Gas 
stop valve

Valve cap

Hexagonal 
wrench

Close

Liquid 
stop valve

Service port

1

2

3

The selective connector for standby electricity 
saving in use (with standby electricity saving 
function turned off)

Push here

Screwdriver

Power supply
terminal block

1

2

3

S70

S40

S2

S90

J5

J4

J3

Cut J4 with nippers 
or a similar tools.

01_EN_3P203824-8H.fm  Page 9  Tuesday, October 26, 2010  8:33 PM

Summary of Contents for RXS20J2V1B

Page 1: ...ion manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split systeem Manual de...

Page 2: ...e 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB64564 12E Shinri Sada Manager Quality Control Department DAIKIN TCF 015 N4 09 2010 RXS20J2V1B RXS25J2V1B RXS35J2V1B RKS20J2V1B RKS25J2V1B RKS3...

Page 3: ...ls If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrige...

Page 4: ...8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit a...

Page 5: ...necting the FVXS indoor unit the shortest piping length should be no less than around 2 5m 1 5m Min allowable length CAUTION Set the piping length from 1 5m to 20m Wrap the insulation pipe with the fi...

Page 6: ...door Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necess...

Page 7: ...re nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches Cut exactl...

Page 8: ...p valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping an...

Page 9: ...on dimensions as below 3 Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D 9 5mm O D 6 4mm...

Page 10: ...turned off Turn it off if has not been turned off 2 Remove the stop valve cover 3 Disconnect the selective connector for standby electricity saving 4 Turn on the main power supply CAUTION Before conne...

Page 11: ...ing the switch do not touch the terminal block It has a high voltage so doing so may cause electric shock After closing the liquid stop valve close the gas stop valve within 3 minutes then stop the fo...

Page 12: ...supply terminal board Precautions to be taken for power supply wiring Use a round crimp style terminal for connection to the power supply terminal board In case it cannot be used due to unavoidable r...

Page 13: ...tion in accordance with the operation manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a small amount of power in its standby mod...

Page 14: ...1101 HT 3P203824 8H M09B389 Two dimensional bar code is a code for manufacturing 00_CV_3P203824 8H fm Page 2 Thursday October 7 2010 11 00 AM...

Reviews: