Outdoor Unit Installation

6. 

Refilling the refrigerant

Check the type of refrigerant to be used on the machine nameplate.

Precautions when adding R410A

Fill from the gas pipe in liquid form.

It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation.
1)  Before filling, check whether the cylinder has a siphon attached or not. (It should have something like “liquid filling siphon 

attached” displayed on it.)

Filling a cylinder with an attached siphon

Stand the cylinder upright when 

filling.

There is a siphon pipe inside, so the 
cylinder need not be upside-down to 

fill with liquid.

Filling other cylinders

Turn the cylinder upside-down 

when filling.

• Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.

7. 

Refrigerant piping work

7-1 Caution on pipe handling 

1)  Protect the open end of the pipe against dust and moisture.
2)  All pipe bends should be as gentle as possible. Use a pipe bender for  

bending.

7-2 Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the following:
1)  Insulation material:  Polyethylene foam 

Heat transfer rate:  0.041 to 0.052W/mK (0.024 to 0.030Btu/fth°F (0.035 to 0.045kcal/mh°C)) 
Be sure to use insulation that is designed for use with HVAC Systems.

2)  Be sure to insulate both the gas and liquid piping and to provide insulation  

dimensions as below. 

Gas side

Liquid side

Gas pipe thermal 

insulation

Liquid pipe thermal 

insulation

O.D. 3/8 inch

(9.5mm)

O.D. 1/4 inch 

(6.4mm)

I.D. 15/32-19/32 inch

(12-15mm)

I.D. 5/16-13/32 inch  

(8-10mm)

Minimum bend radius

Thickness 13/32 inch (10mm) Min.

1-3/16 inch (30mm) or more

Thickness 0.031 inch (0.8mm) (C1220T-O)

• Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Wall

If no flare cap is 

available, cover the 

flare mouth with 

tape to keep dirt or 

water out.

Be sure to 

place a cap.

Rain

Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Inter-unit wire

01_EN_3P300674-1.indd   8

10/6/2011   1:37:43 PM

Summary of Contents for RXS09LVJU

Page 1: ...Installation manual R410A Split series Fran ais Espa ol Manual de instalaci n Serie Split R410A INSTALLATION MANUAL R410A Split Series Models RXS09LVJU RXS12LVJU 00_CV_3P300674 1 indd 1 10 18 2011 10...

Page 2: ...gs so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk...

Page 3: ...e to install a ground fault circuit interrupter breaker may result in electrically shocks or fire personal injury CAUTION Do not install the air conditioner where gas leakage would be exposed to open...

Page 4: ...more than 10ft 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain f...

Page 5: ...Max allowable piping height Min allowable piping length Max allowable piping length 65 6ft 20m 4 92ft 1 5m 49 2ft 15m Liquid pipe Gas pipe O D 1 4 inch 6 4mm O D 3 8 inch 9 5mm 0 21oz ft 20g m Additio...

Page 6: ...ndation drawing fix the unit securely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the f...

Page 7: ...he flare nuts to prevent damage to the flare nuts and gas leakage Flare nut tightening torque Liquid side 1 4 inch 6 4mm 10 4 12 7ft lbf 14 2 17 2N m Gas side 3 8 inch 9 5mm 24 1 29 4ft Ibf 32 7 39 9N...

Page 8: ...re gauge reads 29 9inHg 0 1MPa 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not sw...

Page 9: ...l pipe bends should be as gentle as possible Use a pipe bender for bending 7 2 Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the following 1...

Page 10: ...t use tapped wires stranded wires extension cords or starburst connections as they may cause overheating electrical shock or fire Do not use locally purchased electrical parts inside the product Do no...

Page 11: ...r power supply wiring CAUTION When connecting the connection wires to the terminal block using a single core wire be sure to perform curling Problems with the work may cause heat and fires Strip wire...

Page 12: ...S2 S90 J5 J4 J3 Cut J4 with nippers or a similar tools CAUTION If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind provide a windbreak wall Intermittent noi...

Page 13: ...uires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circui...

Page 14: ...3P300674 1 M11B134 1111 HT Two dimensional bar code is a code for manufacturing 00_CV_3P300674 1 indd 2 10 18 2011 10 38 27 AM...

Reviews: