Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit.

1)  Remove the valve cap from liquid stop valve and gas stop  

valve.

2)  Carry out forced cooling operation.
3)  After 5 to 10 minutes, close the liquid stop valve with a  

hexagonal wrench.

4)  After 2 to 3 minutes, close the gas stop valve and stop forced  

cooling operation.

Forced cooling operation

 

Using the indoor unit ON/OFF switch

Press the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.)

•  Forced cooling operation will stop automatically after around 15 minutes.  

To stop the operation, press the indoor unit ON/OFF switch.

 

Using the indoor unit’s remote controller

1)  Press “MODE” button and select the cooling mode.
2)  Press “ON/OFF” button to turn on the system.
3)  Press both of “TEMP” button and “MODE” button at the same time.
4)  Press “MODE” button twice. (   will be displayed and the unit will enter forced cooling operation.)

•  Forced cooling operation will stop automatically after around 30 minutes.  

To stop the operaion, press “ON/OFF” button.

 

Using the outdoor unit forced cooling operation switch

Forced cooling operation can be performed when the outdoor unit forced  
cooling operation switch is pressed within around 3 minutes after power  
is supplied. 
Push on “ 

 ” (SW1) with a screwdriver. (The operation will start.)

•  Forced cooling operation will stop automatically after around 15 minutes. 

To stop the operation, press the switch (SW1).

Wiring

   WARNING

• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

• Be sure to install a ground fault circuit interrupter breaker. (One that can handle higher harmonics.)  

(This unit uses an inverter, which means that it must be used a ground fault circuit interrupter breaker capable handling 
harmonics in order to prevent malfunctioning of the ground fault circuit interrupter breaker itself.)

• Use an all-pole disconnection type breaker with at least 1/8 inch (3mm) between the contact point gaps.
• When carrying out wiring connection, take care not to pull at the conduit.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

• Do not turn on the safety breaker until all work is completed.

1)  Strip the insulation from the wire (3/4inch (20mm)).
2)  Connect the connection wires between the  

indoor and outdoor units so that the terminal  
numbers match. Tighten the terminal screws  
securely. We recommend a flathead  
screwdriver be used to tighten the screws. 

Gas stop valve

Valve cap

Hexagonal wrench

Close

Liquid stop valve

Service port

1

2

3

Push

Screwdriver

Power supply
terminal block

Forced cooling 
operation switch
(SW1)

1

2

3

1 2 3

L

1

L

2

GR

Safety 

breaker 

15A

Ground fault

circuit interrupter

Ground

Use AWG16 if the connection wire 
length is less than 32.8ft (10m), or 
AWG14 if it is 32.8ft (10m) or more.

Outdoor unit

Indoor 
unit

Power supply
60Hz 208-230V

Use AWG 14 wires.

01_EN_3P300674-1.indd   9

10/6/2011   1:37:43 PM

Summary of Contents for RXS09LVJU

Page 1: ...Installation manual R410A Split series Fran ais Espa ol Manual de instalaci n Serie Split R410A INSTALLATION MANUAL R410A Split Series Models RXS09LVJU RXS12LVJU 00_CV_3P300674 1 indd 1 10 18 2011 10...

Page 2: ...gs so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk...

Page 3: ...e to install a ground fault circuit interrupter breaker may result in electrically shocks or fire personal injury CAUTION Do not install the air conditioner where gas leakage would be exposed to open...

Page 4: ...more than 10ft 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain f...

Page 5: ...Max allowable piping height Min allowable piping length Max allowable piping length 65 6ft 20m 4 92ft 1 5m 49 2ft 15m Liquid pipe Gas pipe O D 1 4 inch 6 4mm O D 3 8 inch 9 5mm 0 21oz ft 20g m Additio...

Page 6: ...ndation drawing fix the unit securely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the f...

Page 7: ...he flare nuts to prevent damage to the flare nuts and gas leakage Flare nut tightening torque Liquid side 1 4 inch 6 4mm 10 4 12 7ft lbf 14 2 17 2N m Gas side 3 8 inch 9 5mm 24 1 29 4ft Ibf 32 7 39 9N...

Page 8: ...re gauge reads 29 9inHg 0 1MPa 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not sw...

Page 9: ...l pipe bends should be as gentle as possible Use a pipe bender for bending 7 2 Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the following 1...

Page 10: ...t use tapped wires stranded wires extension cords or starburst connections as they may cause overheating electrical shock or fire Do not use locally purchased electrical parts inside the product Do no...

Page 11: ...r power supply wiring CAUTION When connecting the connection wires to the terminal block using a single core wire be sure to perform curling Problems with the work may cause heat and fires Strip wire...

Page 12: ...S2 S90 J5 J4 J3 Cut J4 with nippers or a similar tools CAUTION If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind provide a windbreak wall Intermittent noi...

Page 13: ...uires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circui...

Page 14: ...3P300674 1 M11B134 1111 HT Two dimensional bar code is a code for manufacturing 00_CV_3P300674 1 indd 2 10 18 2011 10 38 27 AM...

Reviews: