7

English

5. 

Purging air and checking gas leakage

   WARNING

• Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
• When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
• R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.
• Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum 

pump or the unit.

• When piping work is completed, it is necessary to purge the air and check for  

gas leakage.

• If using additional refrigerant, perform air purging from the refrigerant pipes  

and indoor unit using a vacuum pump, then charge additional refrigerant.

• Use a hexagonal wrench (3/16 inch (4mm)) to operate the stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench at the  

specified tightening torque.

1)  Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s service port.

2)  Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi).  

(High-pressure valve subsequently requires no operation.)

3)   Do vacuum pumping and make sure that the compound pressure gauge reads –29.9inHg (–0.1MPa).*1

4)  Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump.  

(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2

5)  Remove caps from liquid stop valve and gas stop valve.

6)  Turn the liquid stop valve’s rod 90 degrees counterclockwise with a hexagonal wrench to open valve. 

Close it after 5 seconds, and check for gas leakage. 
Using soapy water, check for gas leakage from indoor unit’s flare and outdoor unit’s flare and valve rods. 
After the check is complete, wipe all soapy water off.

7)  Disconnect charging hose from gas stop valve’s service port, then fully open liquid and gas stop valves. 

(Do not attempt to turn valve rod beyond its stop.)

8)  Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.

*1. Pipe length vs. vacuum pump run time

Pipe length

Up to 49.2ft (15m)

More than 49.2ft (15m)

Run time

Not less than 10 min.

Not less than 15 min

*2.  If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exists. Check 

all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).

Gauge 

manifold

Compound 

pressure gauge

Pressure meter

Low-pressure 

valve

High-pressure 

valve

Charging 

hoses

Vacuum pump

Valve caps

Service port

Liquid 

stop 

valve

Gas 

stop 

valve

01_EN_3P300674-1.indd   7

10/6/2011   1:37:42 PM

Summary of Contents for RXS09LVJU

Page 1: ...Installation manual R410A Split series Fran ais Espa ol Manual de instalaci n Serie Split R410A INSTALLATION MANUAL R410A Split Series Models RXS09LVJU RXS12LVJU 00_CV_3P300674 1 indd 1 10 18 2011 10...

Page 2: ...gs so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk...

Page 3: ...e to install a ground fault circuit interrupter breaker may result in electrically shocks or fire personal injury CAUTION Do not install the air conditioner where gas leakage would be exposed to open...

Page 4: ...more than 10ft 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain f...

Page 5: ...Max allowable piping height Min allowable piping length Max allowable piping length 65 6ft 20m 4 92ft 1 5m 49 2ft 15m Liquid pipe Gas pipe O D 1 4 inch 6 4mm O D 3 8 inch 9 5mm 0 21oz ft 20g m Additio...

Page 6: ...ndation drawing fix the unit securely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the f...

Page 7: ...he flare nuts to prevent damage to the flare nuts and gas leakage Flare nut tightening torque Liquid side 1 4 inch 6 4mm 10 4 12 7ft lbf 14 2 17 2N m Gas side 3 8 inch 9 5mm 24 1 29 4ft Ibf 32 7 39 9N...

Page 8: ...re gauge reads 29 9inHg 0 1MPa 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not sw...

Page 9: ...l pipe bends should be as gentle as possible Use a pipe bender for bending 7 2 Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the following 1...

Page 10: ...t use tapped wires stranded wires extension cords or starburst connections as they may cause overheating electrical shock or fire Do not use locally purchased electrical parts inside the product Do no...

Page 11: ...r power supply wiring CAUTION When connecting the connection wires to the terminal block using a single core wire be sure to perform curling Problems with the work may cause heat and fires Strip wire...

Page 12: ...S2 S90 J5 J4 J3 Cut J4 with nippers or a similar tools CAUTION If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind provide a windbreak wall Intermittent noi...

Page 13: ...uires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circui...

Page 14: ...3P300674 1 M11B134 1111 HT Two dimensional bar code is a code for manufacturing 00_CV_3P300674 1 indd 2 10 18 2011 10 38 27 AM...

Reviews: