5 Commissioning

Installation manual

9

(A)RXP20~35M5V1B
R32 split series
3P519299-5B – 2018.12

4.6.1

Specifications of standard wiring
components

Component

Power supply cable Voltage

220~240 V

Phase

1~

Frequency

50 Hz

Wire sizes

MUST comply with

applicable legislation

Interconnection cable
(indoor↔outdoor)

4-core cable ≥1.5 mm² and

applicable for 220~240 V

Recommended field fuse

16 A

Earth leakage circuit breaker

MUST comply with

applicable legislation

4.6.2

To connect the electrical wiring on the
outdoor unit

1

Remove the service cover.

2

Open the wire clamp.

3

Connect the interconnection cable and power supply as follows:

a

Interconnection cable

b

Power supply cable

c

Circuit breaker

d

Earth leakage circuit breaker

e

Power supply

f

Earth

4

Tighten  the  terminal  screws  securely.  We  recommend  using  a
Phillips screwdriver.

4.7

Finishing the outdoor unit
installation

4.7.1

To finish the outdoor unit installation

1

Insulate and fix the refrigerant piping and interconnection cable
as follows:

f

b

a

e

d

c

a

Gas pipe

b

Gas pipe insulation

c

Interconnection cable

d

Liquid pipe

e

Liquid pipe insulation

f

Finishing tape

2

Install the service cover.

4.7.2

To close the outdoor unit

NOTICE

When  closing  the  outdoor  unit  cover,  make  sure  that  the
tightening torque does NOT exceed 1.3 N•m.

2

1

1

5

Commissioning

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or
pressure  sensors/switches.  Burning  of  the  compressor
might result.

5.1

Checklist before commissioning

After the installation of the unit, first check the following items. Once
all  below  checks  are  fulfilled,  the  unit  MUST  be  closed,  ONLY  then
can the unit be powered up.

The 

indoor unit

 is properly mounted.

The 

outdoor unit

 is properly mounted.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

There are NO 

refrigerant leaks

.

The 

refrigerant  pipes

  (gas  and  liquid)  are  thermally

insulated.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

The 

stop valves

 (gas and liquid) on the outdoor unit are

fully open.

The following 

field wiring

 has been carried out according

to  this  document  and  the  applicable  legislation  between
the outdoor unit and the indoor unit.

Drainage

Make sure drainage flows smoothly.

Possible consequence: 

Condensate water might drip.

The indoor unit receives the signals of the 

user interface

.

The  specified  wires  are  used  for  the 

interconnection

cable

.

The 

fuses, circuit breakers,

 or locally installed protection

devices  are  installed  according  to  this  document,  and
have NOT been bypassed.

5.2

Checklist during commissioning

To perform an 

air purge

.

Summary of Contents for RXP25M5V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXP20M5V1B RXP25M5V1B RXP35M5V1B ARXP20M5V1B ARXP25M5V1B ARXP35M5V1B...

Page 2: ...ka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumiem atbilst sekojo iem standartiem un citie...

Page 3: ...9 4 6 2 To connect the electrical wiring on the outdoor unit 9 4 7 Finishing the outdoor unit installation 9 4 7 1 To finish the outdoor unit installation 9 4 7 2 To close the outdoor unit 9 5 Commis...

Page 4: ...stall a baffle plate when the air outlet is exposed to wind It is recommended to install the outdoor unit with the air inlet facing the wall and NOT directly exposed to the wind b a b c a Baffle plate...

Page 5: ...12 m 3 2 3 Refrigerant piping insulation Pipe outer diameter p Insulation inner diameter i Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 9 5 mm 3 8 12 15 mm i i t p p If the temperature is higher t...

Page 6: ...necting the refrigerant piping involves Connecting the refrigerant piping to the indoor unit Connecting the refrigerant piping to the outdoor unit Insulating the refrigerant piping Keeping in mind the...

Page 7: ...recharging refrigerant Example When relocating the system After a leak Charging additional refrigerant Before charging additional refrigerant make sure the outdoor unit s external refrigerant piping i...

Page 8: ...2 Charge the additional refrigerant amount 3 Open the gas stop valve 4 5 6 To fix the fluorinated greenhouse gases label 1 Fill in the label as follows b Contains fluorinated greenhouse gases 2 1 1 1...

Page 9: ...E NEVER operate the unit without thermistors and or pressure sensors switches Burning of the compressor might result 5 1 Checklist before commissioning After the installation of the unit first check t...

Page 10: ...T use the unit s automatic pump down function with which you can collect all refrigerant from the system into the outdoor unit Possible consequence Self combustion and explosion of the compressor beca...

Page 11: ...TER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VO...

Page 12: ...MA S STEMLER SAN T C A K kbakkalk y Mah Kay da Cad No 1 Kat 21 22 34750 Ata ehir STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr 3P519299 5B 2018 12...

Reviews: