4 Installation

Installation manual

6

(A)RXP20~35M5V1B

R32 split series

3P519299-5B – 2018.12

4.2.3

To provide drainage

NOTICE

If  the  unit  is  installed  in  a  cold  climate,  take  adequate
measures  so  that  the  evacuated  condensate  CANNOT
freeze.

INFORMATION

For  information  on  the  available  options,  contact  your
dealer.

NOTICE

Provide  at  least  300  mm  of  free  space  below  the  unit.
Additionally,  make  sure  the  unit  is  positioned  at  least
100 mm above the expected level of snow.

1

Use a drain plug for drainage.

2

Use a Ø16 mm hose (field supply).

b

c

d

a

a

Drain port

b

Bottom frame

c

Drain plug

d

Hose (field supply)

4.2.4

To prevent the outdoor unit from falling
over

In  case  the  unit  is  installed  in  places  where  strong  wind  can  tilt  the
unit, take following measure:

1

Prepare  2  cables  as  indicated  in  the  following  illustration  (field
supply).

2

Place the 2 cables over the outdoor unit.

3

Insert  a  rubber  sheet  between  the  cables  and  the  outdoor  unit
to prevent the cables from scratching the paint (field supply).

4

Attach the ends of the cables and tighten them.

4.3

Connecting the refrigerant piping

DANGER: RISK OF BURNING

4.3.1

About connecting the refrigerant piping

Before connecting the refrigerant piping

Make sure the outdoor and indoor unit are mounted.

Typical workflow

Connecting the refrigerant piping involves:

▪ Connecting the refrigerant piping to the indoor unit

▪ Connecting the refrigerant piping to the outdoor unit

▪ Insulating the refrigerant piping

▪ Keeping in mind the guidelines for:

▪ Pipe bending

▪ Flaring pipe ends

▪ Using the stop valves

4.3.2

Precautions when connecting the
refrigerant piping

DANGER: RISK OF BURNING

CAUTION

▪ Use the flare nut fixed to the main unit.

▪ To  prevent  gas  leakage,  apply  refrigeration  oil  only  to

the inside of the flare. Use refrigeration oil for R32.

▪ Do NOT reuse joints.

WARNING

Connect the refrigerant piping securely before running the
compressor. If the refrigerant piping is NOT connected and
the stop valve is open when the compressor is run, air will
be  sucked  in.  This  will  cause  abnormal  pressure  in  the
refrigeration cycle, which may result in equipment damage
and even injury.

4.3.3

To connect the refrigerant piping to the
outdoor unit

Piping length.

 Keep field piping as short as possible.

Piping  protection.

  Protect  the  field  piping  against  physical

damage.

1

Connect the liquid refrigerant connection from the indoor unit to
the liquid stop valve of the outdoor unit.

a

b

c

a

Liquid stop valve

b

Gas stop valve

c

Service port

2

Connect  the  gas  refrigerant  connection  from  the  indoor  unit  to
the gas stop valve of the outdoor unit.

NOTICE

It  is  recommended  that  the  refrigerant  piping  between
indoor  and  outdoor  unit  is  installed  in  a  ducting  or  the
refrigerant piping is wrapped with finishing tape.

Summary of Contents for RXP25M5V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXP20M5V1B RXP25M5V1B RXP35M5V1B ARXP20M5V1B ARXP25M5V1B ARXP35M5V1B...

Page 2: ...ka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumiem atbilst sekojo iem standartiem un citie...

Page 3: ...9 4 6 2 To connect the electrical wiring on the outdoor unit 9 4 7 Finishing the outdoor unit installation 9 4 7 1 To finish the outdoor unit installation 9 4 7 2 To close the outdoor unit 9 5 Commis...

Page 4: ...stall a baffle plate when the air outlet is exposed to wind It is recommended to install the outdoor unit with the air inlet facing the wall and NOT directly exposed to the wind b a b c a Baffle plate...

Page 5: ...12 m 3 2 3 Refrigerant piping insulation Pipe outer diameter p Insulation inner diameter i Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 9 5 mm 3 8 12 15 mm i i t p p If the temperature is higher t...

Page 6: ...necting the refrigerant piping involves Connecting the refrigerant piping to the indoor unit Connecting the refrigerant piping to the outdoor unit Insulating the refrigerant piping Keeping in mind the...

Page 7: ...recharging refrigerant Example When relocating the system After a leak Charging additional refrigerant Before charging additional refrigerant make sure the outdoor unit s external refrigerant piping i...

Page 8: ...2 Charge the additional refrigerant amount 3 Open the gas stop valve 4 5 6 To fix the fluorinated greenhouse gases label 1 Fill in the label as follows b Contains fluorinated greenhouse gases 2 1 1 1...

Page 9: ...E NEVER operate the unit without thermistors and or pressure sensors switches Burning of the compressor might result 5 1 Checklist before commissioning After the installation of the unit first check t...

Page 10: ...T use the unit s automatic pump down function with which you can collect all refrigerant from the system into the outdoor unit Possible consequence Self combustion and explosion of the compressor beca...

Page 11: ...TER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VO...

Page 12: ...MA S STEMLER SAN T C A K kbakkalk y Mah Kay da Cad No 1 Kat 21 22 34750 Ata ehir STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr 3P519299 5B 2018 12...

Reviews: