10

English

Wiring

 WARNING

• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, 

electrical shock, or fire.

• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

• Be sure to install an earth leak detector. (One that can handle higher harmonics.)

(This unit uses an inverter, which means that an earth leak detector capable of handling higher harmonics must be used, in 
order to prevent malfunctioning of the earth leak detector itself.)

• Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

• Do not turn ON the safety breaker until all work is completed.

1) Strip the insulation from the wire (20mm).
2) Connect the connection wires between the 

indoor and outdoor units so that the terminal 
numbers match. Tighten the terminal screws 
securely. We recommend a flathead 
screwdriver be used to tighten the screws. 
The screws are packed with the terminal block. 

Observe the notes mentioned below when wiring to the power supply terminal block.
Precautions to be taken for power supply wiring.

 CAUTION

• When connecting the connection wires to the terminal block using a single core wire, be sure to perform curling.

Problems with the work may cause heat and fires.  

• If the stranded wires must be used, make sure to use the round 

crimp-style terminal for connection to the power supply terminal 
block. Place the round crimp-style terminals on the wires up to the 
covered part and secure in place.

3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.

Safety 
breaker 
10A

Earth leakage 
circuit breaker

Earth

Inter-unit wire 
4-core 1.5mm² or more
H05RN

Firmly fix the wires with 
the terminal screws.

Outdoor unit

Indoor 
unit

Power supply
50Hz 220-240V

Firmly fix the wires with 
the terminal screws.

Power supply wire 
3-core 2.5mm² or more
H05RN

Use the specified wire type 
and connect it securely.

Firmly secure wire retainer so wire 
terminations will not receive external stress.

Power supply 
terminal block

Shape wires so 
that the service lid 
and stop valve 
cover fit securely.

Strip wire end 
to this point.

Excessive strip length 
may cause electrical 
shock or leakage.

Good

Wrong

Good

Wrong

Stripping wire at terminal block

Stranded wire

Round crimp-style 
terminal

Summary of Contents for RXJ20M2V1B

Page 1: ...INSTALLATION MANUAL R32 Split Series Models RXJ20M2V1B RXJ25M2V1B RXJ35M2V1B RXM20M2V1B RXM25M2V1B RXM35M2V1B ARXM25M2V1B ARXM35M2V1B...

Page 2: ...amente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B d...

Page 3: ...ion lead as this may cause overheating electric shocks or fire Make sure that all wiring is secured the specified wires are used and that there is no strain on the terminal connections or wires Improp...

Page 4: ...be installed hanging from ceiling or stacked CAUTION Do not install the air conditioner at any place where there is a danger of flammable gas leakage In the event of a gas leakage build up of gas nea...

Page 5: ...ion side facing the wall Never install the outdoor unit at a site where the suction side may be exposed directly to wind To prevent exposure to wind it is recommended to install a baffle plate on the...

Page 6: ...nger of the unit falling use foot bolts or wires 250mm from wall unit mm How to remove the stop valve cover Remove the screw on the stop valve cover Slide the cover downward to remove it How to attach...

Page 7: ...e foundation surface Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2...

Page 8: ...age to the flare nuts and gas leakage After the piping work is finished after checking for gas leaks open the stop valves or the compressor might break down Align the centres of both flares and tighte...

Page 9: ...is necessary to evacuate the air and check for gas leakage If using additional refrigerant perform air evacuating from the refrigerant pipes and indoor unit using a vacuum pump then charge additional...

Page 10: ...y water off 7 Disconnect charging hose from gas stop valve s service port then fully open liquid and gas stop valves Do not attempt to turn valve rod beyond its stop 8 Tighten valve caps and service p...

Page 11: ...losing the liquid stop valve close the gas stop valve within 3 minutes then stop the forced cooling operation Facility Setting cooling at low outdoor temperature This function is designed for faciliti...

Page 12: ...nal block Observe the notes mentioned below when wiring to the power supply terminal block Precautions to be taken for power supply wiring CAUTION When connecting the connection wires to the terminal...

Page 13: ...RMISTOR DS DIPSWITCH RC RECEIVER E H HEATER S C LIMITSWITCH F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S L FLOATSWITCH FG CONNECTOR FRAMEGROUND S NPH PRESSURESENSOR HIGH H HARNESS S NPL P...

Page 14: ...a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit brea...

Page 15: ......

Page 16: ...3P386697 2C 2015 10 Copyright 2015 Daikin...

Reviews: