3
English
Outdoor Unit Installation Drawings
**
*
’
Wrap the insulation
pipe with the finishing
tape from bottom to top.
Max. allowable piping height
Min. allowable piping length
Max. allowable piping length
30m
1.5m
20m
Liquid pipe
Gas pipe
O.D. 6.4mm
O.D. 12.7mm
20g/m
Additional refrigerant
required for refrigerant
pipe exceeding 10m in
length.
*
Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
**
The suggested shortest pipe length is 1.5m, in order to avoid
noise from the outdoor unit and vibration.
(Mechanical noise and vibration may occur depending on how
the unit is installed and the environment in which it is used.)
When connecting the FVXG indoor unit, the shortest piping
length should be no less than about 2.5m.
(Foot bolt-hole
centres)
330
250mm from wall
Stop valve cover
Service lid
(Foot bolt-hole centres)
580
120
(From unit’
s side)
unit: mm
CAUTION
**Set the piping length
from 1.5m to 30m.
Allow space for piping
and electrical servicing.
Where there is a danger of
the unit falling, use foot bolts,
or wires.
In sites with poor drainage,
use block bases for outdoor
unit.
Adjust foot height until the
unit is leveled. Otherwise,
water leakage or pooling of
water may occur.
Allow 300mm of
work space below
the ceiling surface.