Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit.

1) Remove the valve cap from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4) After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.

Forced cooling operation

Using the indoor unit ON/OFF switch

Press the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.)

• Forced cooling operation will stop automatically after around 15 minutes. 

To stop the operation, press the indoor unit ON/OFF switch.

Using the indoor unit’s remote controller

1) Press the 

On/Off

 button to turn on the system. 

2) Press the center of the 

Temp

 button and the 

Mode

 button at the same time.

3) Select 

 (trial operation) with the 

Temp

 or 

Temp

 button. 

4) Press the 

Mode

 button to start the trial operation.

5) Press the 

Mode

 button and select operation mode.

6) Trial operation terminates in approx. 30 minutes and switches into normal mode. To quit trial operation, press the 

On/Off

button.

Using the outdoor unit forced cooling 
operation switch 

Forced cooling operation can be performed 
when the outdoor unit forced cooling 
operation switch is pressed within around 
3 minutes after power is supplied.

• Push on  “

” (SW1) with a screwdriver.  

(The operation will start.)

• Forced cooling operation will stop 

automatically after around 15 minutes.
To stop the operation, press the switch 
(SW1).

Standby Electricity Saving

The standby electricity saving function turns off power supply to the outdoor unit and sets the indoor unit into 
standby electricity saving mode, thus reducing the power consumption of the air conditioner.

Procedure for turning on standby electricity saving function

1) Check that the main power supply is turned off. Turn it off if it has 

not been turned off.

2) Remove the stop valve cover.
3) Disconnect the selective connector for standby electricity saving.
4) Turn on the main power supply.

 CAUTION

• Before connecting or disconnecting the selective connector for standby electricity saving, make sure that the main power 

supply is turned off.

• The selective connector for standby electricity saving is required if an indoor unit other than the above applicable one is 

connected.

Liquid stop valve

Gas stop valve

Service port

Valve cap

Close

Hexagonal 

wrench

Screwdriver

Push

Forced cooling 

operation switch 

(SW1)

1

2

3

1

2

3

Standby electricity saving 
function off.

Standby electricity saving 
function on.

The standby electricity saving function is turned off before 
shipping.

3PEN358184-2E.book  Page 8  Friday, October 23, 2015  10:54 AM

Summary of Contents for RXG50L2V1B

Page 1: ...rie split R410A Fran ais Montagehandleiding R410A Split systeem Nederlands Manual de instalaci n Serie Split R410A Espa ol Manuale d installazione Serie Multiambienti R410A Italiano R410A Manual de I...

Page 2: ...B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo c...

Page 3: ...en wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control bo...

Page 4: ...iling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent exposure to wind install the outdoor unit...

Page 5: ...e and vibration may occur depending on how the unit is installed and the environment in which it is used When connecting the FVXG indoor unit the shortest piping length should be no less than about 2...

Page 6: ...Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessary...

Page 7: ...he flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches A A...

Page 8: ...h comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requir...

Page 9: ...and to provide insulation dimensions as below Use separate thermal insulation for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D...

Page 10: ...utdoor unit forced cooling operation switch is pressed within around 3 minutes after power is supplied Push on SW1 with a screwdriver The operation will start Forced cooling operation will stop automa...

Page 11: ...he screws Observe the notes mentioned below when wiring to the power supply terminal block Precautions to be taken for power supply wiring CAUTION When connecting the wires to the terminal block using...

Page 12: ...ser DISCHARGE Discharge C7 C8 Capacitor DB1 DB3 Diode bridge FU1 FU2 FU3 Fuse FU4 Field fuse IPM Intelligent power module L Live L803 L804 Reactor M1C Compressor motor M1F Fan motor MRCW MRM10 MRM20 M...

Page 13: ...nt of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to...

Page 14: ...3P358184 2E 2015 10 Copyright 2014 Daikin 3PEN358184 2E book Page 1 Friday October 23 2015 10 54 AM...

Reviews: