7 Electrical installation

Installation manual

19

ARXM50-71+RXM42~7 RXP50~7
RXA42+5 RXF50+6 RXF7
RXJ5 ARXF50~71A2V1B
R32 split series
3P512025-9S – 2020.05

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

DANGER: RISK OF ELECTROCUTION

All  electrical  parts  (including  thermistors)  are  powered  by
the power supply. Do not touch them with bare hands.

DANGER: RISK OF ELECTROCUTION

Disconnect  the  power  supply  for  more  than  10  minutes,
and  measure  the  voltage  at  the  terminals  of  main  circuit
capacitors  or  electrical  components  before  servicing.  The
voltage MUST be less than 50 V DC before you can touch
electrical  components.  For  the  location  of  the  terminals,
see the wiring diagram.

b

c

DC P1+

DC N1-

a

d

e

g

f

a

Multimeter (DC voltage range)

b

S80 – reversing solenoid valve lead wire

c

S20 – electronic expansion valve lead wire

d

S40 – thermal overload relay lead wire

e

S90 – thermistor lead wire

f

LED

g

S70 – fan motor lead wire

7.1

Specifications of standard wiring
components

Component

Power supply
cable

Voltage

220~240 V

Phase

1~

Frequency

50 Hz

Wire sizes

3-core cable

2.5 mm2~4.0 mm

2

H05RN-F (60245 IEC 57)

Interconnection cable
(indoor↔outdoor)

4-core cable

1.5 mm

2

~2.5 mm

2

 and applicable for

220~240 V

H05RN-F (60245 IEC 57)

Component

Recommended circuit breaker RXM71R

RXP50~71M

RXF50+60B

RXF71A

ARXF50~71A

20 A

(a)

ARXM50~71R

RXM50+60R

16 A

RXM42R

RXA42+50R

RXJ50N

13 A

Earth leakage circuit breaker

MUST comply with applicable

legislation

(a)

Electrical equipment complying with EN/IEC 61000-3-12
(European/International Technical Standard setting the limits for
harmonic currents produced by equipment connected to public
low-voltage systems with input current >16 A and ≤75 A per
phase).

7.2

To connect the electrical wiring to
the outdoor unit

1

Remove the switch box cover.

2

Open the wire clamp.

3

Connect the interconnection cable and power supply as follows:

50 Hz

220-240 V

c

d

f

a

b

e

a

Interconnection cable

b

Power supply cable

c

Circuit breaker

d

Residual current device

e

Power supply

f

Earth

1 2 3

4

Tighten  the  terminal  screws  securely.  We  recommend  using  a
Phillips screwdriver.

5

Install the switch box cover.

Summary of Contents for RXF71A2V1B

Page 1: ...tallation manual R32 split series RXF50B2V1B RXF60B2V1B RXF71A2V1B ARXF50A2V1B ARXF60A2V1B ARXF71A2V1B RXP50M2V1B RXP60M2V1B RXP71M2V1B ARXM50R2V1B ARXM60R2V1B ARXM71R2V1B RXM42R2V1B RXM50R2V1B RXM60R...

Page 2: ...er Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor...

Page 3: ...ava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TS...

Page 4: ...atte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 D...

Page 5: ...ava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TS...

Page 6: ...ellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele...

Page 7: ...ava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TS...

Page 8: ...sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamente...

Page 9: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Page 10: ...endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Direc...

Page 11: ...ava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TS...

Page 12: ...d 21 12 2 Piping diagram 22 12 2 1 Piping diagram Outdoor unit 22 1 About the documentation 1 1 About this document INFORMATION Make sure that the user has the printed documentation and ask him her to...

Page 13: ...lare nuts may cause refrigerant gas leakage CAUTION Do NOT open the valves before flaring is complete This would cause refrigerant gas leakage DANGER RISK OF EXPLOSION Do NOT start the unit if it is v...

Page 14: ...RISK OF ELECTROCUTION Make sure that the system is earthed properly Turn off the power supply before servicing Install the switch box cover before turning on the power supply Commissioning see 9 Comm...

Page 15: ...it is positioned at least 100 mm above the maximum expected level of snow If necessary construct a pedestal See 4 2 Mounting the outdoor unit 415 for more details In heavy snowfall areas it is very im...

Page 16: ...ene foam as insulation material with a heat transfer rate between 0 041 and 0 052 W mK 0 035 and 0 045 kcal mh C with a heat resistance of at least 120 C Insulation thickness Pipe outer diameter p Ins...

Page 17: ...nnections 3 Discharge all nitrogen gas 5 3 2 To perform vacuum drying DANGER RISK OF EXPLOSION Do NOT start the unit if it is vacuumed 1 Vacuum the system until the pressure on the manifold indicates...

Page 18: ...1 Fill in the label as follows b Contains fluorinated greenhouse gases 2 1 1 1 2 2 kg tCO2 eq GWP kg 1000 kg kg GWP XXX RXXX a f c d e a If a multilingual fluorinated greenhouse gases label is deliver...

Page 19: ...lve lead wire d S40 thermal overload relay lead wire e S90 thermistor lead wire f LED g S70 fan motor lead wire 7 1 Specifications of standard wiring components Component Power supply cable Voltage 22...

Page 20: ...oor unit are fully open The following field wiring has been carried out according to this document and the applicable legislation between the outdoor unit and the indoor unit Drainage Make sure draina...

Page 21: ...nector A Rectifier Earth Relay connector Field wiring Short circuit connector Fuse Terminal INDOOR Indoor unit Terminal strip OUTDOOR Outdoor unit Wire clamp Residual current device Symbol Colour Symb...

Page 22: ...oise filter 12 2 Piping diagram 12 2 1 Piping diagram Outdoor unit PED categories of equipment High pressure switch category IV Compressor category II Other equipment art 4 3 HPS 7 0 CuT 7 0 CuT 7 0 C...

Page 23: ...2 7 CuT 12 7 CuT 12 7 CuT 12 7 CuT 9 5 CuT 6 4 CuT 9 5 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 4 0 CuT 4 0 CuT 4 0 CuT 9 5 CuT 12 7 CuT 12 7 CuT 6 4 CuT RXP60M RXP71M RXF60B RXF71A ARXF60A ARXF71A b a c d...

Page 24: ...0 CuT 7 0 CuT 12 7 CuT 12 7 CuT 12 7 CuT 12 7 CuT 12 7 CuT 6 4 CuT 9 5 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 4 0 CuT 4 0 CuT 4 0 CuT 9 5 CuT 9 5 CuT 6 4 CuT 12 7 CuT b a c d m m m j3 n o l e j1 i i i j...

Page 25: ...9 5 CuT 9 5 CuT 9 5 CuT 9 5 CuT 9 5 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 12 7 CuT 12 7 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT j3 b a c d f h g j1 i i i 4 0 CuT 4 0 CuT 4 0...

Page 26: ......

Page 27: ......

Page 28: ...3P512025 9S 2020 05 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...

Reviews: