4 Unit installation

Installation manual

15

ARXM50-71+RXM42~7 RXP50~7
RXA42+5 RXF50+6 RXF7
RXJ5 ARXF50~71A2V1B
R32 split series
3P512025-9S – 2020.05

NOTICE

The height of the wall on the outlet side of the outdoor unit
MUST be ≤1200 mm.

Do  NOT  install  the  unit  in  sound  sensitive  areas  (e.g.  near  a
bedroom), so that the operation noise will cause no trouble.

Note: 

If  the  sound  is  measured  under  actual  installation  conditions,

the  measured  value  might  be  higher  than  the  sound  pressure  level
mentioned  in  "Sound  spectrum"  in  the  data  book  due  to
environmental noise and sound reflections.

INFORMATION

The sound pressure level is less than 70 dBA.

4.1.2

Additional installation site requirements
of the outdoor unit in cold climates

Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.

a

b

c

c

d

a

Snow cover or shed

b

Pedestal

c

Prevailing wind direction

d

Air outlet

It  is  recommended  to  provide  at  least  150  mm  of  free  space  below
the unit (300 mm for heavy snowfall areas). Additionally, make sure
the unit is positioned at least 100 mm above the maximum expected
level of snow. If necessary, construct a pedestal. See 

"4.2 Mounting

the outdoor unit" 

[

4

 15] for more details.

In  heavy  snowfall  areas  it  is  very  important  to  select  an  installation
site  where  the  snow  will  NOT  affect  the  unit.  If  lateral  snowfall  is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.

4.2

Mounting the outdoor unit

4.2.1

To provide the installation structure

Use a vibration-proof rubber (field supply) in cases where vibrations
may be transmitted to the building.

Prepare  4  sets  of  M8  or  M10  anchor  bolts,  nuts  and  washers  (field
supply).

20 mm

353

600

240

(mm)

240

a

a

100 mm above expected level of snow

4.2.2

To install the outdoor unit

4× M8/M10

4.2.3

To provide drainage

NOTICE

If  the  unit  is  installed  in  a  cold  climate,  take  adequate
measures  so  that  the  evacuated  condensate  CANNOT
freeze.

NOTICE

If  the  drain  holes  of  the  outdoor  unit  are  blocked  up  by  a
mounting base or floor surface, place additional foot bases
≤30 mm under the outdoor unit's feet.

INFORMATION

For  information  on  the  available  options,  contact  your
dealer.

1

Use a drain plug for drainage.

2

Use a Ø16 mm hose (field supply).

b

c

d

a

a

Drain port

b

Bottom frame

Summary of Contents for RXF71A2V1B

Page 1: ...tallation manual R32 split series RXF50B2V1B RXF60B2V1B RXF71A2V1B ARXF50A2V1B ARXF60A2V1B ARXF71A2V1B RXP50M2V1B RXP60M2V1B RXP71M2V1B ARXM50R2V1B ARXM60R2V1B ARXM71R2V1B RXM42R2V1B RXM50R2V1B RXM60R...

Page 2: ...er Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor...

Page 3: ...ava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TS...

Page 4: ...atte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 D...

Page 5: ...ava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TS...

Page 6: ...ellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele...

Page 7: ...ava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TS...

Page 8: ...sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamente...

Page 9: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Page 10: ...endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Direc...

Page 11: ...ava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TS...

Page 12: ...d 21 12 2 Piping diagram 22 12 2 1 Piping diagram Outdoor unit 22 1 About the documentation 1 1 About this document INFORMATION Make sure that the user has the printed documentation and ask him her to...

Page 13: ...lare nuts may cause refrigerant gas leakage CAUTION Do NOT open the valves before flaring is complete This would cause refrigerant gas leakage DANGER RISK OF EXPLOSION Do NOT start the unit if it is v...

Page 14: ...RISK OF ELECTROCUTION Make sure that the system is earthed properly Turn off the power supply before servicing Install the switch box cover before turning on the power supply Commissioning see 9 Comm...

Page 15: ...it is positioned at least 100 mm above the maximum expected level of snow If necessary construct a pedestal See 4 2 Mounting the outdoor unit 415 for more details In heavy snowfall areas it is very im...

Page 16: ...ene foam as insulation material with a heat transfer rate between 0 041 and 0 052 W mK 0 035 and 0 045 kcal mh C with a heat resistance of at least 120 C Insulation thickness Pipe outer diameter p Ins...

Page 17: ...nnections 3 Discharge all nitrogen gas 5 3 2 To perform vacuum drying DANGER RISK OF EXPLOSION Do NOT start the unit if it is vacuumed 1 Vacuum the system until the pressure on the manifold indicates...

Page 18: ...1 Fill in the label as follows b Contains fluorinated greenhouse gases 2 1 1 1 2 2 kg tCO2 eq GWP kg 1000 kg kg GWP XXX RXXX a f c d e a If a multilingual fluorinated greenhouse gases label is deliver...

Page 19: ...lve lead wire d S40 thermal overload relay lead wire e S90 thermistor lead wire f LED g S70 fan motor lead wire 7 1 Specifications of standard wiring components Component Power supply cable Voltage 22...

Page 20: ...oor unit are fully open The following field wiring has been carried out according to this document and the applicable legislation between the outdoor unit and the indoor unit Drainage Make sure draina...

Page 21: ...nector A Rectifier Earth Relay connector Field wiring Short circuit connector Fuse Terminal INDOOR Indoor unit Terminal strip OUTDOOR Outdoor unit Wire clamp Residual current device Symbol Colour Symb...

Page 22: ...oise filter 12 2 Piping diagram 12 2 1 Piping diagram Outdoor unit PED categories of equipment High pressure switch category IV Compressor category II Other equipment art 4 3 HPS 7 0 CuT 7 0 CuT 7 0 C...

Page 23: ...2 7 CuT 12 7 CuT 12 7 CuT 12 7 CuT 9 5 CuT 6 4 CuT 9 5 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 4 0 CuT 4 0 CuT 4 0 CuT 9 5 CuT 12 7 CuT 12 7 CuT 6 4 CuT RXP60M RXP71M RXF60B RXF71A ARXF60A ARXF71A b a c d...

Page 24: ...0 CuT 7 0 CuT 12 7 CuT 12 7 CuT 12 7 CuT 12 7 CuT 12 7 CuT 6 4 CuT 9 5 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 4 0 CuT 4 0 CuT 4 0 CuT 9 5 CuT 9 5 CuT 6 4 CuT 12 7 CuT b a c d m m m j3 n o l e j1 i i i j...

Page 25: ...9 5 CuT 9 5 CuT 9 5 CuT 9 5 CuT 9 5 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 12 7 CuT 12 7 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT j3 b a c d f h g j1 i i i 4 0 CuT 4 0 CuT 4 0...

Page 26: ......

Page 27: ......

Page 28: ...3P512025 9S 2020 05 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...