Field Settings for FDMQ, FFQ Series
SiUS092230EA
214
Part 7 Trial Operation and Field Settings
Note
5. Field Settings for FDMQ, FFQ Series
5.1 How to Change the Field Settings
Outline
If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be
changed. Refer to the instruction manual for each optional accessory.
When using 2 remote controllers for 1 indoor unit, change the field settings from MAIN remote
controller. Note that the field settings cannot be set from SUB remote controller.
Procedure
BRC1E73 Wired Remote Controller
a
Unit No.
b
First code No.
c
Second code No.
d
Mode
a
b
c
d
(R18831)
1. Press and hold
Cancel
button for 4 seconds or longer.
Service settings menu is displayed.
2. Select
in the Service Settings menu, and press
Menu/OK
button.
Field settings screen is displayed.
<Basic screen>
1
Fan
Press and hold
Cancel
button for 4 seconds or
longer during backlight lit.
Field Settings
<Service settings menu screen>
2
Service Settings
1/3
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Function
Min Setpoints Differential
Setting
Press
Menu/OK
button.
Summary of Contents for RX-W Series
Page 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Page 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Page 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...