Troubleshooting by Indication on the Remote Controller
SiUS30-1301
202
Service Diagnosis
3.30 Momentary Overcurrent of Inverter Compressor
Error Code
L5
Applicable
Models
RWEYQ72P, 84P
Method of Error
Detection
Error is detected from current flowing in the power transistor.
Error Decision
Conditions
When an excessive current flows in the power transistor
(Instantaneous overcurrent also causes activation.)
Supposed
Causes
Defective compressor coil (disconnected, defective insulation)
Compressor startup error (mechanical lock)
Defective inverter PCB