2-5 Technical specifications 

(1)

(1) Refer to the engineering data book for the complete list of specifications.
(2) The normal cooling capacities are based on:

–indoor temperature:

80 °FDB  /  67 °FWB,

–inlet water temperature:

85 °F,

–outlet water temperature:

95 °F,

–equivalent pipe length:

25 ft,

–level difference:

0 ft

(3) The normal heating capacities are based on:

–indoor temperature:

70°FDB  /  60 °FWB,

–inlet water temperature:

70 °F,

–equivalent pipe length:

25 ft,

–level difference:

0 ft

(4) The nominal input includes total input of the unit: compressor and control circuit.
(5) In case of heat recovery system

2-6 Electrical specifications

General

RWEYQ72PTJU

RWEYQ84PTJU

Nominal cooling capacity (2) (MBh)

72

84

Nominal cooling capacity (3) (MBh)

81

94.5

Nominal input cooling / heating (4)

(kW)

4.20 / 4.00

5.60 / 5.40

Dimensions HxWxD

(inch)

39-3/8×30-3/4×21-11/16

Weight

(lbs)

330

330

Connections

refrigerant liquid pipe

(inch)

3/8

3/8

refrigerant gas pipe

(inch)

3/4

7/8

refrigerant discharge gas pipe (5) (inch)

5/8

3/4

Water piping connections

Inlet pipe

(inch)

1-1/4FPT

female Thread

1-1/4FPT

female Thread

Outlet pipe

(inch)

1-1/4FPT

female Thread

1-1/4FPT

female Thread

Drain pipe

(inch)

1/2FPS

female Thread

1/2FPS

female Thread

General

RWEYQ144PTJU

RWEYQ168PTJU

Nominal cooling capacity (2) (MBh)

144

168

Nominal cooling capacity (3) (MBh)

162

189

Nominal input cooling / heating (4)

(kW)

8.40 / 8.00

11.20 / 10.80

Dimensions HxWxD

(inch)

(39-3/8×30-3/4×21-11/16)×2

Weight

(lbs)

330×2

330×2

Connections

refrigerant liquid pipe

(inch)

1/2

5/8

refrigerant gas pipe

(inch)

1-1/8

1-1/8

refrigerant discharge gas pipe (5) (inch)

7/8

7/8

Water piping connections

Inlet pipe

(inch)

(1-1/4FPT)×2

female Thread

(1-1/4FPT)×2

female Thread

Outlet pipe

(inch)

(1-1/4FPT)×2

female Thread

(1-1/4FPT)×2

female Thread

Drain pipe

(inch)

(1/2FPS)×2

female Thread

(1/2FPS)×2

female Thread

General

RWEYQ216PTJU

RWEYQ252PTJU

Nominal cooling capacity (2) (MBh)

216

252

Nominal cooling capacity (3) (MBh)

243

283.5

Nominal input cooling / heating (4)

(kW)

12.60 / 12.00

16.80 / 16.20

Dimensions HxWxD

(inch)

(39-3/8×30-3/4×21-11/16)×3

Weight

(lbs)

330×3

330×3

Connections

refrigerant liquid pipe

(inch)

5/8

3/4

refrigerant gas pipe

(inch)

1-1/8

1-1/4

refrigerant discharge gas pipe (5) (inch)

1

1-1/8

Water piping connections

Inlet pipe

(inch)

(1-1/4FPT)×3

female Thread

(1-1/4FPT)×3

female Thread

Outlet pipe

(inch)

(1-1/4FPT)×3

female Thread

(1-1/4FPT)×3

female Thread

Drain pipe

(inch)

(1/2FPS)×3

female Thread

(1/2FPS)×3

female Thread

Compressor

RWEYQ72PTJU

RWEYQ84PTJU

Oil type

Synthetic (ether) oil

Synthetic (ether) oil

Crankcase heater

(W)

33

33

Refrigerant type

R410A

R410A

Refrigerant charge

(lbs)

9.9

11.5

Compressor

RWEYQ144PTJU

RWEYQ168PTJU

Oil type

Synthetic (ether) oil

Synthetic (ether) oil

Crankcase heater

(W)

(33)×2

(33)×2

Refrigerant type

R410A

R410A

Refrigerant charge

(lbs)

(9.9)×2

(11.5)×2

Compressor

RWEYQ216PTJU

RWEYQ252PTJU

Oil type

Synthetic (ether) oil

Synthetic (ether) oil

Crankcase heater

(W)

(33)×3

(33)×3

Refrigerant type

R410A

R410A

Refrigerant charge

(lbs)

(9.9)×3

(11.5)×3

Model

RWEYQ72PTJU

RWEYQ84PTJU

Power supply

Phase

3~

3~

Frequency

(Hz)

60

60

Voltage

(V)

208-230

208-230

Voltage tolerance

(%)

±10

±10

Recommended fuses

(A)

40

40

Compressor

Phase

3~

3~

Frequency

(Hz)

60

60

Voltage

(V)

208-230

208-230

Nominal running current

(A)

11.6

15.4

Model

RWEYQ144PTJU

RWEYQ168PTJU

Power supply

Phase

3~

3~

Frequency

(Hz)

60

60

Voltage

(V)

208-230

208-230

Voltage tolerance

(%)

±10

±10

Recommended fuses

(A)

(40)×2

(40)×2

Compressor

Phase

3~

3~

Frequency

(Hz)

60

60

Voltage

(V)

208-230

208-230

Nominal running current

(A)

(11.6)×2

(15.4)×2

Model

RWEYQ216PTJU

RWEYQ252PTJU

Power supply

Phase

3~

3~

Frequency

(Hz)

60

60

Voltage

(V)

208-230

208-230

Voltage tolerance

(%)

±10

±10

Recommended fuses

(A)

(40)×3

(40)×3

Compressor

Phase

3~

3~

Frequency

(Hz)

60

60

Voltage

(V)

208-230

208-230

Nominal running current

(A)

(11.6)×3

(15.4)×3

Summary of Contents for RWEYQ72PTJU

Page 1: ...for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de main pour r f rence ult rieure Ce manuel...

Page 2: ...6 13 16 3 15 16 9 13 16 21 5 8 30 11 16 9 9 8 10 8 9 7 7 6 6 6 9 7 8 5 8 15 3 8 4 3 1 2 11 13 16 39 3 8 35 7 16 19 11 16 1 2 3 4 4 10 5 6 5 4 9 6 7 7 10 8 1 2 3 4 9 Heat recovery system Heat pump syst...

Page 3: ...figure 13 figure 12 figure 11 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 6 1 2 7 C H SELECTOR TO IN D UNIT TO OUT D UNIT TO MULTI UNIT 3 A B C F1 F1 F2 F2...

Page 4: ...very system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 16 A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N TO IN D UNIT F1 F2 A1P A1P DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 1 2 6 3 3 4 5...

Page 5: ...4 5 6 Heat pump system Heat recovery system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3...

Page 6: ...sult in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive leak can lead to oxygen depletion especially in base ments and an asphyxiat...

Page 7: ...on tribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrig erant piping installation Read the chapter Refrigerant Pip ing and follow...

Page 8: ...itches off automatically in order to protect the unit from freezing Hold ambient temperature at 35 95 F Heat release from the unit 0 64 kW hour Model 72 84 It is therefore recommended to always ventil...

Page 9: ...emale Thread 1 2FPS 2 female Thread General RWEYQ216PTJU RWEYQ252PTJU Nominal cooling capacity 2 MBh 216 252 Nominal cooling capacity 3 MBh 243 283 5 Nominal input cooling heating 4 kW 12 60 12 00 16...

Page 10: ...ower without fail Open type tower cannot be used 4 Strainer Install the strainer accessory without fail at the inlet of water pip ing If sands wastes rust particles etc are mixed in the water cir cula...

Page 11: ...manner 7 1 When designing the equipment 1 Install the strainer accessory at the water inlet side adjacent to the outside unit in order to prevent any foreign materials such as dust sand etc from ente...

Page 12: ...within the standard 2 Clean the strainer 3 Make sure that the flow rate is correct 4 Make sure that the operational conditions pressure flow rate outlet temperature etc are normal 2 Because the plate...

Page 13: ...fect but also may cause the capacitor to overheat due to high frequency waves Therefore never install a phase advancing capacitor Keep power imbalance within 2 of the supply rating 1 Large imbalance w...

Page 14: ...electromagnetic switch for the water pump to each outside unit Select without fail an auxiliary a contact able to switch min imum load of DC15V 1mA When connecting for each outside unit Connect to the...

Page 15: ...erminals for connections to the power terminal block When none is available follow the instructions below Do not connect wiring of different thicknesses to the power termi nal block Slack in the power...

Page 16: ...s always required When installing the piping follow the instructions in the installation manual that comes with the kit Restriction for the installation of the outside unit multi connection piping kit...

Page 17: ...cal piping with the provided insulation to prevent it from coming into contact with the casing Precautions for installation of units NOTE The outside unit multi connection piping kit that is sold sepa...

Page 18: ...c d e f r s t g h j k l m n o p i 23 3 lbs Total length ft of liquid piping size at 7 8 0 235 lbs ft Total length ft of liquid piping size at 3 8 Total length ft of liquid piping size at 1 4 Total len...

Page 19: ...etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be sure to...

Page 20: ...refrigerant 9 10 Stop valve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without...

Page 21: ...onfiguration on the main unit Any settings made on a sub unit will be ignored After this close the electrical compo nents box lid Always perform configuration after turning ON the power To learn the s...

Page 22: ...rding to local regulations or standards The following standards may be applicable if local regulations are not available The VRV System like other air conditioning systems uses R410A as refrigerant R4...

Page 23: ...e open ings above and below the door which are each equivalent in size to 0 15 or more of the floor area 3 Calculating the refrigerant density using the results of the calcula tions in steps 1 and 2 a...

Page 24: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P153897 12P EM09A022 0910 FS...

Reviews: