EDUS30-900-N
Installation
Installation of Outdoor Units
49
13. Field Setting
h
: OFF
k
: ON
l
: Blinking
*2 "Demand 2" setting is even more "power-saving" operation than "Demand 1" setting.
*3 There are 7 stages in "error indication - ON" setting where you can set the amount of interval time until each error indication.
* See the Service Manual for setting other than the above.
No.
Details of setting
LED display
Setting condition display
H1P H2P H3P H4P H5P H6P H7P
Setting condition
LED display
* Factory setting
A
Additional refrigerant charging operation
setting
k
h
k
h
k
h
h
ON
OFF
khhhhlh
khhhhhl
*
B
Refrigerant recovery operation / Evacuation
mode setting
k
h
k
h
k
h
k
ON
OFF
khhhhlh
khhhhhl
*
C
Auto demand control setting (*2)
k
k
h
h
h
h
h
OFF
Demand setting 1
Demand setting 1
khhhhhl
*
khhhhlh
khhhlhh
D
Demand 1 level setting
k
h
k
k
k
k
h
Level 1: 60% level
Level 2: 70% level
Level 3: 80% level
khhhhhl
khhhhlh
*
khhhlhh
E
External control adaptor setting (*1)
k
h
h
k
k
h
h
ON
OFF
khhhhlh
khhhhhl
*
F
Remote controller display malfunction code,
when interlock open setting (*3)
k
h
k
k
h
k
h
OFF
5 min.
10 min.
15 min.
20 min.
25 min.
30 min.
35 min.
khhhhhh
*
khhhhhl
khhhhlh
khhhhll
khhhlhh
khhhlhl
khhhllh
khhhlll
G
Pump control
k
h
k
k
h
k
k
ON
OFF
khhhhlh
khhhhhl
*
Push the SET button (BS2) and adjust the LED
indication to the example shown below
according to the required mode (
A
to
G
).
Push the SET button (BS2) and adjust the LED
indication to the example shown below
according to the required setting.
Push the RETURN button (BS3) for defining the
setting.
Push the RETURN button (BS3), (The current
setting will be indicated.)
When the RETURN button (BS3) is pushed
again, the system starts the operation according
to the setting.
<Selection of setting item>
<Selection of setting
condition>
Settng of the following items can be carried out.
<Setting Procedures>
Summary of Contents for RWEYQ72
Page 1: ...EDUS 30 900 N AMERICAS AMERICAS Installation...
Page 17: ...REFNET Pipe System EDUS30 900 N 16 Installation of Outdoor Units 3P161697D...
Page 21: ...REFNET Pipe System EDUS30 900 N 20 Installation of Outdoor Units C 3P113151C 7 8 1 1 1 8...
Page 23: ...REFNET Pipe System EDUS30 900 N 22 Installation of Outdoor Units C 3P113623C 7 8 1 1 1 8...
Page 25: ...REFNET Pipe System EDUS30 900 N 24 Installation of Outdoor Units 3P185500...
Page 27: ...REFNET Pipe System EDUS30 900 N 26 Installation of Outdoor Units 1P185542...