background image

English

4

3.

SELECTION OF LOCATION

Select a location for installation that meets the following conditions 
and get the customer’s permission.

(1)

There is no danger of fire due to leakage of inflammable gas.

(2)

Select the location of the unit in such a way that neither the dis-
charged air nor the sound generated by the unit disturb anyone.

(3)

The foundation is strong enough to support the weight of the unit 
and the floor is flat to prevent vibration and noise generation.

(4)

The piping length between the outdoor unit and the indoor unit 
may not exceed the allowable piping length.
(Refer to

  

6. REFRIGERANT PIPING

”)

(5)

Locations where the unit’s suction vent and outlet vent do not 
generally face the wind.
Wind blowing directly into the suction or outlet vents will interfere 
with the unit’s operation.
If necessary, install some kind of obstruction to block the wind.

(6)

The space around the unit is adequate for servicing and the min-
imum space for air inlet and air outlet is available.
(See the “

Installation Space Examples

” for the minimum space 

requirements.)

Installation Space Examples

The installation space requirement shown in figure 2 is a refer-
ence for cooling operation when the outdoor temperature is 35°C. 
If the design outdoor temperature exceeds 35°C or the heat load 
exceeds maximum capacity in all the outdoor unit, take an even 
large space on the intake shown in figure 2.

During installation, install the units using the most appropriate of 
the patterns shown in figure 2 for the location in question, taking 
into consideration human traffic and wind.
If the number of units installed is more than that shown in the pat-
tern in figure 2, install the units so there are no short circuits.

As regards space in front of the unit, consider the space needed 
for the local refrigerant piping when installing the units.

If a snowbreak hood (sold separately) is mounted, secure the 
required space of installation including the outer dimensions of 
the product and snowbreak hood.

If the work conditions in figure 2 do not apply, contact your dealer 
or Daikin directly.

(Refer to figure 2)

1.

In case of single outdoor unit system

2.

In case of multi outdoor unit system

3.

Pattern 1

4.

Pattern 2

5.

Pattern 3

6.

Front side

7.

No limit to wall height

8.

Service space of front side

9.

Service space of suction side

For Patterns 1 and 2 in figure 2 :

Wall height for front side – no higher than 1500 mm.

Wall height on the suction side – no higher than 500 mm.

Wall height for sides – no limit.

If the height is exceeded the above, calculate h1 and h2 shown in 
the figure below, and add h2/2 to the service space of front side 
and h1/2 to the service space of suction side.

Note

(1)

An inverter air conditioner may cause electronic noise gener-
ated from AM broadcasting. Examine where to install the 
main air conditioner and electric wires, keeping proper dis-
tances away from stereo equipment, personal computers, etc.
Particularly for locations with weak reception, ensure there is 
a distance of at least 3 meters for indoor remote controllers, 
place power wiring and transmission wiring in conduits, and 
ground the conduits.

 (Refer to figure 3)

1.

Indoor unit

2.

Branch switch, overcurrent breaker

3.

Remote controller

4.

Personal computer or radio

5.

Air outlet

6.

Rear side suction grille

(2)

When installing in a locations where there is heavy snowfall, 
implement the following snow measures.

Install the outdoor unit and function unit on a mount (pro-
cured locally) so that they may not be buried or covered 
with snowfall while the bottom frame will be 200 to 300 mm 
higher than the surface of the deposited snow.

Mount the snowbreak hood (sold separately) and dismount 
the rear suction grille (see fig. 3).

(3)

When mounting the snowbreak hood (sold separately) to 
the air inlet, make sure that the air outlet of the snow protec-
tion food will be located right angles to the winter wind or in 
the leeward direction.

(4)

If the outdoor temperature of the place of installation is low 
in winter and defrost water discharged from the system 
freezes while the system is in defrost operation in heating 
mode, provide a sufficient space between the bottom frame 
of the outdoor unit and the foundation side. (A space of 500 
to 1000 mm is recommended.)

(5)

If condensate may drip on downstairs (or walkway) depend-
ing on the floor condition, take a measure such as the instal-
lation of drain pan (field supply).

(6)

The refrigerant R410A itself is nontoxic, nonflammable and is 
safe. If the refrigerant should leak however, its concentration 
may exceed the allowable limit depending on room size. Due to 
this it could be necessary to take measures against leakage. 
See “

12. CAUTION FOR REFRIGERANT LEAKS

” for details.

4.

INSPECTING AND HANDLING THE UNIT

At delivery, the package should be checked and any damage 
should be reported immediately to the carrier claims agent.

When handling the unit, take into account the following:

(1)

Fragile, handle the unit with care.

Keep the unit upright in order to avoid compressor damage.

(2)

Decide on the transportation route.

(3)

If hanging the unit, keep the following points in mind and hang the 
unit following the procedure shown in figure 4.

Use a sling sufficiently strong to hold the mass of the unit.

Use 2 sling of at least 8m long.

Place extra cloth or boards in the locations where the casing 
comes in contact with the sling to prevent damage. 

Hoist the unit making sure it is being lifted at its center of gravity.

In the case of transporting the outdoor unit by forklift, insert the 
fork into the opening (large) under the bottom of the outdoor unit. 

(Refer to figure 5)

The function unit is not provided with any opening for fork inser-
tion.

Note

Apply a filler cloth on a fork to prevent coating of the bottom frame 
from coming off and rust from occurring when bringing the unit 
using a forklift.

(4)

After the outdoor unit is installed, remove the transportation 
bracket (yellow) by pushing the hook mounted to the opening 
(large) of the outdoor unit. 

(Refer to figure 5)

(Refer to figure 4)

1.

Slinging procedure for outdoor unit

2.

Slinging procedure for function unit

3.

Sling

4.

Patch plate or path cloth

5.

Opening (large)

6.

Opening (small)

h2

1500

<Front side>

<Suction side>

500

h2

2

or more

Service

space

h1

2

or more

h1

500

+

+

01_EN_3P201178-10P.fm  Page 4  Wednesday, September 2, 2009  11:10 AM

Summary of Contents for RTSYQ10PY1

Page 1: ...nglish Norsk Svenska Deutsch Fran ais Polski Installation manual VRVIII C System air conditioner Installationsanleitung VRVIII C System Klimaanlage Manuel d installation Conditionneur d air VRVIII C S...

Page 2: ...PY1 RTSYQ16PY1 RTSYQ20PY1 RTSQ8PY1 RTSQ10PY1 RTSQ12PY1 RTSQ14PY1 RTSQ16PY1 BTSQ20PY1 REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1 REYQ20PY1 REYQ22PY1 REYQ24PY1 REYQ26PY1 REYQ28PY1 REYQ30...

Page 3: ...0 300 500 10 50 100 10 100 300 300 500 50 200 200 400 200 200 50 100 10 100 500 50 50 100 50 100 1 3 6 6 6 2 7 6 6 6 9 8 9 8 9 8 9 8 3 4 5 4 5 2 unit mm 1 2 5 4 3 figure 7 727 765 300 460 1 1 2 8 8 5...

Page 4: ...re 11 6 3 4 5 2 8 7 9 10 1 2 4 3 2 1 figure 12 1 3 5 11 11 11 11 9 12 12 13 13 7 10 9 10 4 7 3 6 11 11 11 11 11 11 9 9 8 8 10 10 2 figure 15 figure 21 9 7 8 10 2 3 12 13 7 15 17 18 15 16 14 1 11 4 5 6...

Page 5: ...10 9 1 8 5 7 9 6 4 3 2 figure 26 1 3 2 2 1 3 4 5 6 7 1 10 8 9 figure 30 figure 31 2 3 13 7 8 9 10 12 11 16 6 5 4 14 15 1 17 18 19 20 figure 34 figure 29 figure 23 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1...

Page 6: ...leakage electric shocks or fire Install the air conditioner in accordance with the instructions in this installation manual Improper installation may result in water leakage electric shocks or fire Wh...

Page 7: ...quired additional refrig erant must be charged in its liquid state If the system is charged with refrigerant in its gaseous state due to composition change the system will not function normally Limit...

Page 8: ...both units Do not throw away any of the accessories until installation is com plete They are needed for installation work Request the user to keep the explanation documents after the installation work...

Page 9: ...power wiring and transmission wiring in conduits and ground the conduits Refer to figure 3 1 Indoor unit 2 Branch switch overcurrent breaker 3 Remote controller 4 Personal computer or radio 5 Air outl...

Page 10: ...intless phosphor deoxidized copper pipe Size See 6 5 Example of connection to determine the cor rect size Thickness Select a thickness for the refrigerant piping which complies with national and local...

Page 11: ...tract the gas in the pinch piping 4 Step 2 After the gas is extracted melt the blazing mate rial with a burner and remove the pinch pipes 3 Connecting refrigerant piping to outdoor units and function...

Page 12: ...int horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 17 1 Do not install vertically Refer to figure 17 2 Maintain a straight portion of 500 mm...

Page 13: ...Horizontal surface 2 B arrow view Oil remains in the stopping outdoor unit Rising height 200 mm or more 1 Connect straightly 2 Put rising Prohibited pattern Front connection Bottom connection To indoo...

Page 14: ...nd outdoor units Between outdoor unit and function unit Actual pipe length Equivalent length Actual and Equivalent pipe length Difference in height Difference in height Difference in height Difference...

Page 15: ...s the requirements of Japanease High Pressure Gas Controll low As of Jan 2003 The thickness and material shall be selected in accordance with local code In case of single outdoor unit system In case o...

Page 16: ...at 19 1 Total length m of liquid piping size at 12 7 Total length m of liquid piping size at 6 4 0 37 0 18 0 059 0 26 0 12 0 022 FOR THE SYSTEM SYSTEM NAME THE AMOUNT OF REFRIGERANT Example for refri...

Page 17: ...and an malfunction code will be displayed on the indoor remote controller Never remove thermistor sensor or etc when connecting power wiring and transmission wiring If operated with thermistor sensor...

Page 18: ...board Attach with care See the table below for the tightening torque of the transmission wiring terminals All transmission wiring should use sheathed vinyl cord 0 75 1 25 mm2 or cable duplex Transmiss...

Page 19: ...ing in the power wiring and ground wir ing from the left hand side 6 In the case of pulling in the power wiring and ground wir ing from the right hand side 7 Pull in the transmission wiring from the p...

Page 20: ...rogen gas then depressurize down to 100 7 kPa for an hour using the vacuum pump vacuum drying 2 If the pressure does not reach 100 7 kPa even after depressur izing for at least two hours repeat the va...

Page 21: ...the refrigerant charging operation close the valve of the refrigerant tank immediately The refrigerant charge port of this product have electric expan sion valve The valve will be closed at end of ref...

Page 22: ...cts the main body seal 3 Make sure to tighten the cap securely For the tightening torque refer to the item Tightening Torque 8HP type 10HP type 12HP type 14HP type 16HP type Liquid pipe shutoff valve...

Page 23: ...refrigerant amount in the field and total refrig erant amount of the system to Refrigerant charge label and adhere in the proximity of the refrigerant charge port About Refrigerant charge label refer...

Page 24: ...the remote control ler display shows P9 code After checking push the MODE button BS1 once and the charg ing is complete In case of heating mode 7 Push the TEST button BS4 once within 5 minutes after...

Page 25: ...ve A PA PH The refrigerant tank is empty Close the valve A and replace empty tank to the new tank After changing the tank open the valve A again Beware the fan running The outdoor unit does not stop o...

Page 26: ...tandards may be applicable if local regulations are not available The VRV System like other air conditioning systems uses R410A as refrigerant R410A itself is an entirely safe non toxic non combusti b...

Page 27: ...ntration 4 Dealing with the situations where the result exceeds the maxi mum concentration level Where the installation of a facility results in a concentration in excess of the maximum concentration...

Page 28: ...3P201178 10P EM07A033B 0908 HT 00_CV_3P201178 10P fm Page 5 Wednesday September 2 2009 11 09 AM...

Reviews: