background image

 

Installation manual

5

R(Y)(P)71~125B7

Split System air conditioners

4PW10931-1B

In case of simultaneous operation system

Upward and downward piping should be performed at the main
piping line.

Use branch piping kit (optional) for branching refrigerant pipes.

Precautions to be taken. (For details, refer to the manual attached to
branch piping kit.)

-

Install the branch pipes horizontally. (Maximum inclination: 
20° or less)

-

Length of branch pipe to the indoor unit should be as short as 
possible.

-

Try to keep lengths of both branch pipes to the indoor unit 
equal.

E

VACUATING

The units were checked for leaks by the manufacturer.

The refrigerant lines fitted in site are to be checked for leaks by the
fitter.

Confirm that the valves are firmly closed before pressure test or
vacuuming.

Air tight test and vacuum drying (take special care for R407C units):
see 

figure 7

Air tight test: make sure to use nitrogen gas. Pressurize the
liquid and gas pipes to 3.3 MPa (do not pressurize more than
3.3 MPa). If the pressure drops, check where the nitrogen
comes from.

Vacuum drying: use a vacuum pump which can evacuate to
-100.7 kPa (5 Torr, -755 mmHg).
-

Evacuate the system from the liquid and gas pipes by using a 
vacuum pump for more than 2 hours and bring the system to 
-100.7 kPa. After keeping the system under that condition for 
more than one hour, check if the vacuum gauge rises or not. 
If it rises, the system may either contain moisture inside or 
have leaks.

-

Following should be executed if there is a possibility of 
moisture remaining in the pipe (if piping work is carried out 
during the raining season or over a long period of time, 
rainwater may enter the pipe during work).

-

After evacuating the system for 2 hours, pressurize the 
system to 0.05 MPa (vacuum break) with nitrogen gas and 
evacuate the system again using the vacuum pump for 
1 hour to -100.7 kPa (vacuum drying). If the system cannot 
be evacuated to -100.7 kPa within 2 hours, repeat the 
operation of vacuum break and vacuum drying. Then after 
leaving the system in vacuum for 1 hour, confirm that the 
vacuum gauge does not rise.

Leak test

1

Evacuate the pipes and check vacuum. (No pressure increase
for 1 minute.)

2

Break the vacuum with a minimum of 2 bar of nitrogen.

3

Conduct leak test by applying soap water, etc. to the connecting
part of the pipes.

4

Discharge nitrogen.

5

Evacuate and check vacuum again.

6

Open the stop valve and inject the refrigerant into the refrigerant
pipe and into the indoor unit.

7

Leak test must satisfy EN 378-2.

C

HARGING

 

REFRIGERANT

This unit requires additional charging of refrigerant according to the
length of pipe connected at the site. Concerning R407C refrigerant:
charge the refrigerant to the liquid pipe in its liquid state. Since
R407C is a mixed refrigerant, its composition changes if charged in a
state of gas and normal system operation would no longer be
assured.

Concerning L1~L4 (see following tables), refer to 

figure 2

~

figure 4

.

Additional charging of refrigerant

Find the correct amount of additional refrigerant to charge 'G' (kg)
using one of the following formulas.

Pair system: see 

figure 2

L1 (m) .................... one way length of liquid pipe

Simultaneous operation system 
(Twin: see 

figure 3

, Triple: see 

figure 4

)

L1 (m) .................... one way length of main liquid pipe

L2~L4 (m) .............. one way length of branched liquid pipes

R407C:

Do not purge the air with refrigerants. Use a vacuum pump
to vacuum the installation. No additional refrigerant is
provided for air purging.

A

Pair system

B

Simultaneous operation system

1

Pressure gauge

2

Nitrogen

3

Refrigerant

4

Weighing machine

5

Vacuum pump

6

Stop valve

7

Main pipe

8

Branched pipes

9

Pipe branching kit (optional)

R407C

R22

R(P)71~125

G = (L1-30) x 0.025

G= (L1-7.5) x 0.03

RY(P)71

G = (L1-30) x 0.045

G= (L1-7.5) x 0.05

RY(P)100,125

G = (L1-30) x 0.07

R(Y)P71-
100-125

L1 

 30 m

G = (L1-30 m) x A + L2 
x A +L3 x A + L4 x A

L1< 30 m

G = (L1+ L2 - 30 m) x A 
(L2) + L3 x A + L4 x A

&  L1 + L2 

 30 m

L1 + L2 < 30 m

G = (L1+ L2 + L3 - 30 m) 
x A (L3) +  L4 x A

&  L1 + L2  + L3  

  30 m

L1 + L2  + L3  <  30 m

G = (L1+ L2 + L3 + L4 - 
30 m) x A (L4)

& L1 + L2 + L3 + L4  

  30 m

Branched pipe

A

R(Y)P71

Ø 9.5

0.045 kg/m

Ø 6.4

0.03 kg/m

R(Y)P100

Ø 9.5

0.07 kg/m

Ø 6.4

0.03 kg/m

R(Y)P125

Ø 9.5

0.025 kg/m

Summary of Contents for RP100B7T1

Page 1: ...oners English R71B7V1 R71B7W1 R100B7V1 R100B7W1 R125B7W1 RP71B7V1 RP71B7W1 RP71B7T1 RP100B7V1 RP100B7W1 RP100B7T1 RP125B7W1 RP125B7T1 RY71B7V1 RY71B7W1 RY100B7V1 RY100B7W1 RY125B7W1 RYP71B7V1 RYP71B7W...

Page 2: ...timuksia edellytt en ett niit k ytet n ohjeidemme mukaisesti following the provisions of Directives as amended gem den Vorschriften der Direktiven gem nderung conform ment aux stipulations des Directi...

Page 3: ...1250 500 1000 1000 1000 1000 150 150 50 100 150 500 500 500 50 100 150 250 L1 H H L1 L H L H 500 L1 L2 L1 L2 L2 L1 L1 L2 L2 L1 500 750 1000 0 L1 1 2H 1 2H L1 1000 50 100 100 200 L2 H H L2 L2 L1 500 50...

Page 4: ...onal when used as the outdoor unit for the simultaneous operation system Refer to catalogues for details Never operate the unit without the thermistor R3T burning of the compressor may result Be sure...

Page 5: ...locks etc the height of the foundation should be maximum 150 mm 5 If you install the unit on a frame please install a waterproof plate within 150 mm of the underside of the unit in order to prevent th...

Page 6: ...ion system twin see figure 3 triple see figure 4 The pipes between the outdoor unit and the branch L1 should have the same size as the outdoor connections The pipes between the branch and the indoor u...

Page 7: ...nitially tighten by hand before tightening firmly Make sure to flow nitrogen gas through the pipe when brazing Take measures against contamination when installing pipes Prevent foreign materials like...

Page 8: ...of vacuum break and vacuum drying Then after leaving the system in vacuum for 1 hour confirm that the vacuum gauge does not rise Leak test 1 Evacuate the pipes and check vacuum No pressure increase f...

Page 9: ...dedicated power circuit Do not share a common source with other equipment Fix cables so that cables do not make contact with the pipes especially on high pressure side For W1 and T1 models Make sure...

Page 10: ...T1 MODEL PHASE REVERSE CIRCUIT Q1L Q2L THERMO SWITCH M1F M2F Q3E EARTH LEAK DETECTOR R1T THERMISTOR AIR R2T THERMISTOR COIL R3T THERMISTOR DISCHARGE R4C R5C V1 MODEL RESISTOR RC SIGNAL RECEIVER CIRCUI...

Page 11: ...2 R407C 8 6 5 4 2 1 3 9 7 A B 3 3 1 2 4 5 5 1 5 4 A B 2 3 V1 1 50Hz 230V L N N L 3 2 1 3 2 1 P2 P1 3 2 1 P2 P1 3 2 1 P2 P1 W1 3N 50Hz 400V L3 N N L3 L2 L1 L1 L2 T1 3 50Hz 230V L2 L3 L3 L2 L1 L1 l ll l...

Page 12: ...DaikinZandvoordestraat 300 B 8400 Oostende Belgium 4PW10931 1B...

Reviews: