4 Installation

Installation manual

10

RRGA04~08DAV3

ROTEX HPSU Bi-Bloc Ultra

4P496756-1B – 2018.07

4.5.3

To fix the fluorinated greenhouse gases
label

1

Fill in the label as follows:

b

Contains fluorinated greenhouse gases

2

1

1

1

2

2

kg

tCO

2

eq

GWP × kg

1000

=
=

+

kg

=

kg

=

GWP: XXX

RXXX

a

f

c

d
e

a

If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of 

a

.

b

Factory refrigerant charge: see unit name plate

c

Additional refrigerant amount charged

d

Total refrigerant charge

e

Greenhouse gas emissions

 of the total refrigerant charge

expressed as tonnes CO

2

 equivalent

f

GWP = Global warming potential

NOTICE

In  Europe,  the 

greenhouse  gas  emissions

  of  the  total

refrigerant charge in the system (expressed as tonnes CO

2

equivalent) is used to determine the maintenance intervals.
Follow the applicable legislation.

Formula  to  calculate  the  greenhouse  gas  emissions:

GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000

2

Fix the label on the inside of the outdoor unit near the gas and
liquid stop valves.

4.6

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

4.6.1

About electrical compliance

Only for RRGA04~08DAV3

Equipment  complying  with  EN/IEC  61000‑3‑12  (European/
International  Technical  Standard  setting  the  limits  for  harmonic
currents  produced  by  equipment  connected  to  public  low-voltage
systems with input current >16 A and ≤75 A per phase.).

4.6.2

Specifications of standard wiring
components

Component

06DAV3

RRGA08DAV3

Power
supply
cable

MCA

(a)

19.9 A

24.0 A

Voltage

230 V

Phase

1~

Frequenc
y

50 Hz

Wire
sizes

Must comply with applicable legislation

Interconnection
cable

Minimum cable section of 1.5 mm² and

applicable for 230 V

Recommended field
fuse

20 A

25 A

Earth leakage circuit
breaker

Must comply with applicable legislation

(a)

MCA=Minimum circuit ampacity. Stated values are
maximum values (see electrical data of combination with
indoor units for exact values).

4.6.3

To connect the electrical wiring on the
outdoor unit

1

Remove the switch box cover.

2

Connect the interconnection cable and power supply as follows.
Ensure stress relief by using the wire clamp.

a

c

d

1N~ 50 Hz

220-240 V

b

a

Interconnection cable

b

Power supply cable

c

Fuse

d

Earth leakage circuit breaker

1 2 3

L

N

L N PWR

12 3

a

a

Wire clamp

3

Reattach the switch box cover.

4

Optional: Attach the wire clamp (accessory) to the screw of the
refrigerant piping cover, and fix the cables to it with a cable tie.

Summary of Contents for ROTEX HPSU Bi-Bloc Ultra

Page 1: ...Installation manual ROTEX HPSU Bi Bloc Ultra English Installation manual ROTEX HPSU Bi Bloc Ultra RRGA04DAV3 RRGA06DAV3 RRGA08DAV3...

Page 2: ...ektyw n urma prevederilor 19 20 21 22 23 24 25 ob upo tevanju dolo b vastavalt n uetele laikantis nuostat pateikiam iev rojot pras bas kas noteiktas odr iavaj c ustanovenia bunun ko ullar na uygun ola...

Page 3: ...S vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplot...

Page 4: ...To finish the outdoor unit installation 11 5 Starting up the outdoor unit 11 6 Technical data 11 6 1 Piping diagram Outdoor unit 11 6 2 Wiring diagram Outdoor unit 13 1 About the documentation 1 1 Abo...

Page 5: ...following spacing guidelines 1200 250 250 250 350 350 mm mm a b b a a Air outlet b Air inlet INFORMATION In sound sensitive areas e g near a bedroom you can install the low sound cover EKLN08A1 to de...

Page 6: ...ectrical wiring on the outdoor unit on page 10 4 2 Mounting the outdoor unit 4 2 1 To provide the installation structure This topic shows different installation structures For all use 4 sets of M8 or...

Page 7: ...ti vibration rubber field supply 4 2 2 To install the outdoor unit CAUTION Do NOT remove the protective cardboard before the unit is installed properly 1 Lift the outdoor unit as described in 2 1 1 To...

Page 8: ...al of the drain pan heater Non heated drain tube When using the drain pan heater without drain tube or with a non heated drain tube remove the drain hole insulation Item c on the illustration INFORMAT...

Page 9: ...essure Then Does not change There is no moisture in the system This procedure is finished Increases There is moisture in the system Go to the next step 3 Vacuum the system for at least 2 hours to a ma...

Page 10: ...e multicore cable for power supply cables 4 6 1 About electrical compliance Only for RRGA04 08DAV3 Equipment complying with EN IEC 61000 3 12 European International Technical Standard setting the limi...

Page 11: ...ice cover 5 Starting up the outdoor unit See the indoor unit installation manual for configuration and commissioning of the system 6 Technical data 6 1 Piping diagram Outdoor unit R2T 7 0 CuT 7 0 CuT...

Page 12: ...Bi Bloc Ultra 4P496756 1B 2018 07 M1F Fan R1T Thermistor outdoor air R2T Thermistor heat exchanger R3T Thermistor compressor discharge S1PH High pressure switch automatic reset Y1E Electronic expansio...

Page 13: ...YLW yellow 3 Legend AL Connector C Capacitor DB Rectifier bridge DC Connector DP Connector E Connector F1U Fuse T 6 3 A 250 V FU1 FU2 Fuse T 3 15 A 250 V FU3 Fuse T 30 A 250 V H Connector IPM Intelli...

Page 14: ......

Page 15: ......

Page 16: ...usland Our partners abroad Unsere Partner im Ausland Nos partenaires l tranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granic Na i partne i v zahrani http...

Reviews: