9
x
Service and maintenance
FA ROTEX A1 BOe - 02/2014
43
Dismounting and regenerating the condensate box
1. Open the fixing belt (fig. 9-4, pos. 3).
2. Lift the stabilising plate (fig. 9-5, pos. 2) and pull out the
connecting muff (fig. 9-5, pos. 1) from the condensate drain.
3. Lift the condensate box and empty it through the connection
hose (fig. 9-6).
4. Place collector container under the hose connection. Remove
the flexible connector hose from the condensate box
(fig. 9-7).
5. Pull the condensate box forwards under the boiler.
DANGER OF CHEMICAL BURNS!
The condensate box contains acidic condensate that
can lead to injury upon contact with the skin or eyes.
Ɣ
Wear protective clothing (safety glasses, rubber
gloves) when working on the condensate box.
Ɣ
If your skin comes in contact with anything, wash
the affected area immediately with tap water.
Ɣ
If the chemicals come in contact with eyes,
immediately wash with tap water and consult an
ophthalmologist.
1
Condensate box
2
Condensate plug connector on flue gas elbow
3
Fixing belt with snap closing
4
Flexible connecting hose
Fig. 9-4
Connections to the condensate box
1
Connector sleeve for condensate connector
2
Stabilising plate
Fig. 9-5
Condensate box (plug connector)
Fig. 9-6
Emptying the condensate box
Fig. 9-7
Pull out connecting flexible hose