Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Comfort heat-
ing
If the heat pump cannot cover the heating demand when outside temperat-
ures are very low, heat is extracted from the storage tank and used for
room heating (see
N
E
Off
Only if the heating demand is not covered is the storage tank temperature
raised. During the time it takes to raise the temperature, there may be a
slight loss of comfort.
On
At corresponding outside temperatures, the storage tank temperature is al-
ways raised above the storage tank temperature set for the hot water re-
quirement. The power consumption of the heat pump may increase.
Tab. 7-15
Parameter in the "Heating" menu
7.6.4
Menu: Cooling
[→ Main menu → Configuration → Cooling]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Target flow
cooling, start
5 – 25 °C
Only if [Weather-compensated] parameter = Weather-compensated:
Setting of the cooling feed target temperature at the start of cooling mode
(outside temperature = [Start cooling outside temp.] parameter)
18 °C
1 °C
E
E
Target flow
cooling, max.
5 – 25 °C
Only if [Weather-compensated] parameter = Weather-compensated:
Setting of the minimum cooling feed target temperature. This is held con-
stant as of the outside temperature ([Max. cooling outside temp.] para-
meter).
8 °C
1 °C
E
E
Start cooling
outside temp.
15 – 45 °C
Only if [Weather-compensated] parameter = Weather-compensated:
Setting as of which outside temperature cooling mode starts with the
highest cooling feed target temperature [Target flow cooling, start] (setting
condition: "Cooling" operating mode).
24 °C
1 °C
E
E
Max. cooling
outside temp.
20 – 45 °C
Only if [Weather-compensated] parameter = Weather-compensated:
Setting of the outside temperature at which the lowest cooling feed target
temperature [Target flow cooling, max.] is specified (setting condition:
"Cooling" operating mode).
35 °C
1 °C
E
E
Feed temper-
ature lower
limit
5 – 25 °C
Setting of the absolute lower limit of the cooling feed target temperature.
Limitation acts if a lower cooling feed target temperature is determined
from other parameter settings.
If optional frost protection valves are installed in the system, the [Feed tem-
perature lower limit] parameter must not be set below 7 °C.
18 °C
1 °C
N
E
Feed temper-
ature, cooling
mode
8 – 30 °C
Only if [Weather-compensated] parameter = Feed temperature, fixed:
Setting of the cooling feed target temperature (fixed value) for active cool-
ing mode.
18 °C
1 °C
E
E
Cooling set-
point correc-
tion
-5.0 – +5.0 K
Parallel shift of the cooling characteristic curve by the set value.
0.0 K
1 K
N
E
Interlink tem-
perature re-
duction
1 – 50 K
Only if [Interlink function] parameter = On:
When the RT switching contact cooling is closed, the cooling feed target
temperature is reduced by the set value (see [Interlink function] para-
meter). Request, e.g. by HP convector.
5 K
1 K
N
E
Tab. 7-16
Parameter in the "Cooling" menu
7.6.5
Menu: Hot water
[→ Main menu → Configuration → DHW]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Max. hot water
loading time
10 – 240 min
Setting of the maximum duration of a domestic hot water preparation cycle.
Then cancellation of domestic hot water preparation if the current hot water
temperature does not reach the set target value in the [Hot water temperat-
ure target 1] parameter.
60 min
10 min
N
E
Summary of Contents for RoCon+ HP Series
Page 116: ...Betriebsanleitung 116 Daikin RoCon HP Daikin Regelung RoCon HP1 008 1447899_00 09 2019 DE ...
Page 236: ...Gebruiksaanwijzing 236 Daikin RoCon HP Daikin regeling RoCon HP1 008 1447899_00 09 2019 NL ...
Page 351: ...Driftsvejledning 351 Daikin RoCon HP Daikin regulering RoCon HP1 008 1447899_00 09 2019 DA ...
Page 406: ...Instruktionsbok 406 Daikin RoCon HP Daikin reglerenhet RoCon HP1 008 1447899_00 09 2019 SV ...
Page 460: ...Brukerveiledning 460 Daikin RoCon HP Daikin Regulering RoCon HP1 008 1447899_00 09 2019 NO ...
Page 516: ...008 1447899_00 09 2019 EN DE FR NL IT DA SV NO FI Copyright Daikin ...