Parameter settings
Operating Instructions
35
Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Room thermo-
stat
Configuration of a room thermostat with potential-free contacts connected
to Daikin Altherma ETS(X/H) connection J16.
-
N
E
No
Deactivated
Yes
Only if [Interlink function] parameter = Off:
Evaluation of the heating and cooling switching contacts at plug connection
J16 on the RoCon BM2C PCB (only if none of the "Standby", "Reduce",
"Summer", "Holiday", "Public holiday" or "Screed" is active):
▪ Closed heating switching contact: Operating mode is switched to "Heat-
ing". Priority if both switching contacts are closed.
▪ Closed cooling switching contact: Operating mode is switched to "Cool-
ing".
Open contacts: Only frost protection active.
Interlink func-
tion
Configuration for systems that are operated with 2 different feed target
temperatures (see
).
One possible application is, for example, the additional integration of an
HP convector in a surface heating and cooling system.
Prerequisite: 2 room thermostats are connected to Daikin Altherma ETS(X/
H) plug connection J16.
-
N
E
Off
Deactivated
On
Evaluation of the heating nd cooling switching contacts at plug connection
J16 on the RoCon BM2C PCB.
Activation of cooling mode only by switching the operating mode to "Cool-
ing" (see
Setting of the [Room thermostat] parameter is no longer evaluated.
▪ Open switching contacts: Only frost protection active
▪ "Heating" and "Automatic 1" / "Automatic 2" operating mode active dur-
ing the switching cycles in day mode.
▪ Closed heating switching contact = IL1:
▪ It is regulated to the normal feed target temperature in accordance
with the parameter settings in [→ Main menu → Configuration
→ Heating].
▪ Closed cooling switching contact = IL2:
▪ The system is regulated to the increased feed target temperature (nor-
mal feed target tempe value of the [Interlink temperature in-
crease ] parameter. Priority if both switching contacts are closed!
▪ "Cooling" operating mode active.
▪ Closed heating switching contact = IL1:
▪ It is regulated to the normal feed target temperature in accordance
with the parameter settings in [→ Main menu → Configuration
→ Heating].
▪ Closed cooling switching contact = IL2:
The system is regulated to the reduced feed target temperature (normal
feed target temperature value of the [Interlink temperature reduction] para-
meter. Priority if both switching contacts are closed
Programmable
output (230 V)
Configuration of the multi-function output (230 V, J14 connection):
-
N
E
Inactive
The output has no function.
Heating circuit
request
Header pump – The output becomes active as soon as any heating circuit
(e.g. mixer circuit) of the system reports a heat request to the heat gener-
ator.
Circulation re-
quest
Circulation pump – The output is activated either after the time program of
the circulation pump or after the time program of the domestic hot water
preparation, depending on the parametrisation (see
Direct heating
circuit request
Feeder pump – The output becomes active as soon as a heat requirement
is pending for the direct heating circuit of the heat generator.
Func. burner
blocking con-
tact
Resistance val-
ues
Selection of the functionality of the EXT switching contact (J8) (see
)
-
N
E
Burner blocking
contact
Summary of Contents for RoCon+ HP Series
Page 116: ...Betriebsanleitung 116 Daikin RoCon HP Daikin Regelung RoCon HP1 008 1447899_00 09 2019 DE ...
Page 236: ...Gebruiksaanwijzing 236 Daikin RoCon HP Daikin regeling RoCon HP1 008 1447899_00 09 2019 NL ...
Page 351: ...Driftsvejledning 351 Daikin RoCon HP Daikin regulering RoCon HP1 008 1447899_00 09 2019 DA ...
Page 406: ...Instruktionsbok 406 Daikin RoCon HP Daikin reglerenhet RoCon HP1 008 1447899_00 09 2019 SV ...
Page 460: ...Brukerveiledning 460 Daikin RoCon HP Daikin Regulering RoCon HP1 008 1447899_00 09 2019 NO ...
Page 516: ...008 1447899_00 09 2019 EN DE FR NL IT DA SV NO FI Copyright Daikin ...