background image

REMOVAL

PROCEDURE

S E R V I C E   M A N U A L

3.5 kW Class

Outdoor Unit

Non-Inverter

Pair Type

Si011414E

Summary of Contents for RNE35LV1

Page 1: ...REMOVAL PROCEDURE S E R V I C E M A N U A L 3 5 kW Class Outdoor Unit Non Inverter Pair Type Si011414E ...

Page 2: ...Service Manual Removal Procedure Outdoor Unit zCooling Only RNE35LV1 RNE35MV1 RNE35MV14 RNE35MV1V9 ...

Page 3: ...1 Table of Contents 1 Outer Panels 2 2 Outdoor Fan Fan Motor 4 3 Electrical Components Partition Plate 6 4 Sound Blanket 9 5 Capillary Tube 10 6 Compressor 12 Note The illustrations may be slightly different depending on the model ...

Page 4: ...rocedure Points 1 2 Remove the screw of the stop valve cover Slide the stop valve cover downward and remove it The stop valve cover is united with the shield plate When reassembling make sure to fit the 3 hooks 3 4 Remove the 3 screws and remove the top panel Remove the 6 screws of the front panel Stop valve cover R21343 Shield plate Hook R21344 Top panel Front panel R21345 ...

Page 5: ...n the 2 right side hooks Remove the front panel 7 8 Press the 2 projections from the rear side and rotate the discharge grille to the left to unfasten the 6 hooks Remove the discharge grille Step Procedure Points Front panel R21346 Discharge grille Hook Hook Projection Rear side R21347 ...

Page 6: ...ull out the terminal front black from the terminal board X1M 1 Pull out the 2 terminals red white from the capacitor C1R Cut the clamp and release the fan motor lead wire from the groove When reassembling put the fan motor lead wire through the back of the fan motor so as not to be entangled with the outdoor fan Terminal board Capacitor D cut Shaft Outdoor fan Nut R21348 10 mm 0 39 inch R18954 Cla...

Page 7: ...When reassembling fit the 2 lower hooks into the bottom frame 6 Unfasten the 2 hooks on the fan motor fixing frame and release the fan motor lead wire 7 Remove the 3 screws and remove the fan motor M4 12 Step Procedure Points Fan motor fixing frame R21350 R10460 Hook R21351 Fan motor lead wire Fan motor R21352 ...

Page 8: ...l power supplies before disassembling work Step Procedure Points 1 2 Remove the screw of the wire fixture Unfasten the hook and remove the wire fixture 3 Remove the 2 screws on the terminal board and disconnect the connecting wire 4 Remove the 5 screws and remove the right side panel Hook Wire fixture R21353 Connecting wire Terminal board Screw R21354 Right side panel R21355 ...

Page 9: ... the 3 terminals yellow red black from the capacitor C1R When reassembling confirm the terminal location Step Procedure Points Hook Hook R21356 Hook R21358 To compressor C blue To capacitor C black Terminal board X1M R21357 To compressor S yellow To compressor R red To terminal board 2 black Capacitor C1R R21360 C1R X1M To fan motor black To compressor C blue To capacitor C black To fan motor whit...

Page 10: ...ews of the capacitor fixing band Remove the capacitor 11 Remove the 2 screws and lift up the partition plate to remove it When reassembling fit the partition plate to the hook at the bottom frame Step Procedure Points Capacitor Capacitor fixing band R21361 Partition plate R21362 Hook R21363 ...

Page 11: ...ait for 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points 1 Untie the 2 strings and pull out the sound blanket Since the piping ports on the sound blanket are torn easily remove the blanket carefully Sound blanket R21364 R21365 ...

Page 12: ...the refrigerant gas is empty in the circuit Be sure to apply nitrogen replacement when heating up the brazed part Do not use a metal saw for cutting pipes by all means because the sawdust comes into the circuit When withdrawing the pipes be careful not to pinch them firmly with pliers The pipes may get deformed Provide a protective sheet or a steel plate so that the brazing flame cannot influence ...

Page 13: ...the compressor lead wires and remove the gasket 3 4 Remove the sheets of putty Heat up the 2 brazed parts and remove the capillary tube Capillary tube Step Procedure Points Gasket S yellow C blue R red R21367 Putty Capillary tube Putty Brazed part R21368 R21469 ...

Page 14: ... by non oxidation brazing Note Before working make sure that the refrigerant gas is empty in the circuit Be sure to apply nitrogen replacement when heating up the brazed part Do not use a metal saw for cutting pipes by all means because the sawdust comes into the circuit When withdrawing the pipes be careful not to pinch them firmly with pliers The pipes may get deformed Provide a protective sheet...

Page 15: ...brazed part of the discharge side pipe and disconnect it Heat up the brazed part of the suction side pipe and disconnect it Remove the 3 nuts of the compressor Lift the compressor up and remove it Step Procedure Points Gasket S yellow C blue R red R21367 Putty R21369 Compressor Brazed part of discharge side pipe Brazed part of suction side pipe Nut R21370 ...

Page 16: ...Revision History Month Year Version Revised contents 03 2015 Si011414E First edition ...

Page 17: ...sories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage electrical shock fire or explosion z Read the user s manual carefully before using this product The user s manual provides important safety instruc...

Reviews: