ELECTRICAL DATA
RKS+FHQ50B
RKS+FHQ60B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FHQ50BUV1B
RKS50BVMB9
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
79
7.5
53
0.18
62
0.6
FHQ60BUV1B
RKS60BVMB9
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
90
8.84
53
0.24
62
0.6
3D040597
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RHz
: Rated operating frequency(Hz)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps
W
: Rated motor output (W)
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. For more details concerning conditional connections, see
http://www.daikineurope.com/extranet, select ’’Daikin
Documentation’’ and select ’’conditional connection’’, ’’the
requested product type’’ and ’’English’’ from the drop down lists,
click the search button.
Finally, click on the document title of your choice.
•
Pair Application, Inverter Controlled Unit
•
R-410A
•
RKS50-60-71BVMB9
2
Specifications
1
2
5
•
Split - Sky Air
•
Outdoor Units