Precautions for Selecting the Location

1)  Choose a place solid enough to bear the weight and vibration of the unit, where the operation sounds will not be amplified.
2)  Choose a location where the hot air discharged from the unit or the operation sounds will not disturb the neighbors of the user.
3)  Avoid installing near bedrooms so that operation sounds will not be a problem.
4)  There must be sufficient spaces for carrying the unit into and out of the site.
5)  There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.
6)  The site must be free from the possibility of flammable gas leakage in a nearby place.
7)  Install units, power cords and inter-unit wire at least 10ft (3m) away from television and radio sets. This is to prevent interference 

to images and sounds. (Noises may be heard even if they are more than 10ft (3m) away depending on radio wave conditions.)

8)  In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the air conditioner.
9)  Since drain flows out of the outdoor unit, do not place anything under the unit which must be kept away from moisture. 

NOTE

Cannot be installed hanging from ceiling or stacked.

   CAUTION

When operating the air conditioner in a low outdoor ambient 
temperature, be sure to follow the instructions described below. 

• To prevent exposure to wind, install the outdoor unit with its suction 

side facing the wall.

• Never install the outdoor unit at a site where the suction side may 

be exposed directly to wind.

• To prevent exposure to wind, it is recommended to install a baffle 

plate on the air discharge side of the outdoor unit.

• In heavy snowfall areas, select an installation site where the snow 

will not affect the unit.

Construct a large canopy.
Construct a pedestal.

Install the unit high enough off the 
ground to prevent burying in snow.

Precautions on Installation

• Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed.
• In accordance with the foundation drawing, fix the unit securely by means of the foundation bolts.  

(Prepare 4 sets of 1/2 inch (M12) foundation bolts, nuts and washers each which are available on the market.)

• It is best to screw in the foundation bolts until their ends are 3/4 inch (20mm) from the foundation surface.

3/4 inch 

(20mm)

01_EN_3P300674-3.indd   3

10/13/2011   2:23:51 PM

Summary of Contents for RKS30LVJU

Page 1: ...lit series Français Español Manuel dinstallation Série split R410A Manual de instalación Serie Split R410A INSTALLATION MANUAL R410A Split Series Models RXS30LVJU RXS36LVJU RKS30LVJU RKS36LVJU 00_CV_3P300674 3 indd 1 10 21 2011 1 32 11 PM ...

Page 2: ...gs so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk of explosion resulting in serious injury or death Do not ground units to telephone wires or lightning rods because lightning strikes could cause a severe shock hazard resulting in severe injury or dea...

Page 3: ...re to install a ground fault circuit interrupter breaker may result in electrically shocks or fire personal injury CAUTION Do not install the air conditioner where gas leakage would be exposed to open flames If the gas leaks and builds up around the unit it may catch fire Establish drain piping according to the instructions of this manual Inadequate piping may cause water damage Tighten the flare ...

Page 4: ...nything under the unit which must be kept away from moisture NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent exposure to wind install the outdoor unit with its suction side facing the wall Never install the outdoor unit at a site where the suction s...

Page 5: ...ce below the ceiling surface 9 7 8 250 from wall Allow space for piping and electrical servicing Right side plate 13 3 4 350 Clamping material Insulation tube Bottom frame Tape Also insulate the connection on the outdoor unit Use tape or insulating material on all connections to prevent air from getting in between the copper piping and the insulation tube Be sure to do this if the outdoor unit is ...

Page 6: ...rain socket A drain caps B and a drain hose with the outdoor unit Otherwise drain water may freeze impairing heating performance 1 Insert drain receiver C onto drain socket A and drain cap B beyond 4 projections around drain socket and drain cap 2 Insert drain socket and drain caps into their matching drain hole Drain socket A into drain hole I and drain caps B into the other drain holes After ins...

Page 7: ...are nuts to prevent damage to the flare nuts and gas leakage Flare nut tightening torque Liquid side 3 8 inch 9 5mm 24 1 29 4ft lbf 32 7 39 9N m Gas side 5 8 inch 15 9mm 45 6 55 6ft lbf 61 8 75 4N m Valve cap tightening torque Liquid side 3 8 inch 9 5mm 15 9 20 2ft lbf 21 6 27 4N m Gas side 5 8 inch 15 9mm 35 5 44 0ft lbf 48 1 59 7N m Service port cap tightening torque Do not apply refrigeration o...

Page 8: ...re gauge reads 29 9inHg 0 1MPa 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back 2 5 Remove caps from liquid stop valve and gas stop valve 6 Turn the liquid stop valve s rod 90 degrees counterclockwise with a hexagonal wrench to open valve Close it after 5 seconds and che...

Page 9: ...e as possible Use a pipe bender for bending 7 2 Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the following 1 Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to 0 045kcal mh C Be sure to use insulation that is designed for use with HVAC Systems 2 Be sure to insulate both the gas an...

Page 10: ...cooling operation switch SW1 Wiring WARNING Do not use tapped wires stranded wires extension cords or starburst connections as they may cause overheating electrical shock or fire Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the terminal block Doing so may cause electric shock or fire Be sure to install a ground fault circuit i...

Page 11: ...ing the binding band as shown in the figure Secure firmly making sure no outside pressure is exerted on the terminals Power supply terminal block L1 L2 1 2 3 Use the specified wires and connect them securely Shape the wires so that there is no lifting of the service hatch or other structural parts D C Observe the notes mentioned following when wiring to the power supply terminal block Precautions to ...

Page 12: ...is designed for facilities such as equipment or computer rooms It is never to be used in a residence or office where people occupy the space 1 You can expand the operation range to 14 F 10 C by turning on switch B SW4 on the PCB If the outdoor temperature falls to 0 4 F 18 C or lower the operation will stop If the outdoor temperature rises the operation will start again LED A SW4 ON A B CD S102 SW...

Page 13: ...3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts such as fin movement are working properly The air conditioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut o...

Page 14: ...3P300674 3 M11B136 1111 HT Two dimensional bar code is a code for manufacturing 00_CV_3P300674 3 indd 2 10 21 2011 1 32 12 PM ...