Outdoor Unit Installation Drawings 

Max. allowable piping height

Min. allowable piping length

Max. allowable piping length

98.4ft (30m)

6.56ft (2m)

65.6ft (20m)

Liquid pipe

Gas pipe

O.D. 3/8 inch (9.5mm)

O.D. 5/8 inch (15.9mm)

0.54oz/ft (50g/m)

Additional refrigerant 

required for refrigerant 

pipe exceeding 

32.8ft (10m) in length. 

**

*

 *

 Be sure to add the proper amount of additional refrigerant.

  Failure to do so may result in reduced performance.

**

 The suggested shortest pipe length is 6.56ft (2m), in order to avoid 

  noise from the outdoor unit and vibration. 
  (Mechanical noise and vibration may occur depending on how 
  the unit is installed and the environment in which it is used.)

Wrap the insulation 

pipe with the finishing 

tape from bottom to top.

Allow 11-13/16 inch (300mm) 

of work space below the 

ceiling surface.

9-7/8 (250) from w

all

Allow space for piping 

and electrical servicing.

Right side plate

13-3/4

(350)

Clamping material

Insulation tube

Bottom frame

Tape

Also insulate the connection on the outdoor unit.

Use tape or insulating material on all connections 
to prevent air from getting in between the copper 
piping and the insulation tube.
Be sure to do this if the outdoor unit is installed 
above.

(Foot bolt-hole 

 centers)

(Foot bolt-hole centers)

24-7/16

(620)

Level mounting base 

(available separately)

If there is the danger of the unit falling 

or overturning, fix the unit with 

foundation bolts, or with wire or other 

means.

If the location does not have good 

drainage, place the unit on a level 

mounting base (or a plastic pedestal). 

Install the outdoor unit in a level 

position. Failure to do so may result in 

water leakage or accumulation.

CAUTION

** Set the piping length 

  from 6.56ft (2m) to 
  98.4ft (30m).

unit : inch (mm)

01_EN_3P300674-3.indd   4

10/13/2011   2:23:51 PM

Summary of Contents for RKS30LVJU

Page 1: ...lit series Français Español Manuel dinstallation Série split R410A Manual de instalación Serie Split R410A INSTALLATION MANUAL R410A Split Series Models RXS30LVJU RXS36LVJU RKS30LVJU RKS36LVJU 00_CV_3P300674 3 indd 1 10 21 2011 1 32 11 PM ...

Page 2: ...gs so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk of explosion resulting in serious injury or death Do not ground units to telephone wires or lightning rods because lightning strikes could cause a severe shock hazard resulting in severe injury or dea...

Page 3: ...re to install a ground fault circuit interrupter breaker may result in electrically shocks or fire personal injury CAUTION Do not install the air conditioner where gas leakage would be exposed to open flames If the gas leaks and builds up around the unit it may catch fire Establish drain piping according to the instructions of this manual Inadequate piping may cause water damage Tighten the flare ...

Page 4: ...nything under the unit which must be kept away from moisture NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent exposure to wind install the outdoor unit with its suction side facing the wall Never install the outdoor unit at a site where the suction s...

Page 5: ...ce below the ceiling surface 9 7 8 250 from wall Allow space for piping and electrical servicing Right side plate 13 3 4 350 Clamping material Insulation tube Bottom frame Tape Also insulate the connection on the outdoor unit Use tape or insulating material on all connections to prevent air from getting in between the copper piping and the insulation tube Be sure to do this if the outdoor unit is ...

Page 6: ...rain socket A drain caps B and a drain hose with the outdoor unit Otherwise drain water may freeze impairing heating performance 1 Insert drain receiver C onto drain socket A and drain cap B beyond 4 projections around drain socket and drain cap 2 Insert drain socket and drain caps into their matching drain hole Drain socket A into drain hole I and drain caps B into the other drain holes After ins...

Page 7: ...are nuts to prevent damage to the flare nuts and gas leakage Flare nut tightening torque Liquid side 3 8 inch 9 5mm 24 1 29 4ft lbf 32 7 39 9N m Gas side 5 8 inch 15 9mm 45 6 55 6ft lbf 61 8 75 4N m Valve cap tightening torque Liquid side 3 8 inch 9 5mm 15 9 20 2ft lbf 21 6 27 4N m Gas side 5 8 inch 15 9mm 35 5 44 0ft lbf 48 1 59 7N m Service port cap tightening torque Do not apply refrigeration o...

Page 8: ...re gauge reads 29 9inHg 0 1MPa 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back 2 5 Remove caps from liquid stop valve and gas stop valve 6 Turn the liquid stop valve s rod 90 degrees counterclockwise with a hexagonal wrench to open valve Close it after 5 seconds and che...

Page 9: ...e as possible Use a pipe bender for bending 7 2 Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the following 1 Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to 0 045kcal mh C Be sure to use insulation that is designed for use with HVAC Systems 2 Be sure to insulate both the gas an...

Page 10: ...cooling operation switch SW1 Wiring WARNING Do not use tapped wires stranded wires extension cords or starburst connections as they may cause overheating electrical shock or fire Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the terminal block Doing so may cause electric shock or fire Be sure to install a ground fault circuit i...

Page 11: ...ing the binding band as shown in the figure Secure firmly making sure no outside pressure is exerted on the terminals Power supply terminal block L1 L2 1 2 3 Use the specified wires and connect them securely Shape the wires so that there is no lifting of the service hatch or other structural parts D C Observe the notes mentioned following when wiring to the power supply terminal block Precautions to ...

Page 12: ...is designed for facilities such as equipment or computer rooms It is never to be used in a residence or office where people occupy the space 1 You can expand the operation range to 14 F 10 C by turning on switch B SW4 on the PCB If the outdoor temperature falls to 0 4 F 18 C or lower the operation will stop If the outdoor temperature rises the operation will start again LED A SW4 ON A B CD S102 SW...

Page 13: ...3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts such as fin movement are working properly The air conditioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut o...

Page 14: ...3P300674 3 M11B136 1111 HT Two dimensional bar code is a code for manufacturing 00_CV_3P300674 3 indd 2 10 21 2011 1 32 12 PM ...

Reviews: