Outdoor Unit Installation Drawings

Installation Guidelines

• Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the 

installation guidelines below.

• For any of the below installation patterns, the wall height on the exhaust side should be 47-1/4 inch 

(1200mm) or less.

* Be sure to add the proper amount of additional refrigerant. 

Failure to do so may result in reduced performance.

Max. allowable height

Max. allowable length

98.4ft (30m)

65.6ft (20m)

Model

30/36 class

Liquid pipe

Gas pipe

O.D. 3/8 inch (9.5mm)

O.D. 5/8 inch (15.9mm)

0.55oz/ft

(50g/m)

Additional refrigerant 
required for refrigerant 
pipe exceeding 32ft 
(10m) in length.

Min. allowable length

6.6ft (2m)

More than 1-15/16”

(50mm)

More 
than 
3-15/16”
(100mm)

More than 13-3/4” (350mm)

47-1/4” 
(1200mm)
or less

More than 1-15/16”

(50mm)

More than 
13-3/4”
(350mm)

Wrap the insulation 
pipe with the finishing 
tape from bottom to top.

Allow 11-13/16 inch (300mm) 
of work space below the 
ceiling surface.

9-7/8” (250mm) from w

all

Allow space for piping 
and electrical servicing.

Right side plate

13-5/8”

(345mm)

Clamping material

Insulation tube

Bottom frame

Tape

Also insulate the connection on the outdoor unit.

Use tape or insulating material on all connections 
to prevent air from getting in between the copper 
piping and the insulation tube.
Be sure to do this if the outdoor unit is installed 
above.

(F

oot bolt-hole 

 centres)

(Foot bolt-hole centres)

24-7/16”

(620mm)

Level mounting base 
(available separately)

If there is the danger of the unit falling 
or overturning, fix the unit with 
foundation bolts, or with wire or other 
means.

If the location does not have good 
drainage, place the unit on a level 
mounting base (or a plastic pedestal). 
Install the outdoor unit in a level 
position. Failure to do so may result in 
water leakage or accumulation.

More than 3-15/16”

(100mm)

Side view

Wall facing one side

Top view

Walls facing two sides

Top view

More than 3-15/16”

(100mm)

More than 13-3/4”

(350mm)

More than 1-15/16”

(50mm)

Walls facing three sides

CAUTION

Set the piping length 
from 6.6ft (2m) to 98.4ft (30m).

Summary of Contents for RKS30

Page 1: ... if it comes in contact with fire such as from a fan heater stove or cooking device Exposure to this gas could cause severe injury or death Do not ground units to water pipes telephone wires or lightning rods because incomplete grounding could cause a severe shock hazard resulting in severe injury or death and to gas pipes because a gas leak could result in an explosion which could lead to severe ...

Page 2: ...ecified types of wires for electrical connections between the indoor and outdoor units Follow all state and local electrical codes Firmly clamp the inter unit wire so their terminals receive no external stresses Incomplete connections or clamping may cause terminal overheating fire or equipment damage After connecting all wiring be sure to shape the cables so that they do not put undue stress on t...

Page 3: ... under the unit anything which must be kept away from moisture NOTE Cannot be installed hanging from ceiling or stacked Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed In accordance with the foundation drawing fix the unit securely by means of the foundation bolts Prepare four sets of 1 2 inch M12 foundation b...

Page 4: ...mm of work space below the ceiling surface 9 7 8 250mm from wall Allow space for piping and electrical servicing Right side plate 13 5 8 345mm Clamping material Insulation tube Bottom frame Tape Also insulate the connection on the outdoor unit Use tape or insulating material on all connections to prevent air from getting in between the copper piping and the insulation tube Be sure to do this if th...

Page 5: ...ps into their matching drain hole Drain socket A into drain hole I and drain caps B into drain hole II and III After insertion turn them about 40 clockwise Be sure not to insert them into wrong drain holes or there causes water leakage View from bottom 3 Connect vinyl hose on the market internal diameter of 1 inch 25mm to drain socket A If the hose is too long and hangs down fix it carefully to pr...

Page 6: ...9 7N m Valve cap tightening torque Service port cap tightening torque 7 9 10 8ft lbf 10 8 14 7N m CAUTION 1 Use the flare nut fixed to the main unit To prevent cracking of the flare nut by aged deterioration 2 To prevent gas leakage apply refrigeration oil only to the inner surface of the flare Use refrigeration oil for R410A 3 Use torque wrenches when tightening the flare nuts to prevent damage t...

Page 7: ...mage the vacuum pump or the unit 1 Connect projection side of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and make sure that the compound pressure gauge reads 29 9inHg 0 1MPa 1 4 Close gauge...

Page 8: ...sure to pump down when relocating or disposing of the unit 1 Remove the valve cap from liquid stop valve and gas stop valve 2 Carry out forced cooling operation 3 After 5 to 10 minutes close the liquid stop valve with a hexagonal wrench 4 After 2 to 3 minutes close the gas stop valve and stop forced cooling operation Forced cooling operation 1 Press the Forced Operation switch SW1 to begin forced ...

Page 9: ...er harmonics This unit uses an inverter which means that it must be used an earth leak detector capable handling harmonics in order to prevent malfunctioning of the earth leak detector itself 4 Use an all pole disconnection type breaker with at least 1 8 inch 3mm between the contact point gaps 5 When carrying out wiring connection take care not to pull at the conduit 6 Do not connect the power wir...

Page 10: ...voidable reasons be sure to observe the following instruction Place the round crimp style terminals on the wires up to the covered part and secure in place Ground terminal installation Use the following method when installing the round crimp style terminal CAUTION 1 Stranded wire Round crimp style terminal 1 2 3 1 2 3 Safety breaker 20A Earth leakage circuit breaker Earth Firmly fix the wires with...

Page 11: ...door temperature rises the operation will start again 1 If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind provide a windbreak wall 2 Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings 3 Do not place humidifiers or other items which might raise the humidity in rooms where facilit...

Page 12: ...ter it is turned off 1 3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts are working properly The air conditioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut...

Page 13: ...3P235796 1F M08B133E ...

Reviews: