ELECTRICAL DATA
RKS+FCQ35B
RKS+FCQ50B
RKS+FCQ60B
* This information was not available at the time of publication.
RKS+FHQ35B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FHQ35BUV1B
RKS35BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
15
15
78
4.91
19
0.35
62
0.6
3D040596
RKS+FHQ50B
RKS+FHQ60B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FHQ50BUV1B
RKS50BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
79
7.5
53
0.18
62
0.6
FHQ60BUV1B
RKS60BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
90
8.84
53
0.24
62
0.6
3D040597
RKS+FBQ35B
RKS+FBQ50B
RKS+FBQ60B
* This information was not available at the time of publication.
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RHz
: Rated operating frequency (Hz)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps
W
: Rated motor output (W)
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
•
Pair Application
•
R-410A
•
RKS25-35-50-60-71BVMB
2
Specifications
2
7
•
Split - Sky Air
•