ii

 CAUTION

• 

Do not touch the switch with wet fingers. Touching a switch 
with wet fingers may result in electric shock.

• 

Do not allow children to play on or around the unit or it 
may result in injury.

• 

The heat exchanger fins are sharp enough to cut, and 
may result in injury if improperly used. To avoid injury wear 
glove or cover the fins when working around them.

• 

Do not touch the refrigerant pipes during and immediately 
after operation as the refrigerant pipes may be hot or 
cold, depending on the condition of the refrigerant flow

-

ing through the refrigerant piping, compressor, and other 
refrigerant cycle parts. It may result in your hands get

-

ting burns or frostbite if you touch the refrigerant pipes. 
To avoid injury, give the pipes time to return to normal 
temperature or, if you must touch them, be sure to wear 
proper gloves.

• 

Install drain piping to proper drainage. Improper drain pip

-

ing may result in water leakage and property damage.

• 

Insulate piping to prevent condensation.

• 

Be careful when transporting the product.

• 

Do not turn off the power immediately after stopping 
operation. Always wait for at least 5 minutes before turning 
off the power. Otherwise, water leakage may result.

• 

Do not use a charging cylinder. Using a charging cylinder 
may cause the refrigerant to deteriorate.

• 

Refrigerant R410A in the system must be kept clean, dry, 
and tight.
(a)  Clean and Dry - Foreign materials (including mineral 

oils such as SUNISO oil or moisture) should be pre

-

vented from getting into the system.

(b)  Tight - R410A does not contain any chlorine, does 

not destroy the ozone layer, and does not reduce the 
earth’s protection again harmful ultraviolet radiation. 
R410A can contribute to the greenhouse effect if it is 
released. Therefore take proper measures to check 
for the tightness of the refrigerant piping installation. 
Read the chapter Refrigerant Piping and follow the 
procedures.

• 

Since R410A is a blend, the required additional refriger

-

ant must be charged in its liquid state. If the refrigerant is 
charged in a state of gas, its composition can change and 
the system will not work properly.

• 

The indoor unit is for R410A. See the catalog for indoor 
models that can be connected. Normal operation is not 
possible when connected to other units.

• 

Remote controller (wireless kit) transmitting distance can 
be shorter than expected in rooms with electronic fluores

-

cent lamps (inverter or rapid start types). Install the indoor 
unit far away from fluorescent lamps as much as possible.

• 

Indoor units are for indoor installation only. Outdoor units 
can be installed either outdoors or indoors. This unit is for 
indoor use.

• 

Do not install the air conditioner or heat pump in the fol

-

lowing locations:
(a)  Where a mineral oil mist or oil spray or vapor is pro

-

duced, for example, in a kitchen.
Plastic parts may deteriorate and fall off and thus may 
result in water leakage.

(b)  Where corrosive gas, such as sulfurous acid gas, is 

produced.
Corroding copper pipes or soldered parts may result 
in refrigerant leakage.

(c)  Near machinery emitting electromagnetic waves.

Electromagnetic waves may disturb the operation of 
the control system and cause the unit to malfunction.

(d)  Where flammable gas may leak, where there is car

-

bon fiber, or ignitable dust suspension in the air, or 
where volatile flammables such as thinner or gasoline 
are handled. Operating the unit in such conditions 
may result in a fire.

• 

Take adequate measures to prevent the outdoor unit from 
being used as a shelter by small animals. Small animals 
making contact with electrical parts may result in malfunc

-

tions, smoke, or fire. Instruct the customer to keep the 
area around the unit clean.

 NOTE

• 

Install the power supply and transmission wires for the in

-

door and outdoor units at least 3.5 ft. (1 m) away from tele

-

visions or radios to prevent image interference or noise. 
Depending on the radio waves, a distance of 3.5 ft. (1 m) 
may not be sufficient to eliminate the noise.

• 

Dismantling the unit, treatment of the refrigerant, oil and 
additional parts must be done in accordance with the 
relevant local, state, and national regulations.

• 

Do not use the following tools that are used with con

-

ventional refrigerants: gauge manifold, charge hose, gas 
leak detector, reverse flow check valve, refrigerant charge 
base, vacuum gauge, or refrigerant recovery equipment.

• 

If the conventional refrigerant and refrigerator oil are 
mixed in R410A, the refrigerant result in deterioration.

• 

This air conditioner or heat pump is an appliance that 
should not be accessible to the general public.

• 

As design pressure is 478 psi (3.3 MPa), the wall thick

-

ness of field-installed pipes should be selected in accor

-

dance with the relevant local, state, and national regula

-

tions.

Codes and Regulations

This product is designed and manufactured to comply with 
national codes. Installation in accordance with such codes 
and/or prevailing local codes/regulations is the responsibility 
of the installer. The manufacturer assumes no responsibility 
for equipment installed in violation of any codes or regula

-

tions. Rated performance is achieved after 72 hours of opera

-

tion. 
Make sure to use a DAIKIN specified checker while measur

-

ing sub cooling. Do not use the check valve or the other port 
to measure it.

01_EN_3P734038-1_PL.indd   2

01_EN_3P734038-1_PL.indd   2

2023/05/29   10:18:20

2023/05/29   10:18:20

Summary of Contents for REYQ72XBTJ Series

Page 1: ...XBYC REYQ432XBYC VRV System air conditioner Please visit http www daikinac com content resources manuals for the most current version of installation instructions and service manual In the event of co...

Page 2: ...llation work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric shock or fire When installing the unit in a small room t...

Page 3: ...alled either outdoors or indoors This unit is for indoor use Do not install the air conditioner or heat pump in the fol lowing locations a Where a mineral oil mist or oil spray or vapor is pro duced f...

Page 4: ...Field wiring 18 9 1 Power circuit safety device and cable requirements 19 9 2 Wiring connection example for whole system 19 9 3 Leading wire procedure 19 9 4 Transmission wiring connection procedure...

Page 5: ...ion for REYQ X units are as indicated in tables right where REYQ 192 456 consists of multiple REYQ 96 168 single modules as indicated 72 96 120 144 168 REYQ72XBTJ XBYD XBYC 1 REYQ96XBTJ XBYD XBYC 1 RE...

Page 6: ...6XBTJ XBYD XBYC 108 280 REYQ240XBTJ XBYD XBYC 120 312 REYQ264XBTJ XBYD XBYC 132 343 REYQ288XBTJ XBYD XBYC 144 374 REYQ312XBTJ XBYD XBYC 156 405 REYQ336XBTJ XBYD XBYC 168 436 REYQ360XBTJ XBYD XBYC 180...

Page 7: ...lation location is flat to prevent vibrations and noise generation and to have sufficient stability The space around the unit is adequate for maintenance and servic ing refer to 5 2 Service space on p...

Page 8: ...esult in the unit turning over 4 2 Weather related precautions Be sure that the air inlet of the unit is not positioned towards the main wind direction Frontal wind will disturb the operation of the u...

Page 9: ...ossibilities a b a c d a b a e d e c a b a e d f c a b a e b d c a b a e d f c 1 2 3 5 4 ABCD Sides along the installation site with obstacles Suction side A B C D A B 1 a 3 8 10 b 11 3 4 300 c 3 8 10...

Page 10: ...e Engineering Data Book 6 Inspecting handling and unpacking the unit 6 1 Inspection At delivery the unit must be checked and any damage must be re ported immediately to the carrier s claims agent 6 2...

Page 11: ...gth remains 13 16 in 20 mm above the foundation surface A A 13 16 in 20 mm NOTE There are restrictions on the refrigerant pipe connecting order between outdoor units in the case of the multi system Se...

Page 12: ...he stop valve until 9 Field wiring on page 18 and 12 Checking of device and installation conditions on page 24 are complete Do not use flux when brazing the refrigerant piping Use the phosphor cop per...

Page 13: ...mm 24 30 36 42 48 54 5 8 in 15 9 mm 3 8 in 9 5 mm 72 3 4 in 19 1 mm 96 7 8 in 22 2 mm 7 4 Selection of refrigerant branch kits For piping example refer to 7 3 Selection of piping size on page 9 When...

Page 14: ...ontally paying attention to the installation restrictions indicated in 8 Precautions on refrigerant piping on page 14 Example of connection Outdoor unit side Indoor unit side Branch Selector unit 1 2...

Page 15: ...valent length 43 ft 13 m B C 33 ft 10 m equivalent length 43 ft 13 m B D 33 ft 10 m equivalent length 43 ft 13 m Allowable height differ ence From outdoor unit to indoor unit Height difference Height...

Page 16: ...ize the liquid pipes b c d e f and g in the figure in the right The upsizing specifications should be as fol lows 3 8 in 9 5 mm 1 2 in 12 7 mm 1 2 in 12 7 mm 5 8 in 15 9 mm 5 8 in 15 9 mm 3 4 in 19 1...

Page 17: ...film ad versely affects valves and compressors in the refrigerating system and prevents proper operation The Dry Nitrogen pressure should be set to 2 9 psi 0 02 MPa i e just enough so it can be felt o...

Page 18: ...tion gas pipe stop value Protective plate Stop valves mounting plate High low pressure gas pipe stop valve 5 Cut off the lower part of the smaller pinched piping with an ap propriate tool such as pipe...

Page 19: ...ing 8 2 4 Precautions when connecting piping between outdoor units multiple outdoor units system To connect the piping between outdoor units an optional multi connection piping kit BHFP26P100U BHFP26P...

Page 20: ...he horizontal plane Mount the REFNET header so that it branches horizontally 2 Installation of the multi connection piping kit 1 B 1 C D 15 15 A C 4 3 4 in 120 mm D 19 11 16 in 500 mm Install the join...

Page 21: ...ightening the service port cover 9 Field wiring NOTE All field wiring and components must be installed by a licensed elec trician and must comply with relevant local and national regulations Be sure t...

Page 22: ...f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 18 9 21 1 2...

Page 23: ...work onsite settings and so on are done by operating the printed circuit board A1P of Master unit NOTE Do not connect the power wiring to terminals for the transmission wiring Doing so would destroy t...

Page 24: ...See the figure below Crimp style terminal Insulating sleeve Power wire For wiring use the designated power wire and connect firmly then secure to prevent outside pressure being exerted on the termina...

Page 25: ...TE Always use nitrogen gas for the air tightness test Absolutely do not open the stop valve until the main power circuit insulation measurement has been completed Measuring after the stop valve is ope...

Page 26: ...uum break with nitrogen gas and evacuate the system again using the vacuum pump for 1 hour to 500 microns or less vacuum drying If the system cannot be evacuated to 500 microns within 2 hours repeat t...

Page 27: ...t the 7 segment display s To access you can remove the service window cover see figure Now you can open the inspection door of the control box cover see figure You can see 3 push buttons and 3 seven s...

Page 28: ...nected to the system Result mode 1 setting 10 is addressed and selected return value is monitored information To leave the monitoring function push BS1 one time you will return to the default situati...

Page 29: ...e the refrigerant more than the specified amount This outdoor unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths systems require additional charg ing of refrigerant...

Page 30: ...er for systems and each pipe length is shown below Example 7 5 System piping length limitations on page 11 Outdoor system REYQ240XBYC REYQ120XBYC REYQ120XBYC Branch Selector units BS4Q54T 1 BSQ60T 1 B...

Page 31: ...form may cause the refrigerant composition to change preventing normal operation Before charging check whether the refrigerant cylinder is equipped with a siphon tube or not If a siphon tube is equipp...

Page 32: ...han 22 lbs 10 kg perform step 3 till the end of the procedure 3 Pre charging can be done without compressor running by con necting the refrigerant tank only to the liquid stop valve service port open...

Page 33: ...not forget to close the cover of the service port The tightening torque for the cover is 8 48 to 10 3 ft lbf 11 5 to 13 9 N m 15 Start up and configuration INFORMATION It is important that all inform...

Page 34: ...ion of the outdoor unit system The first method is to enable an automatic low noise opera tion during night time by field setting The unit will operate at the selected low noise level during the selec...

Page 35: ...tional external control adaptor DTA104A61 62 is installed Default value 0 To activate this function change 2 12 1 2 18 Fan high static pressure setting In order to increase the static pressure the out...

Page 36: ...aptor is required to perform power consumption limitation If the system always needs to run under power consump tion limitation conditions this setting activates and defines the level power consumptio...

Page 37: ...act your Daikin sales representative for further details 2 81 Cooling comfort setting for VRT control Default value 1 Value 2 81 Cooling comfort setting 0 Eco 1 Mild default 2 Quick 3 Powerful Change...

Page 38: ...ult 8 40 4 4 9 45 7 2 10 50 10 11 55 12 7 12 60 15 5 13 65 18 3 14 AUX Heater always NOT allowed 15 AUX Heater always allowed 2 98 Aux heater max allowable temp release differential AUX Heater is not...

Page 39: ...iliary or secondary heat source to be automatically energized in the event of a system failure Error codes capable of auto backup are listed in the table below Please be aware that the error codes tha...

Page 40: ...rt feeling for the customer The selection method of indoor units is important and has to be considered as the available capacity is not the same as under basic operation For details concerning to Hi s...

Page 41: ...uest from the indoor units becomes more moderate the system will eventually go to the steady state condition which is defined by the operation method above The start up condition is different from the...

Page 42: ...ing air purge etc See installation manual of the Branch Selector units and the indoor units for details CAUTION Do not insert fingers rods or other objects into the air inlet or outlet When the fan is...

Page 43: ...compressor 4 Make sure the default idle situation is existing see 13 2 Operat ing the push buttons and DIP switches on the printed circuit board on page 24 Push BS2 for 5 seconds or more The unit will...

Page 44: ...E A7P X11A Check connection on printed circuit board or actuator F3 01 03 05 Discharge temperature too high R21T Stop valves are closed Reverse connection of high low pressure gas pipe and suction gas...

Page 45: ...on trouble 208 230 460V A3P X6A A1P X28A 575V A4P X6A A1P X28A Check connection 19 20 21 Transmission trouble 208 230 460V A5P X3A A3P X41A 575V A5P X3A A4P X41A Check connection 24 25 26 Transmission...

Page 46: ...ct refer ring to the wiring diagram for Branch Selector units and correct if there are any errors Check that the DIP switches settings are correct referring to the installation manual enclosed in Bran...

Page 47: ...e operation on the inverter equipment Be careful not to touch the live parts If a fan rotates due to strong wind it may store electricity in the capacitor or in the main circuit and cause electric sho...

Page 48: ...ely event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum charge of refrigerant and the calculation of the...