background image

3P477778-7G English

ii

 CAUTION

•  Do not touch the switch with wet fingers. Touching a switch 

with wet fingers may result in electric shock.

• 

Do not allow children to play on or around the unit or it 
may result in injury.

•  The heat exchanger fins are sharp enough to cut, and 

may result in injury if improperly used. To avoid injury wear 

glove or cover the fins when working around them.

• 

Do not touch the refrigerant pipes during and immediately 
after operation as the refrigerant pipes may be hot or 

cold, depending on the condition of the refrigerant flow

-

ing through the refrigerant piping, compressor, and other 
refrigerant cycle parts. It may result in your hands get-
ting burns or frostbite if you touch the refrigerant pipes. 
To avoid injury, give the pipes time to return to normal 
temperature or, if you must touch them, be sure to wear 
proper gloves.

• 

Install drain piping to proper drainage. Improper drain pip-
ing may result in water leakage and property damage.

• 

Insulate piping to prevent condensation.

• 

Be careful when transporting the product.

• 

Do not turn off the power immediately after stopping 
operation. Always wait for at least 5 minutes before turning 
off the power. Otherwise, water leakage may result.

• 

Do not use a charging cylinder. Using a charging cylinder 
may cause the refrigerant to deteriorate.

• 

Refrigerant R410A in the system must be kept clean, dry, 
and tight.
(a)  Clean and Dry - Foreign materials (including mineral 

oils such as SUNISO oil or moisture) should be pre-
vented from getting into the system.

(b)  Tight - R410A does not contain any chlorine, does 

not destroy the ozone layer, and does not reduce the 
earth’s protection again harmful ultraviolet radiation. 
R410A can contribute to the greenhouse effect if it is 
released. Therefore take proper measures to check 
for the tightness of the refrigerant piping installation. 
Read the chapter Refrigerant Piping and follow the 
procedures.

• 

Since R410A is a blend, the required additional refriger-
ant must be charged in its liquid state. If the refrigerant is 
charged in a state of gas, its composition can change and 
the system will not work properly.

• 

The indoor unit is for R410A. See the catalog for indoor 
models that can be connected. Normal operation is not 
possible when connected to other units.

• 

Remote controller (wireless kit) transmitting distance can 

be shorter than expected in rooms with electronic fluores

-

cent lamps (inverter or rapid start types). Install the indoor 

unit far away from fluorescent lamps as much as possible.

• 

Indoor units are for indoor installation only. Outdoor units 
can be installed either outdoors or indoors. This unit is for 
indoor use.

• 

Do not install the air conditioner or heat pump in the fol-
lowing locations:
(a)  Where a mineral oil mist or oil spray or vapor is pro-

duced, for example, in a kitchen.

Plastic parts may deteriorate and fall off and thus may 
result in water leakage.

(b)  Where corrosive gas, such as sulfurous acid gas, is 

produced.
Corroding copper pipes or soldered parts may result 
in refrigerant leakage.

(c)  Near machinery emitting electromagnetic waves.

Electromagnetic waves may disturb the operation of 

the control system and cause the unit to malfunction.

(d) 

Where flammable gas may leak, where there is car

-

bon fiber, or ignitable dust suspension in the air, or 
where volatile flammables such as thinner or gasoline 

are handled. Operating the unit in such conditions 

may result in a fire.

• 

Take adequate measures to prevent the outdoor unit from 
being used as a shelter by small animals. Small animals 
making contact with electrical parts may result in malfunc-

tions, smoke, or fire. Instruct the customer to keep the 

area around the unit clean.

 NOTE

• 

Install the power supply and transmission wires for the in-

door and outdoor units at least 3.5 ft. (1 m) away from tele

-

visions or radios to prevent image interference or noise. 

Depending on the radio waves, a distance of 3.5 ft. (1 m) 
may not be sufficient to eliminate the noise.

• 

Dismantling the unit, treatment of the refrigerant, oil and 
additional parts must be done in accordance with the 
relevant local, state, and national regulations.

• 

Do not use the following tools that are used with con-
ventional refrigerants: gauge manifold, charge hose, gas 

leak detector, reverse flow check valve, refrigerant charge 

base, vacuum gauge, or refrigerant recovery equipment.

• 

If the conventional refrigerant and refrigerator oil are 

mixed in R410A, the refrigerant result in deterioration.

• 

This air conditioner or heat pump is an appliance that 
should not be accessible to the general public.

• 

As design pressure is 478 psi (3.3 MPa), the wall thick-

ness of field-installed pipes should be selected in accor

-

dance with the relevant local, state, and national regula-
tions.

Codes and Regulations

This product is designed and manufactured to comply with 
national codes. Installation in accordance with such codes 
and/or prevailing local codes/regulations is the responsibility 
of the installer. The manufacturer assumes no responsibility 
for equipment installed in violation of any codes or regula-
tions. Rated performance is achieved after 72 hours of opera-
tion. 

Make sure to use a DAIKIN specified checker while measur

-

ing sub cooling. Do not use the check valve or the other port 
to measure it.

01_EN_3P477778-7G.indb   2

1/15/2019   10:57:51

Summary of Contents for REYQ120XATJU

Page 1: ...12XAYCU REYQ336XAYCU REYQ360XAYCU REYQ384XAYCU REYQ408XAYCU REYQ432XAYCU VRV System air conditioner Please visit http www daikinac com content resources manuals for the most current version of install...

Page 2: ...sonnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric shock or fire When instal...

Page 3: ...only Outdoor units can be installed either outdoors or indoors This unit is for indoor use Do not install the air conditioner or heat pump in the fol lowing locations a Where a mineral oil mist or oi...

Page 4: ...size and allowable pipe length 9 7 1 General information 9 7 2 Selection of piping material 9 7 3 Selection of piping size 9 7 4 Selection of refrigerant branch kits 10 7 5 System piping length limita...

Page 5: ...REYQ120XATJU XAYDU XAYCU 1 REYQ144XATJU XAYDU XAYCU 1 REYQ168XATJU XAYDU XAYCU 1 REYQ192XATJU XAYDU XAYCU 2 REYQ216XATJU XAYDU XAYCU 1 1 REYQ240XATJU XAYDU XAYCU 2 REYQ264XATJU XAYDU XAYCU 1 1 REYQ288...

Page 6: ...343 REYQ288XATJU XAYDU XAYCU 144 374 REYQ312XATJU XAYDU XAYCU 156 405 REYQ336XATJU XAYDU XAYCU 168 436 REYQ360XATJU XAYDU XAYCU 180 468 REYQ384XATJU XAYDU XAYCU 192 499 REYQ408XATJU XAYDU XAYCU 204 53...

Page 7: ...he weight of the unit Installation location is flat to prevent vibrations and noise generation and to have sufficient stability The space around the unit is adequate for maintenance and servic ing ref...

Page 8: ...improper installation may result in the unit turning over 4 2 Weather related precautions Be sure that the air inlet of the unit is not positioned towards the main wind direction Frontal wind will di...

Page 9: ...elow and choose one of the possibilities a b a c d a b a e d e c a b a e d f c a b a e b d c a b a e d f c 1 2 3 5 4 ABCD Sides along the installation site with obstacles Suction side A B C D A B 1 a...

Page 10: ...ons can be found in the Engineering Data Book 6 Inspecting handling and unpacking the unit 6 1 Inspection At delivery the unit must be checked and any damage must be re ported immediately to the carri...

Page 11: ...a tion bolts until their length remains 13 16 in 20 mm above the foundation surface A A 13 16 in 20 mm NOTE There are restrictions on the refrigerant pipe connecting order between outdoor units in the...

Page 12: ...d installation conditions on page 24 are complete Do not use flux when brazing the refrigerant piping Use the phos phor copper brazing filler metal B Cu93P 710 795 ISO 3677 which does not require flux...

Page 13: ...6 4 mm 24 30 36 42 48 54 5 8 in 15 9 mm 3 8 in 9 5 mm 72 3 4 in 19 1 mm 96 7 8 in 22 2 mm 7 4 Selection of refrigerant branch kits For piping example refer to 7 3 Selection of piping size on page 9 W...

Page 14: ...tally paying attention to the installation restrictions indicated in 8 Precautions on refrigerant piping on page 14 Example of connection Outdoor unit side Indoor unit side Branch Selector unit 1 2 1...

Page 15: ...nits H3 16 ft 5 m Allowable length after branch 5 Actual piping length Actual piping length from the first REFNET joint or REFNET header to indoor unit 130 ft 40 m 8 Example 4 d g i 130 ft 40 m 7 b c...

Page 16: ...j k B1 B2 B3 B4 B5 B6 B7 2 s r q Branch Selector units B1 B7 b c d e f g p 130 ft 40 m From outdoor unit to the farthest indoor unit 9 From outdoor unit to the nearest indoor unit 1 2 The total pipin...

Page 17: ...revents the creation of large quantities of oxidized film on the inside of the piping An oxidized film ad versely affects valves and compressors in the refrigerating system and prevents proper operati...

Page 18: ...quid pipe stop valve Suction gas pipe stop value Protective plate Stop valves mounting plate High low pressure gas pipe stop valve 5 Cut off the lower part of the smaller pinched piping with an ap pro...

Page 19: ...ts are the responsibility of the installer field piping 8 2 4 Precautions when connecting piping between outdoor units multiple outdoor units system To connect the piping between outdoor units an opti...

Page 20: ...T header so that it branches horizontally 2 Installation of the multi connection piping kit A 1 B 1 C D 15 C 4 3 4 in 120 mm D 19 11 16 in 500 mm Install the joints horizontally so that the caution la...

Page 21: ...to 8 3 2 How to use the stop valve Check for refrigerant leaks after tightening the service port cover 9 Field wiring NOTE All field wiring and components must be installed by a licensed elec trician...

Page 22: ...AYDU f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V...

Page 23: ...ck operation in installation work onsite settings and so on are done by operating the printed circuit board A1P of Master unit NOTE Do not connect the power wiring to terminals for the transmission wi...

Page 24: ...ating sleeves for con nections See the figure below Crimp style terminal Insulating sleeve Power wire For wiring use the designated power wire and connect firmly then secure to prevent outside pressur...

Page 25: ...r tight test and vacuum drying NOTE Always use nitrogen gas for the air tightness test Absolutely do not open the stop valve until the main power circuit insulation measurement has been completed Meas...

Page 26: ...system again using the vacuum pump for 1 hour to 500 microns or less vacuum drying If the system cannot be evacuated to 500 microns within 2 hours repeat the operation of vacuum break and vacuum dryin...

Page 27: ...access you can remove the service window cover see figure Now you can open the inspection door of the control box cover see figure You can see 3 push buttons and 3 seven segment displays and DIP switc...

Page 28: ...of indoor units which are con nected to the system Result mode 1 setting 10 is addressed and selected return value is monitored information To leave the monitoring function push BS1 one time you will...

Page 29: ...rant charge In case recharge is required refer to the nameplate of the unit It states the type of refrigerant and necessary amount 14 2 Calculating the additional refrigerant charge NOTE The refrigera...

Page 30: ...units BS4Q54T 1 BSQ60T 1 BSQ96T 1 Indoor units FXMQ type 18 1 24 1 30 1 36 2 FXFQ type 36 2 Other 48 1 Liquid piping a f3 4 60 ft e f1 4 15 ft i f3 8 20 ft m f3 8 15 ft r f1 2 10 ft b f5 8 20 ft f f3...

Page 31: ...te Since this refrigerant is a mixed refrigerant adding it in gas form may cause the refrigerant composition to change preventing normal operation Before charging check whether the refrigerant cylinde...

Page 32: ...ank only to the liquid stop valve service port open valve A Make sure that all outdoor unit stop valves as well as valves B and C are closed 1 2 3 4 5 6 A C B 9 8 10 10 11 13 12 14 15 7 1 Gauge manifo...

Page 33: ...stop valves after pre charging the refrigerant Operating with the stop valves closed will damage the compressor 15 Start up and configuration INFORMATION It is important that all information in this c...

Page 34: ...The second method is to enable low noise operation based on an external input For this operation an optional acces sory is required 1 2 shows the status of power consumption limitation operation 1 uni...

Page 35: ...only be effective when the optional external control adaptor DTA104A61 62 is installed Default value 0 To activate this function change 2 12 1 2 18 Fan high static pressure setting In order to increas...

Page 36: ...l signal is sent to the unit this setting defines the level power consumption limitation that will be applied for step 2 The level is according to the table Default value 1 Change 2 31 1 2 or 3 in fun...

Page 37: ...t 50 m the setting 2 49 has to be changed to 1 Other changes limitations to the circuit apply for more information see 7 5 System piping length limitations on page 11 2 62 Cooling and heating capacity...

Page 38: ...ble temp release differential AUX Heater is not allowed to energize when the outdoor ambient temp is recovered by differential below above the AUX Heater Max Allowable Temp AUX Heater Max Allowable te...

Page 39: ...ll automatically be set This will allow the auxiliary or secondary heat source to be automatically energized in the event of a system failure Error codes capable of auto backup are listed in the table...

Page 40: ...nsible mode is comfort feeling for the customer The selection method of indoor units is important and has to be considered as the available capacity is not the same as under basic operation For detail...

Page 41: ...n the situ ation When the request from the indoor units becomes more moderate the system will eventually go to the steady state condition which is defined by the operation method above The start up co...

Page 42: ...d field piping electrical wiring air purge etc See installation manual of the Branch Selector units and the indoor units for details CAUTION Do not insert fingers rods or other objects into the air in...

Page 43: ...ult idle situation is existing see 13 2 Operat ing the push buttons and DIP switches on the printed circuit board on page 24 Push BS2 for 5 seconds or more The unit will start test operation The test...

Page 44: ...n valve malfunction Y6E A7P X10A Check connection on printed circuit board or actuator 32 37 Electronic expansion valve malfunction Y7E A7P X11A Check connection on printed circuit board or actuator F...

Page 45: ...heck connection on printed circuit board or actuator JC 06 08 Low pressure sensor malfunction open circuit S1NPL A1P X31A Check connection on printed circuit board or actuator 07 09 Low pressure senso...

Page 46: ...ng connection are correct refer ring to the wiring diagram for Branch Selector units and correct if there are any errors Check that the DIP switches settings are correct referring to the installation...

Page 47: ...oor unit before starting service operation on the inverter equipment Be careful not to touch the live parts If a fan rotates due to strong wind it may store electricity in the capacitor or in the main...

Page 48: ...is not exceeded in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum charge of refrigerant...

Page 49: ...3P477778 7G EM18A015 1901 HT 00_CV_3P477778 7G indd 2 12 11 2018 4 33 48 PM...

Reviews: