19
3P477778-7G English
•
Make sure the electrical imbalance ratio is no greater than 2%. If it is
larger than this, the unit’s lifespan will be reduced.
If the ratio exceeds 4%, the unit will shut down and an malfunction
code will be displayed on the indoor remote controller.
• Connect the wire securely using designated wire and fix it with
attached clamp without applying external pressure on the terminal
parts (terminal for power wiring, terminal for transmission wiring
and ground terminal).
• If there exists the possibility of reverse-phase, lose phase, mo
-
mentary blackout or the power goes on and off while the product is
operating, attach a reverse-phase protection circuit locally.
Running the product in reverse-phase may break the compressor
and other parts.
9 .1 . Power circuit, safety device and cable requirements
•
Make sure to apply the rated voltage of 208/230V, 460V or 575V for
the unit.
•
A power circuit (see the following table) must be provided for con-
nection of the unit. This circuit must be protected with the required
safety devices, i.e. a main switch, a slow blow fuse on each phase.
•
When using residual current operated circuit breakers, be sure to
use a high-speed type (0.1 seconds or less) 200 mA rated residual
operating current.
•
Use copper conductors only.
•
Use insulated wire for the power cord.
•
Select the power supply cable type and size in accordance with
relevant local and national regulations.
Model name
Phase and
frequency
Voltage
Minimum circuit
amp.
Maximum
overcurrent
protective device
Transmission
line selection
REYQ72XATJU
REYQ96XATJU
REYQ120XATJU
REYQ144XATJU
REYQ168XATJU
REYQ192XATJU
REYQ216XATJU
REYQ240XATJU
REYQ264XATJU
REYQ288XATJU
REYQ312XATJU
REYQ336XATJU
REYQ360XATJU
REYQ384XATJU
REYQ408XATJU
REYQ432XATJU
REYQ456XATJU
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
38.1
38.1
43.0
58.3
61.9
38.1+38.1
38.1+43.0
43.0+43.0
43.0+58.3
58.3+58.3
58.3+61.9
61.9+61.9
43.0+43.0+43.0
43.0+43.0+58.3
43.0+58.3+58.3
58.3+58.3+58.3
58.3+58.3+61.9
45
45
50
70
70
45+45
45+50
50+50
50+70
70+70
70+70
70+70
50+50+50
50+50+70
50+70+70
70+70+70
70+70+70
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
REYQ72XAYDU
REYQ96XAYDU
REYQ120XAYDU
REYQ144XAYDU
REYQ168XAYDU
REYQ192XAYDU
REYQ216XAYDU
REYQ240XAYDU
REYQ264XAYDU
REYQ288XAYDU
REYQ312XAYDU
REYQ336XAYDU
REYQ360XAYDU
REYQ384XAYDU
REYQ408XAYDU
REYQ432XAYDU
REYQ456XAYDU
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
18.9
21.1
21.1
27.9
31.1
21.1+21.1
21.1+21.1
21.1+21.1
21.1+27.9
27.9+27.9
27.9+31.1
31.1+31.1
21.1+21.1+21.1
21.1+21.1+27.9
21.1+27.9+27.9
27.9+27.9+27.9
27.9+27.9+31.1
25
25
25
40
40
25+25
25+25
25+25
25+40
40+40
40+40
40+40
25+25+25
25+25+40
25+40+40
40+40+40
40+40+40
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
REYQ72XAYCU
REYQ96XAYCU
REYQ120XAYCU
REYQ144XAYCU
REYQ168XAYCU
REYQ192XAYCU
REYQ216XAYCU
REYQ240XAYCU
REYQ264XAYCU
REYQ288XAYCU
REYQ312XAYCU
REYQ336XAYCU
REYQ360XAYCU
REYQ384XAYCU
REYQ408XAYCU
REYQ432XAYCU
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
f
3,
60Hz
575V
575V
575V
575V
575V
575V
575V
575V
575V
575V
575V
575V
575V
575V
575V
575V
15.1
16.8
18.2
22.3
24.9
16.8+16.8
16.8+18.2
18.2+18.2
18.2+22.3
22.3+22.3
22.3+24.9
24.9+24.9
18.2+18.2+18.2
18.2+18.2+22.3
18.2+22.3+22.3
22.3+22.3+22.3
20
20
25
30
30
20+20
20+25
25+25
25+30
30+30
30+30
30+30
25+25+25
25+25+30
25+30+30
30+30+30
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
9 .2 . Wiring connection example for whole system
1 1
2
3
4
3
7
8
5
6
2
1
2
3
4
5
6
7
8
Power supply
Main switch
Fuse or circuit breaker
Outdoor unit
COOL/HEAT selector
Remote controller
Indoor unit
Branch Selector unit
This image is intended as an example only. Please follow local and
national electrical code.
NOTE
•
Make sure the low voltage wiring (i.e. for the remote controller, between
units) and the power wiring do not pass near each other, keeping them at
least 2 in. (51 mm) apart.
Proximity may cause electrical interference, malfunctions, and breakage.
•
Be sure to connect the power wiring to the power wiring terminal block
and secure it as described in 9.5. Power wiring connection procedure.
•
Transmission wiring should be secured as described in 9.4. Trans-
mission wiring connection procedure.
•
Secure wiring with clamp such as insulation lock ties to avoid con-
tact with piping.
• Shape the wires to prevent the structure such as the control box
cover deforming. And close the cover firmly.
• All field wiring is to be procured on site.
9 .3 . leading wire procedure
•
The power wiring and ground wiring are passed out from the power
wiring hole on the front (knock hole).
•
The transmission wiring is passed out from the wiring hole (knock
hole) on the front of the unit.
1
2
3
4
1
2
3
4
Wiring diagram printed on the back of the control box cover.
Knockout hole
Power line
Transmission line
01_EN_3P477778-7G.indb 19
1/15/2019 10:58:13