Configuration
Installer and user reference guide
135
REYQ8~20+REMQ5U7Y1B
VRV IV+ heat recovery
4P561154-1A – 2020.10
[2‑45]
Technical cooling.
[2‑45]
Description
0 (default)
No technical cooling available
1
Technical cooling available
For more information about this setting, refer to the service manual.
[2‑47]
T
e
target temperature during heat recovery operation.
[2‑47]
T
e
target (°C)
0 (default)
Auto
2
6
3
7
4
8
5
9
6
10
7
11
[2‑49]
Height difference setting.
[2‑49]
Description
0 (default)
—
1
In case the outdoor unit is installed in the highest
position (indoor units are installed on a lower position
than outdoor units) and the height difference between
the lowest indoor unit and the outdoor unit exceeds
50 m, the setting [2‑49] has to be changed to 1.
Other changes/limitations to the circuit apply. For more information see
outdoor units and standard multi-outdoor-unit combinations >20 HP"
76] and
"Standard multi-outdoor-unit combinations ≤20 HP and free multi-outdoor-unit
combinations"
79].
[2‑81]
Cooling comfort setting.
This setting is used in conjunction with setting [2‑8].
[2‑81]
Cooling comfort setting
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
For more information and advice about the impact of these settings, see