20
|
Configuration
Installer and user reference guide
131
REYQ8~20+REMQ5U7Y1B
VRV IV+ heat recovery
4P561154-1A – 2020.10
[2‑12]
Description
0 (default)
Deactivated.
1
Activated.
[2‑14]
Input additional refrigerant amount that was charged.
In case you want to use the automatic leak detection functionality, it is required to
input the total additional refrigerant charge amount.
[2‑14]
Additional amount charged (kg)
0 (default)
No input
1
0<x<5
2
5<x<10
3
10<x<15
4
15<x<20
5
20<x<25
6
25<x<30
7
30<x<35
8
35<x<40
9
40<x<45
10
45<x<50
11
50<x<55
12
55<x<60
13
60<x<65
14
65<x<70
15
70<x<75
16
75<x<80
17
80<x<85
18
85<x<90
19
Setting cannot be used. Total refrigerant charge has to
be <100 kg.
20
21
▪
For details concerning the charging procedure, see
▪
For details concerning the calculation of additional refrigerant charge amount,
see
"To determine the additional refrigerant amount"
98].
▪
For guidance concerning the input of the additional refrigerant charge amount
and leak detection function see
"20.4 Using the leak detection function"
143].
[2‑18]
Fan high static pressure setting.