19
|
Electrical installation
Installer and user reference guide
115
REYQ8~20+REMQ5U7Y1B
VRV IV+ heat recovery
4P561154-1A – 2020.10
Single outdoor unit
Model
Minimum circuit
ampacity
Recommended fuses
REMQ5
16.1 A
20 A
REYQ8
16.1 A
20 A
REYQ10
22.0 A
25 A
REYQ12
24.0 A
32 A
REYQ14
27.0 A
32 A
REYQ16
31.0 A
40 A
REYQ18
35.0 A
40 A
REYQ20
39.0 A
50 A
Multi outdoor units
Model
Minimum circuit
ampacity
Recommended fuses
REYQ10
30.0 A
40 A
REYQ13
30.0 A
40 A
REYQ16
30.0 A
40 A
REYQ18
37.0 A
50 A
REYQ20
39.0 A
50 A
REYQ22
46.0 A
63 A
REYQ24
46.0 A
63 A
REYQ26
51.0 A
63 A
REYQ28
55.0 A
63 A
REYQ30
59.0 A
80 A
REYQ32
62.0 A
80 A
REYQ34
66.0 A
80 A
REYQ36
70.0 A
80 A
REYQ38
74.0 A
100 A
REYQ40
81.0 A
100 A
REYQ42
84.0 A
100 A
REYQ44
86.0 A
100 A
REYQ46
89.0 A
100 A
REYQ48
93.0 A
125 A
REYQ50
97.0 A
125 A
REYQ52
101.0 A
125 A
REYQ54
105.0 A
125 A
For all models:
▪
Phase and frequency: 3N~ 50 Hz
▪
Voltage: 380~415 V